55
YORK INTERNATIONAL
FORM 201.18-NM9 (602)
OPERATING LIMITATIONS AND SOUND POWER DATA (60 HZ)
7
TABLE 12
60 HZ SOUND POWER DATA
MODEL
Lwa
YCAS
dBA
0218EB
102
0248EB
102
0268EB
104
0288EB
104
0308EB
104
0328EB
105
0358EB
105
0398EB
105
0418EB
105
TABLE 11
OPERATING LIMITATIONS,
60 HZ ENGLISH UNITS
* Maximum Ambient w/ High Ambient Kit is 130°F.
MIN
MAX
LEAVING CHILLED LIQUID TEMP ( °F)
40.1
59
CHILLED WATER TEMP DIFFERENCE ( °F)
5.5
18
WATER SIDE PRESSURE (PSIG)
150
REFRIGERANT SIDE PRESSURE (PSIG)
300
COOLER FLOW
MODEL
GALLONS/MINUTE
YCAS
MIN.
MAX.
0218EB
318
1072
0248EB
318
1072
0268EB
318
1072
0288EB
415
1205
0308EB
415
1205
0328EB
415
1205
0358EB
530
1601
0398EB
530
1601
0418EB
530
1601
AIR
STANDARD FANS
0
115*
ENTERING
HIGH PRESS. FANS
0
115*
CONDENSER (
°
F)
SLOW SPEED FANS
0
115
FAN
STANDARD FANS
20
AVAILABLE STATIC
HIGH PRESS. FANS OPTION 1
85
PRESSURE (Pa)
HIGH PRESS. FANS OPTION 2
150
SLOW SPEED FANS
10
ELECTRICAL THREE PHASE 60 Hz (V)
200
230
380
460
575
Summary of Contents for eco YCAS Series
Page 65: ...65 YORK INTERNATIONAL FORM 201 18 NM9 602 This page intentionally left blank 7...
Page 77: ...77 YORK INTERNATIONAL FORM 201 18 NM9 602 This page intentionally left blank 7...
Page 81: ...81 YORK INTERNATIONAL FORM 201 18 NM9 602 LD04179 7...
Page 83: ...83 YORK INTERNATIONAL FORM 201 18 NM9 602 7 LD04181 Box Information continued from page 82...
Page 97: ...97 YORK INTERNATIONAL FORM 201 18 NM9 602 This page intentionally left blank 7...
Page 103: ...FORM 201 18 NM9 602 YORK INTERNATIONAL YORK INTERNATIONAL 103 103A LD04267 FORM 201 18 NM9 602...