44
AYK550 User’s Manual
Start-Up
E-bypass
This macro configures for an Electronic Bypass device which can bypass the drive
and connect the motor direct on-line. When using direct speed reference in AUTO
mode or process PID, see "General Considerations" on page 30.
Note!
Does not apply to YORK configured packages.
Parameters Changed Relative to HVAC Default
Parameter
Value
Parameter
Value
9902
APPLIC
MACRO
13 (
E
-
BYPASS
)
1608
START
ENABLE
1
0 (
NOT
SEL
)
1201
CONST
SPEED
SEL
0 (
NOT
SEL
)
2108
START
INHIBIT
1 (
ON
)
1401
RELAY
OUTPUT
1
7 (
STARTED
)
3207
SUPERV
3
PARAM
0103 (
OUTPUT
FREQ
)
1601
RUN
ENABLE
2 (
DI
2)
1 SCR
2 AI1
3 AGND
4 10V
5 AI2
6 AGND
7 AO1
8 AO2
9 AGND
10 24V
11 GND
12 DCOM1
13 DI1
14 DI2
15 DI3
16 DI4
17 DI5
18 DI6
19 RO1C
20 RO1A
21 RO1B
22 RO2C
23 RO2A
24 RO2B
25 RO3C
26 RO3A
27 RO3B
X1
+
mA
mA
External reference
0(2)…10 V or 0(4)…20 mA
Reference voltage 10 VDC
Output frequency:
0(4)…20 mA
Start/Stop:
Activate to start drive
Run enable:
Deactivate to stop drive (P 1601)
Not configured
Not configured
Not configured
Relay output 1 (P 1401)
Default operation:
Started
=>19 connected to 21
Relay output 2 (P 1402)
Default operation:
Running
=>22 connected to 24
Relay output 3 (P 1403)
Default operation:
Fault (-1)
=>25 connected to 27
Output current:
0(4)…20 mA
Not configured
Analog input circuit common
PID feedback:
0(2)…10 V or 0(4)…20 mA
Analog output circuit common
Auxiliary voltage 24 VDC
Common for DI return signals.
Digital input common for all
Signal cable shield (screen)
Analog input circuit common
(Fault => 25 connected to 26)
J1
AI1: 0(2)
…
10 V
AI2: 0(4)
…
20 mA
ON
ON
Jumper Settings
+