232
AYK550-UH User’s Manual
Technical Data
• Longer than 30 m (100 ft) must be limited as specified in the table below. Follow
the instructions in the filter package for all cable screen connections.
Warning! Do not use filters in a floating, or high impedance earthed network.
Cable Requirements for CE Compliance
Drive Type
RFI/EMC Filter
Switching Frequency (Parameter 2606)
1 or 4 kHz (1 or 4)
8 kHz (8)
Maximum motor cable length
AYK550-UH
-03A3-4
ACS400-IF11-3
100 m
(330 ft)
Not CE compliant for
more than 30 m
AYK550-UH
-04A1-4
AYK550-UH
-06A9-4
AYK550-UH
-08A8-4
AYK550-UH
-012A-4
AYK550-UH
-015A-4
ACS400-IF21-3
100 m
(330 ft)
100 m
(330 ft)
AYK550-UH
-023A-4
AYK550-UH
-031A-4
ACS400-IF31-3
100 m
(330 ft)
100 m
(330 ft)
AYK550-UH
-038A-4
AYK550-UH
-044A-4
ACS400-IF41-3
100 m
(330 ft)
100 m
(330 ft)
AYK550-UH
-059A-4
AYK550-UH
-072A-4
AYK550-UH
-077A-4
…
AYK550-UH
-180A-4
Not defined at time of publication.