567175-YTG-E-0512
Johnson Controls Unitary Products
23
Multipliers for determining the performance with other indoor sections.
NOTE:
For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per
degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Continued on next page.
COOLING PERFORMANCE DATA
OUTDOOR UNIT MODEL NO.
CZF04813(C)
INDOOR COIL MODEL NO.
FC64D
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM
1400
1600
1800
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
65
T.C.
46.0
48.2
47.8
53.2
56.1
47.8
49.4
48.4
53.9
56.6
49.6
50.5
49.1
54.7
57.1
S.C.
46.0
41.7
35.4
35.0
26.2
47.8
44.6
37.4
36.1
27.4
49.6
47.4
39.3
37.3
28.6
KW
2.67
2.67
2.66
2.67
2.68
2.74
2.75
2.74
2.74
2.78
2.81
2.83
2.81
2.82
2.87
75
T.C.
44.2
46.1
46.3
50.8
54.5
45.9
47.3
47.3
51.6
55.2
47.6
48.4
48.2
52.4
55.8
S.C.
44.2
40.8
34.7
34.0
26.0
45.9
43.5
36.6
35.5
27.2
47.6
46.3
38.5
36.9
28.4
KW
3.00
3.01
3.01
3.01
3.01
3.08
3.08
3.08
3.08
3.10
3.15
3.15
3.16
3.15
3.19
85
T.C.
42.3
43.9
44.8
48.5
52.9
44.0
45.1
46.1
49.3
53.7
45.6
46.3
47.3
50.1
54.5
S.C.
42.3
39.9
34.0
33.1
25.7
44.0
42.5
35.9
34.8
27.0
45.6
45.2
37.8
36.6
28.2
KW
3.34
3.35
3.36
3.35
3.35
3.41
3.42
3.43
3.42
3.43
3.49
3.48
3.50
3.49
3.51
95
T.C.
40.5
41.8
43.3
46.2
51.4
42.1
43.0
44.9
47.0
52.3
43.7
44.2
46.4
47.8
53.2
S.C.
40.5
38.9
33.3
32.1
25.4
42.1
41.5
35.2
34.2
26.7
43.7
44.1
37.0
36.3
28.0
KW
3.68
3.69
3.71
3.69
3.68
3.75
3.75
3.78
3.76
3.75
3.82
3.80
3.85
3.83
3.83
105
T.C.
38.0
38.4
40.5
43.4
48.3
39.6
39.5
41.8
44.2
49.2
41.2
40.5
43.1
45.1
50.0
S.C.
38.0
36.6
32.1
31.1
24.2
39.6
38.5
33.9
33.1
25.5
41.2
40.5
35.7
35.2
26.8
KW
4.28
4.27
4.32
4.25
4.24
4.33
4.32
4.38
4.32
4.31
4.38
4.36
4.45
4.39
4.39
115
T.C.
35.5
35.1
37.7
40.7
45.4
37.2
36.0
38.8
41.6
46.1
38.8
36.9
39.9
42.4
46.8
S.C.
35.5
34.3
30.9
30.0
23.0
37.2
35.7
32.7
32.1
24.3
38.8
36.9
34.5
34.2
25.6
KW
4.85
4.84
4.91
4.80
4.78
4.88
4.87
4.97
4.86
4.86
4.91
4.90
5.03
4.93
4.94
125
T.C.
33.1
31.8
34.9
37.9
42.4
34.7
32.6
35.8
38.9
43.0
36.4
33.3
36.7
39.8
43.7
S.C.
33.1
31.8
29.7
29.0
21.8
34.7
32.6
31.5
31.1
23.1
36.4
33.3
33.3
33.1
24.4
KW
5.43
5.40
5.50
5.35
5.32
5.44
5.42
5.55
5.41
5.40
5.45
5.45
5.61
5.47
5.48
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (O INDOOR).
Air Handlers
Coils
T.C.
S.C.
KW
–
FC/MC/PC48
0.96
0.94
1.00
–
FC/MC/PC60
0.96
0.94
1.00
–
FC/MC62
0.97
0.96
1.01
–
HD48
0.96
0.94
1.00
–
HD60
0.98
0.96
1.00
AHE48D
–
0.96
0.97
0.96
AHE60D
–
0.97
0.99
0.93
AHP48
–
0.96
0.94
1.00
AHP60
–
0.98
0.96
0.98
AHR48D
–
0.97
0.95
1.01
AHR60D
–
0.97
0.96
0.99
AV*48
–
0.97
0.98
0.97
AV*60
–
0.97
0.99
0.95
AHX48
–
0.98
1.01
0.96
AHX60
–
0.98
0.99
0.94
F4FV060
–
0.96
0.98
0.96
F6FP048
–
0.97
0.98
0.97
F6FP060
–
0.98
0.99
0.94
MV16C
FC/MC48C
0.96
0.96
0.96
MV20D
FC/MC48D
0.96
0.97
0.94
MV16C
FC/PC60C
0.95
0.96
1.01
MV20D
FC/MC60D
0.96
0.97
0.96
MV20D
FC/MC62D
0.97
0.99
0.95
MV20D
FC64D
1.00
1.05
0.94
MX16C
FC/MC48C
0.96
0.99
0.96
MX20D
FC/MC48D
0.96
0.97
0.92
MX16C
FC/PC60C
0.96
0.96
0.92
MX20D
FC/MC62D
0.98
0.99
0.92
MX20D
FC64D
1.00
1.05
0.93