65
AYK550-UH User’s Manual
Start-Up
12 =
DI
1,2,3 – Selects one of seven Constant Speeds (1…7) using
DI
1,
DI
2 and
DI
3.
• Uses three digital inputs, as defined below (0 =
DI
de-activated, 1 =
DI
activated):
13 =
DI
3,4,5 – Selects one of seven Constant Speeds (1…7) using
DI
3,
DI
4 and
DI
5.
• See above (
DI
1,2,3) for code.
14 =
DI
4,5,6 – Selects one of seven Constant Speeds (1…7) using
DI
5,
DI
6 and
DI
7.
• See above (
DI
1,2,3) for code.
15…18 =
TIMER
1…4 – Specifies the timer used to select a Constant Speed as the reference. The reference
selection depends on the state of the selected timer, and the value of 1209
TIMED
MODE
SEL
. See table. To enable
and set timers, see Group 36, Timer Functions.
19 =
TIMER
1&2 – Specifies that Timers 1 and 2 are used together to select a Constant Speed as the reference. The
reference selection depends on the states of these timers, and the value of 1209
TIMED
MODE
SEL
. See table. To
enable and set timers, see Group 36, Timer Functions.
-1 =
DI
1(
INV
) – Selects Constant Speed 1 with digital input
DI
1.
• Inverse operation: Digital input de-activated = Constant Speed 1 activated.
-2…- 6 =
DI
2(
INV
)…
DI
6(
INV
) – Selects Constant Speed 1 with digital input. See above.
-7 =
DI
1,2(
INV
) – Selects one of three Constant Speeds (1…3) using
DI
1 and
DI
2.
• Inverse operation uses two digital inputs, as defined below (0 =
DI
de-activated, 1 =
DI
activated):
-8 =
DI
2,3(
INV
) – Selects one of three Constant Speeds (1…3) using
D
i2 and
DI
3.
• See above (
DI
1,2(
INV
)) for code.
-9 =
DI
3,4(
INV
) – Selects one of three Constant Speeds (1…3) using
DI
3 and
DI
4.
• See above (
DI
1,2(
INV
)) for code.
-10 =
DI
4,5(
INV
) – Selects one of three Constant Speeds (1…3) using
DI
4 and
DI
5.
• See above (
DI
1,2(
INV
)) for code.
-11 =
DI
5,6(
INV
) – Selects one of three Constant Speeds (1…3) using
DI
5 and
DI
6.
• See above (
DI
1,2(
INV
)) for code.
Group 12: Constant Speeds
Code
Description Range
Resolution
Default
S
DI
1
DI
2
DI
3
Function
0
0
0
No constant speed
1
0
0
Constant speed 1 (1202)
0
1
0
Constant speed 2 (1203)
1
1
0
Constant speed 3 (1204)
0
0
1
Constant speed 4 (1205)
1
0
1
Constant speed 5 (1206)
0
1
1
Constant speed 6 (1207)
1
1
1
Constant speed 7 (1208)
1201 = 15 16 17 18
Reference
Timer: 1 2 3 4
1209 = 1
1209 = 2
Timer
State
0
External reference Constant Speed 1
1
Constant Speed 1 Constant Speed 2
1201 = 19
Reference
Timer 1 Timer 2
(used together)
1209 = 1
1209 = 2
0
0
External reference Constant Speed 1
1
0
Constant Speed 1 Constant Speed 2
0
1
Constant Speed 2 Constant Speed 3
1
1
Constant Speed 3 Constant Speed 4
DI
1
DI
2
Function
1
1 No constant speed
0
1 Constant speed 1 (1202)
1
0 Constant speed 2 (1203)
0
0 Constant speed 3 (1204)