36
AYK550 User’s Manual
Start-Up
Condenser
This macro configures for condenser and liquid cooler applications where fan speed
is controlled according to signals received from a transducer. When using direct
speed reference in AUTO mode or process PID, see "General Considerations" on
page 30.
Parameters Changed Relative to HVAC Default
Parameter
Value
Parameter
Value
9902
APPLIC
MACRO
5 (
CONDENSER
)
2203
DECELER
TIME
1
10.0 s
1401
RELAY
OUTPUT
1
7 (
STARTED
)
3207
SUPERV
3
PARAM
0103 (
OUTPUT
FREQ
)
1601
RUN
ENABLE
2 (
DI
2)
4005
ERROR
VALUE
INV
1 (
YES
)
1609
START
ENABLE
2
5 (
DI
5)
4101
GAIN
1.0
2202
ACCELER
TIME
1
10.0 s
4102
INTEGRATION
TIME
60.0 s
1 SCR
2 AI1
3 AGND
4 10V
5 AI2
6 AGND
7 AO1
8 AO2
9 AGND
10 24V
11 GND
12 DCOM1
13 DI1
14 DI2
15 DI3
16 DI4
17 DI5
18 DI6
19 RO1C
20 RO1A
21 RO1B
22 RO2C
23 RO2A
24 RO2B
25 RO3C
26 RO3A
27 RO3B
X1
+
mA
mA
External reference
0(2)…10 V or 0(4)…20 mA
Reference voltage 10 VDC
Output frequency:
0(4)…20 mA
Start/Stop:
Activate to start drive
Run permissive:
Deactivate to stop drive (P 1601)
Constant (Preset) speed 1
(P 1202
1
)
Safety interlock 1:
Deactivate to stop drive (P 1608)
Safety interlock 2:
Deactivate to stop drive (P 1609)
Relay output 1 (P 1401)
Default operation:
Ready
=>19 connected to 21
Relay output 2 (P 1402)
Default operation:
Running
=>22 connected to 24
Relay output 3 (P 1403)
Default operation:
Fault (-1)
=>25 connected to 27
Output current:
0(4)…20 mA
Not configured
Analog input circuit common
PID feedback:
0(2)…10 V or 0(4)…20 mA
Analog output circuit common
Auxiliary voltage 24 VDC
Common for DI return signals.
Digital input common for all
Signal cable shield (screen)
Analog input circuit common
(Fault => 25 connected to 26)
J1
AI1: 0(2)
…
10 V
AI2: 0(4)
…
20 mA
ON
ON
Jumper Settings
+
Summary of Contents for AYK 550
Page 256: ...D1 AYK550 UH User s Manual Appendix D Appendix D Base Drive Drawing 205662 Drawings Fig 1...
Page 257: ...AYK550 UH User s Manual D2 Appendix D Base Drive w Fused Disconnect Drawing 205648 Fig 2...
Page 258: ...D3 AYK550 UH User s Manual Appendix D Base Drive w Non Fused Disconnect Drawing 205647 Fig 3...