AYK550-UH User’s Manual
68
Start-Up
Group 14: Relay Outputs
This group defines the condition that activates each of the relay outputs.
Group 14: Relay Outputs
Code
Description Range
Resolution
Default
S
1401
RELAY OUTPUT 1
0…45
1
1
Defines the event or condition that activates relay 1 – what relay output 1 means.
0 =
NOT
SEL
– Relay is not used and is de-energized.
1 =
READY
– Energize relay when drive is ready to function. Requires:
• Run enable signal present.
• No faults exist.
• Supply voltage is within range.
• Emergency Stop command is not on.
2 =
RUN
– Energize relay when the drive is running.
3 =
FAULT
(-1) – Energize relay when power is applied. De-energizes when a fault occurs.
4 =
FAULT
– Energize relay when a fault is active.
5 =
ALARM
– Energize relay when an alarm is active.
6 =
REVERSED
– Energize relay when motor rotates in reverse direction.
7 =
STARTED
– Energize relay when drive receives a start command (even if Run Enable signal is not present). De-
energized relay when drive receives a stop command or a fault occurs.
8 =
SUPRV
1
OVER
– Energize relay when first supervised parameter (3201) exceeds the limit (3203).
• See "Group 32: Supervision" starting on page 98.
9 = suprv1 under – Energize relay when first supervised parameter (3201) drops below the limit (3202).
• See "Group 32: Supervision" starting on page 98.
10 = suprv2 over – Energize relay when second supervised parameter (3204) exceeds the limit (3206).
• See "Group 32: Supervision" starting on page 98.
11 = suprv2 under – Energize relay when second supervised parameter (3204) drops below the limit (3205).
• See "Group 32: Supervision" starting on page 98.
12 = suprv3 over – Energize relay when third supervised parameter (3207) exceeds the limit (3209).
• See "Group 32: Supervision" starting on page 98.
13 = suprv3 under – Energize relay when third supervised parameter (3207) drops below the limit (3208).
• See "Group 32: Supervision" starting on page 98.
14 =
AT
SET
POINT
– Energize relay when the output frequency is equal to the reference frequency.
15 =
FAULT
(
RST
) – Energize relay when the drive is in a fault condition and will reset after the programmed auto-
reset delay.
• See parameter 3103 delay time.
16 =
FLT
/
ALARM
– Energize relay when fault or alarm occurs.
17 =
EXT
CTRL
– Energize relay when external control is selected.
18 =
REF
2
SEL
– Energize relay when
EXT
2 is selected.
19 =
CONST
FREQ
– Energize relay when a constant speed is selected.
20 =
REF
LOSS
– Energize relay when reference or active control place is lost.
21 =
OVERCURRENT
– Energize relay when an overcurrent alarm or fault occurs.
22 =
OVERVOLTAGE
– Energize relay when an overvoltage alarm or fault occurs.
23 =
DRIVE
TEMP
– Energize relay when a drive overtemperature alarm or fault occurs.
24 =
UNDERVOLTAGE
– Energize relay when an undervoltage alarm or fault occurs.
25 =
AI
1
LOSS
– Energize relay when
AI
1 signal is lost.
26 =
AI
2
LOSS
– Energize relay when
AI
2 signal is lost.
27 =
MOTOR
TEMP
– Energize relay when a motor overtemperature alarm or fault occurs.
28 =
STALL
– Energize relay when a stall alarm or fault exists.
29 =
UNDERLOAD
– Energize relay when an underload alarm or fault occurs.
30 =
PID
SLEEP
– Energize relay when the PID sleep function is active.
31 =
PFA
– Use relay to start/stop motor in PFA control (See Group 81: PFA Control).
• Use this option only when PFA control is used.
• Selection activated / deactivated when drive is not running.
32 =
AUTOCHANGE
– Energize relay when PFA autochange operation is performed.
• Use this option only when PFA control is used.
33 =
FLUX
READY
– Energize relay when the motor is magnetized and able to supply nominal torque (motor has
reached nominal magnetizing).
34 =
USER
S
2 – Energize relay when User Parameter Set 2 is active.