97
AYK550-UH User’s Manual
Start-Up
Group 31: Automatic Reset
This group defines conditions for automatic resets. An automatic reset occurs after a particular fault is
detected. The drive holds for a set delay time, then automatically restarts. You can limit the number of
resets in a specified time period, and you can set up automatic resets for a variety of faults.
Group 31: Automatic Reset
Code Description Range
Resolution
Default
S
3101
NR OF TRIALS
0…5
1
5
Sets the number of allowed automatic resets within a trial period defined by 3102
TRIAL
TIME
.
• If the number of automatic resets exceeds this limit (within the trial
time), the drive prevents additional automatic resets and remains
stopped.
• Starting then requires a successful reset performed from the control
panel or from a source selected by 1604
FAULT
RESET
SEL
.
Example:
Three faults have occurred in the trial time. The last is reset
only if the value for 3101
NR
OF
TRIALS
is 3 or more.
3102
TRIAL TIME
1.0…600.0 s
0.1 s
30.0 s
Sets the time period used for counting and limiting the number of resets.
• See 3101
NR
OF
TRIALS
.
3103
DELAY TIME
0.0…120.0 s
0.1 s
6.0 s
Sets the delay time between a fault detection and attempted drive restart.
• If
DELAY
TIME
= zero, the drive resets immediately.
3104
AR OVERCURRENT
0, 1
1
0
Sets the automatic reset for the overcurrent function on or off.
0 =
DISABLE
– Disables automatic reset.
1 =
ENABLE
– Enables automatic reset.
• Automatically resets the fault (
OVERCURRENT
) after the delay set by 3103
DELAY
TIME
, and the drive resumes
normal operation.
3105
AR OVERVOLTAGE
0, 1
1
1
Sets the automatic reset for the overvoltage function on or off.
0 =
DISABLE
– Disables automatic reset.
1 =
ENABLE
– Enables automatic reset.
• Automatically resets the fault (
DC
OVERVOLT
) after the delay set by 3103
DELAY
TIME
, and the drive resumes
normal operation.
3106
AR UNDERVOLTAGE
0, 1
1
1
Sets the automatic reset for the undervoltage function on or off.
0 =
DISABLE
– Disables automatic reset.
1 =
ENABLE
– Enables automatic reset.
• Automatically resets the fault (
DC
UNDERVOLTAGE
) after the delay set by 3103
DELAY
TIME
, and the drive resumes
normal operation.
3107
AR AI<MIN
0, 1
1
1
Sets the automatic reset for the analog input less than minimum value function on or off.
0 =
DISABLE
– Disables automatic reset.
1 =
ENABLE
– Enables automatic reset.
• Automatically resets the fault (
AI
<
MIN
) after the delay set by 3103
DELAY
TIME
, and the drive resumes normal
operation.
Warning! When the analog input signal is restored, the drive may restart, even after a long stop. Make sure
that automatic, long delayed starts will not cause physical injury and/or damage equipment.
3108
AR EXTERNAL FLT
0, 1
1
1
Sets the automatic reset for external faults function on or off.
0 =
DISABLE
– Disables automatic reset.
1 =
ENABLE
– Enables automatic reset.
• Automatically resets the fault (
EXTERNAL
FAULT
1 or
EXTERNAL
FAULT
2) after the delay set by 3103
DELAY
TIME
,
and the drive resumes normal operation.
X
X X
Time
Trial time
x = Automatic reset
Summary of Contents for AYK 550
Page 256: ...D1 AYK550 UH User s Manual Appendix D Appendix D Base Drive Drawing 205662 Drawings Fig 1...
Page 257: ...AYK550 UH User s Manual D2 Appendix D Base Drive w Fused Disconnect Drawing 205648 Fig 2...
Page 258: ...D3 AYK550 UH User s Manual Appendix D Base Drive w Non Fused Disconnect Drawing 205647 Fig 3...