AYK550-UH User’s Manual
Serial Communication – EFB
The following diagram shows the drives’ integration to the Johnson Controls
Metasys Companion system.
On the N2 Fieldbus each AYK550 drive can be accessed by the full complement of
Metasys FMS features, including Change-of-State (COS) monitoring, alarm
notification, scheduling, trend, and totalization.
On one N2 Fieldbus segment there can be up to 32 nodes while integrating AYK550
drives with Johnson Controls Metasys.
Drive Device Type
For the Metasys and Metasys Companion products, the device type for the AYK550
drive is VND.
N2 Analog Input Objects
The following table lists all of the N2 Analog Input objects defined for the AYK550
drive.
N2 Analog Inputs:
Number
Object
Drive
Parameter
Scale
Factor
Units
Range
AI1
OUTPUT FREQUENCY
0103
10
Hz
0…250
AI2
RATED SPEED
Note 1
10
%
0 …100
AI3
SPEED
0102
1
rpm
0 …9999
AI4
CURRENT
0104
10
A
0…9999
AI5
TORQUE
0105
10
%
-200…200
AI6
POWER
0106
10
kW
0…9999
AI7
DRIVE TEMPERATURE
0110
10
°
C
0 …125
AI8
KILOWATT HOURS
0115
1
kWh
0…9999
PC-Version
Converter
Panel Version/LTD
N2 Fieldbus
PC Version
Panel Version/LTD
RS232 -RS485 Converter