16

AYK550 QUICK START

Start-Up

YORK INTERNATIONAL

Application Macros 

Overview

Macros change a group of parameters to new, predefined values designed for 
specific applications. Use macros to minimize the need for manual editing of 
parameters. Selecting a macro sets all other parameters to their default values, 
except:

Group 99: Start-up Data parameters

The 

PARAMETER LOCK

 1602

The 

PARAM SAVE

 1607

Groups 50…52 serial communication parameters

Group 29: Maintenance triggers

After selecting a macro, additional parameter changes can be made manually using 
the control panel.

Application macros are enabled by setting the value for parameter 9902 

APPLIC

MACRO

. By default, HVAC default (value 1) is the enabled macro.

General Considerations

The following considerations apply for all macros:

When using a direct speed reference in AUTO mode, connect the speed 
reference to analog input 1 (AI1), and provide the START command using digital 
input 1 (DI1). In HAND/OFF mode, the control panel provides the speed 
reference and START command.

When using process PID, connect the feedback signal to analog input 2 (AI2). As 
a default, the control panel sets the Setpoint, but analog input 1 can be used as 
an alternate source. You can set up process PID using parameters (Group 40) or 
using the PID control assistant (recommended).

Application / Macro Listing

This section describes the following macros:

9902 

Value

Macro

9902 

Value

Macro

1

HVAC default 

8

Internal timer

2

Supply fan

9

Internal timer with constant speeds

3

Return fan

10

Floating point

4

Cooling tower fan

11

Dual setpoint PID

5

Condenser

12

Dual setpoint PID with constant speeds

6

Booster pump

13

E-bypass

7

Pump alternation

14

Hand Control

Summary of Contents for AYK 550

Page 1: ...AYK 550 AIR MODULATOR Supersedes Nothing Form 100 42 NO1 U QUICK START UQUICK START AYK550 UH HVAC DRIVES 1 150HP...

Page 2: ...50 UH QUICK START Table of Contents YORK INTERNATIONAL Table of Contents Safety Use of Warnings and Notes 1 Start Up HVAC Control Panel Features 3 Start Up 5 Modes 6 Application Macros 16 YORK Default...

Page 3: ...QUICK START 0 12 12 0 3 4 3 5 4 2 62 7 5 8 5 0 9 5 8 8 8 7 3 2 62 4 3 2 2 4 Consult YORK AYK550 Users Manual Form 100 42 O1 604...

Page 4: ...ution you about conditions which can result in serious injury or death and or damage to the equipment They also tell you how to avoid the danger The warning symbols are used as follows Dangerous volta...

Page 5: ...g Copy function for moving parameters to other AYK550 drives Backup function for saving parameter sets Context sensitive help Real time clock General Display Features Soft Key Functions The soft key f...

Page 6: ...rameters Individually To change the parameters follow these steps 1 Select MENU to enter the main menu 2 Select ASSISTANTS with the Up Down buttons and select ENTER 3 Scroll to COMMISSION DRIVE with t...

Page 7: ...ge are parameter groups 99 Start up data 10 Start Stop Dir 11 Reference Select 20 Limits 21 Start Stop 22 Accel Decel 26 Motor Control and 30 Fault Functions Note To restore the default factory settin...

Page 8: ...he LCD display shows the basic status information of the drive HAND Indicates that the drive control is local that is from the control panel AUTO Indicates that the drive control is remote such as the...

Page 9: ...the drive press the OFF button Reference To modify the reference only possible if the display in the upper right corner is in reverse video press the UP or DOWN buttons the reference changes immediat...

Page 10: ...10 Start Stop Dir 11 Reference Select 20 Limits 21 Start Stop 22 Accel Decel 26 Motor Control and 30 Fault Functions Note To restore the default factory settings select the application macro HVAC defa...

Page 11: ...ompts for control panel display language selection Prompts for motor data Guides user through rotation check Commission drive Prompts for motor data Application Prompts for application macro selection...

Page 12: ...e the same application Also useful to create a backup for recovery if drive parameters are corrupted or erased Panel Display Prompts for display variable and unit settings Timed Functions Prompts for...

Page 13: ...s to drive follow these steps 1 Select MENU to enter the main menu 2 Select PAR BACKUP with the UP DOWN buttons and select ENTER 3 Scroll to Upload to Panel and select SEL 4 The text Copying parameter...

Page 14: ...Select ABORT if you want to stop the process 5 After the download stops the message Parameter download successful is displayed and the control panel goes back to PAR BACKUP menu Select EXIT to return...

Page 15: ...s visible in Fault logs To set the clock follow these steps 5 The text Parameter download successful is displayed and the control panel returns to PAR BACKUP menu Select EXIT to return to the main men...

Page 16: ...gs with the UP DOWN buttons and select ENTER 3 Scroll to the I O setting you want to view with the UP DOWN buttons and select SEL 4 Select the setting you want to view with the UP DOWN buttons and sel...

Page 17: ...s with the UP DOWN buttons and select ENTER 3 Scroll to the I O setting you want to view with the UP DOWN buttons and select SEL 4 Select the setting you want to view with the UP DOWN buttons and sele...

Page 18: ...llowing considerations apply for all macros When using a direct speed reference in AUTO mode connect the speed reference to analog input 1 AI1 and provide the START command using digital input 1 DI1 I...

Page 19: ...Each macro has specific requirements for control wiring For general details about the AYK550 control wiring terminals see Control Terminal Descriptions on page 238 Specific wiring requirements are in...

Page 20: ...PHWHU 9DOXH 2 5 4 2 B 8 6 4 2 C D 4 2 B8 4 2 25 F 2 B 2 2 6 2 B C 2 D 2 6 5 G 5 B G 5 6 C G WHUQDO UHIHUHQFH H 8 B H 825 2XWSXW IUHTXHQF B H 6WDUW 6WRS RQVWDQW 3UHVHW VSHHG 1 6DIHW LQWHUORFN 2 1 6 D 1...

Page 21: ...0 0 Hz 1503 AO1 Content Max 60 0 Hz 1504 Minimum AO1 4 0 mA 1505 Maximum AO1 20 0 mA 1506 Filter AO1 0 1 s 1507 AO2 Content Sel Current 1508 AO2 Content Min 0 0 Hz 1509 AO2 Content Max 60 0 Hz 1510 Mi...

Page 22: ...le 0 0 4108 Value 0 0 4109 100 Value 100 0 4110 Set Point Set Keypad 4111 Internal Setpnt 40 0 4112 Setpoint Min 0 0 4113 Setpoint Max 100 0 4114 Fbk Sel Act1 4115 Fbk Multiplier 0 000 4116 Act1 Input...

Page 23: ...D D6 1 G Q 1 CB 5 5 B B2 NO1 s Nothing V 1 4 8 2...

Reviews: