AYK550-UH User’s Manual
Start-Up
0305
FAULT WORD 1
-
1
0000 hex
Read-only copy of the Fault Word 1.
• When a fault is active, the corresponding bit for the active fault is set in the Fault Words.
• EAYK fault has a dedicated bit allocated within Fault Words.
• See
"Fault Listing"
in section
"Diagnostics"
for a description of the faults.
• The control panel displays the word in hex. For example, all zeros and a 1 in Bit 0 displays a 0001. All zeros and a
1 in Bit 15 displays as 8000.
0306
FAULT WORD 2
-
1
0000 hex
Read-only copy of the Fault Word 2.
• See parameter 0305.
0307
FAULT WORD 3
-
1
0000 hex
Read-only copy of the Fault Word 3.
• See parameter 0305.
Group 03: Actual Signals
Code Description Range
Resolution
Default
S
Bit # 0305,
FAULT
WORD
1 0306,
FAULT
WORD
2 0307,
FAULT
WORD
3
0
OVERCURRENT
UNDERLOAD EFB
1
1
DC OVERVOLT
THERM FAIL
EFB 2
2
DEV OVERTEMP
OPEX LINK
EFB 3
3
SHORT CIRC
OPEX PWR
Reserved
4
OVERLOAD CURR
MEAS Reserved
5
DC UNDERVOLT
SUPPLY PHASE
Reserved
6
AI1 LOSS
Reserved
Reserved
7
AI2 LOSS
OVERSPEED
Reserved
8
MOT OVERTEMP
DC HIGH RUSH
Reserved
9 PANEL
LOSS
DRIVE
ID
Reserved
10 ID RUN FAIL
CONFIG FILE
Reserved
11 MOTOR STALL
SERIAL 1 ERR
System Error
12 Reserved
EFB CON FILE
System Error
13 EXT FLT 1
FORCE TRIP
System Error
14 EXT FLT 2
MOTOR PHASE
Hardware Error
15
EARTH FAULT
OUTPUT WIRING
Param. Setting Fault