AYK550-UH User’s Manual
50
Start-Up
Group 01: Operating Data
This group contains drive operating data, including actual signals. The drive sets the
values for actual signals, based on measurements or calculations. You cannot set
these values.
Group 01: Operating Data
Code Description Range
Resolution
Default
S
0102
SPEED
0…30000 rpm
1 rpm
-
The calculated speed of the motor (rpm).
0103
OUTPUT FREQ
0.0…500.0 Hz
0.1 Hz
-
The frequency (Hz) applied to the motor. (Also shown by default in OUTPUT display.)
0104
CURRENT
0.0…1.5*I
2N
0.1 A
-
The motor current, as measured by the AYK550. (Also shown by default in OUTPUT display.)
0105
TORQUE
-200…200%
0.1%
-
Output torque. Calculated value of torque on motor shaft in % of motor nominal torque.
0106
POWER
-1.5…1.5*P
N
0.1 kW
-
The measured motor power in kW.
0107
DC BUS VOLTAGE
0…2.5*V
dN
1 V
-
The DC bus voltage in VDC, as measured by the AYK550.
0109
OUTPUT VOLTAGE
0…2.0*V
dN
1 V
-
The voltage applied to the motor.
0110
DRIVE TEMP
0…150
°
C
0.1
°
C
-
The temperature of the drive heatsink in Centigrade.
0111
EXTERNAL REF 1
0…30000 rpm /
1 rpm /
-
0…500 Hz
0.1 Hz
External reference,
REF
1, in rpm or Hz – units determined by parameter 9904.
0112
EXTERNAL REF 2
0…100%
0.1%
-
(torque: 0…600%)
External reference,
REF
2, in %.
0113
CTRL LOCATION
0…2
1
-
Active control location. Alternatives are:
0 =
HAND
1 =
EXT
1
2 =
EXT
2
0114
RUN TIME (R)
0…9999 h
1 h
0 h
The drive’s accumulated running time in hours (h).
• Can be
reset
by pressing UP and DOWN buttons simultaneously when in parameter set mode.
0115
KWH COUNTER (R)
0…9999 kWh
1 kWh
-
The drive’s accumulated power consumption in kilowatt hours.
• Can be
reset
by pressing UP and DOWN buttons simultaneously when in parameter set mode.
0116
APPL BLK OUTPUT
0…100%
0.1%
-
(torque: 0…600%)
Application block output signal. Value is from either:
• PFA control, if PFA Control is active, or
• Parameter 0112
EXTERNAL
REF
2.
Summary of Contents for AYK 550
Page 256: ...D1 AYK550 UH User s Manual Appendix D Appendix D Base Drive Drawing 205662 Drawings Fig 1...
Page 257: ...AYK550 UH User s Manual D2 Appendix D Base Drive w Fused Disconnect Drawing 205648 Fig 2...
Page 258: ...D3 AYK550 UH User s Manual Appendix D Base Drive w Non Fused Disconnect Drawing 205647 Fig 3...