Start-Up
Group 51: Ext Comm Module
This group defines set-up variables for a fieldbus adaptor (FBA) communication
module. For more information on these parameters, refer to the user’s manual
supplied with the FBA module. FBAs are modules that plug into the drive.
Group 51: Ext Comm Module
Code Description Range
Resolution
Default
S
5101
FBA TYPE
-
1
0
Displays the type of the connected fieldbus adapter module.
0 =
NOT
DEFINED
– Module not found, or not properly connected, or parameter 9802 is not set to 4 (ex
T
FBA
).
1 =
PROFIBUS
-
DP
–
16 =
INTERBUS
–
21 =
LONWORKS
–
32 =
CANOPEN
–
37 =
DEVICENET
–
64 =
MODBUS
PLUS
–
101 =
CONTROLNET
–
128 =
ETHERNET
–
5102
…
5126
FB PAR 2…FB PAR 26
0...65535
1
0
For more information on these parameters, refer to the user’s manual supplied with the FBA module.
5127
FBA PAR REFRESH
0, 1
1
0
Validates any changed fieldbus parameter settings.
• After refreshing, the value reverts automatically to DONE.
5128
FILE CPI FW REV
0000…FFFF hex
1
0000 hex
Displays the CPI firmware revision of the drive’s fieldbus adapter configuration file. Format is xyz where:
• x = major revision number
• y = minor revision number
• z = correction number
Example:
107 = revision 1.07
5129
FILE CONFIG ID
0000…FFFF hex
1
0000 hex
Displays the revision of the drive’s fieldbus adapter module’s configuration file identification.
• File configuration information is drive application program-dependent.
5130
FILE CONFIG REV
0000…FFFF hex
1
0000 hex
Contains the revision of the drive’s fieldbus adapter module configuration file.
Example:
1 = revision 1
5131
FBA STATUS
0…6
1
0
Contains the status of the adapter module.
0 =
IDLE
– Adapter not configured.
1 =
EXEC
.
INIT
– Adapter is initializing.
2 =
TIME
OUT
– A timeout has occurred in the communication between the adapter and the drive.
3 =
CONFIG
ERROR
– Adapter configuration error.
• The major or minor revision code of the adapter’s CPI firmware revision differs from that stated in the drive’s
configuration file.
4 =
OFF
-
LINE
– Adapter is off-line.
5 =
ON
-
LINE
– Adapter is on-line.
6 =
RESET
– Adapter is performing a hardware reset.
5132
FBA CPI FW REV
0000…FFFF hex
1
0000 hex
Contains the revision of the module’s CPI program. Format is xyz where:
• x = major revision number
• y = minor revision number
• z = correction number
Example:
107 = revision 1.07