135
YORK INTERNATIONAL
FORM 201.18-NM8
ues are entered, or the switch is incorrectly selected
when setpoints below 4°C (40°F) are entered, the fol-
lowing message will be displayed before returning to
the Control Range message:
After the Setpoint is keyed in, the cursor will automati-
cally advance to the first digit of the Range as shown:
This value should be programmed for the maximum al-
lowable positive and negative chilled liquid temperature
deviation that is acceptable from setpoint in the system
application. A typical value would be +/-1°C (2.0°F).
The micro will accept a range from 0.8-1.4°C (1.5-2.5°F).
After the Setpoint and Range is keyed in, press the
ENTER Key to store the data in memory.
Failure to press the Enter key will
cause the newly programmed values
to be ignored and not entered into
memory.
After pressing the Enter key, the display will continue
to show the message until another key is pressed.
6.4
REMOTE COOLING SETPOINTS KEY
Remote Cooling Setpoints key allows resetting the set-
point upward from the programmed value in memory
from a remote device. This feature is typically used for
demand limiting or ice storage applications. Reset is
accomplished by timed closure of external contacts for
a defined period of time and allows reset of the set-
point upward by up to 22°C (40°F) above the setpoint
programmed in memory - see Section 1.7.
The maximum allowable reset must be programmed into
memory and can be a value of 1 to 22°C (2 to 40°F)
depending on user requirements. To program the reset,
press the Remote Reset Temperature Range key. The
following message will appear:
The display indicates the Remote Setpoint which is al-
ways equal to the chilled liquid setpoint programmed
by the Chilled Liquid Temperature / Range key plus
the offset from the remote reset signal. The display will
also show the Range which is the programmed maxi-
mum deviation allowed for the application. This dis-
play is not programmable, and will change the setpoint
only through a signal from a remote device.
Pressing the REM RESET TEMP RANGE Key again
scrolls the display to the MAX EMS-PWM REMOTE
TEMP RESET which is programmable. This should be
programmed to the maximum offset which is required
for the application. The maximum programmable value
is 22°C (40°F), while the minimum programmable value
is 1°C (2°F).
The cursor will stop beneath the first digit of the maxi-
mum reset. Key in the maximum reset allowed for the
application, remembering to use a leading “0” for val-
ues less than 10°C (or 10°F). Press the ENTER Key to
store the new value in memory.
O U T
O F
R A N G E -
T R Y
A G A I N !
S E T P O I N T
=
6 . 7
° C
R A N G E
=
+ / -
1 . 1
° C
R E M
S E T P
=
6 . 7
° C
R A N G E
=
+ / -
1 . 1
° C
M A X
E M S - P W M
R E M O T E
T E M P
R E S E T
=
+ 2 2 ° C
9
Summary of Contents for eco2 YCAS0425EB
Page 26: ...26 YORK INTERNATIONAL This page intentionally left blank Product Description ...
Page 49: ...49 YORK INTERNATIONAL FORM 201 18 NM8 This page intentionally left blank 7 ...
Page 60: ...60 YORK INTERNATIONAL FIG 20 CONTINUED ELEMENTARY DIAGRAM Technical Data ...
Page 65: ...65 YORK INTERNATIONAL FORM 201 18 NM8 WIRING DIAGRAM WYE DELTA START LD03229 FIG 23 CONT D 7 ...
Page 66: ...66 YORK INTERNATIONAL FIG 23 CONTINUED ELEMENTARY DIAGRAM Technical Data ...
Page 68: ...68 YORK INTERNATIONAL FIG 24 POWER PANEL FRONT INSIDE VIEW WYE DELTA START Technical Data ...
Page 71: ...71 YORK INTERNATIONAL FORM 201 18 NM8 LD03282 LD03283 LD03284 FIG 27 DETAIL A 7 ...
Page 74: ...74 YORK INTERNATIONAL FIG 32 DETAIL B Technical Data LD03285 ...
Page 75: ...75 YORK INTERNATIONAL FORM 201 18 NM8 FIG 33 DETAIL C 7 3 4 5 6 7 8 5 6 3 4 7 8 9 10 LD06841 ...