background image

035-11845-001-A-0304

4

Unitary Products Group

FIG. 1 - UNIT SUSPENSION MOUNTING (Horizontal Application)

Model

Power

Supply

Voltage Variation

1

Supply Air CFM

Entering Air Temperatures,

°

F

Cooling - wb

Heating - db

Min.

Max.

Min.

Max.

Min.

Max.

Min.

Max.

FCHP090

208/230-3-60

187

252

2400

3600

57

72

50

2

80

460-3-60

414

506

FDHP120

208/230-3-60

187

252

3200

4800

57

72

50

2

80

460-3-60

414

506

1

Utilization Range “A” in accordance with ARI Standard 110.

2

The system may operate below 50

°

F for a short period of time when warming up the conditioned space after a long shutdown.

TABLE 2 - APPLICATION DATA

Model

Accessory

Based on a Standard Blower Motor

Center of Gravity

Dimensions, In.

Weight

Distribution, Lbs.

A

B

W1

W2

W3

W4

Total

FHP090

Basic Unit Only

25-5/8

23-1/4

99

104

79

83

365

Unit with Electric Heat

30-3/4

23-3/8

90

150

72

121

433

Unit with Plenum

35-1/8

23-1/2

71

186

58

152

467

Unit with Electric Heat & Plenum

38

23-5/8

62

232

51

190

535

FHP120

Basic Unit Only

24-1/8

23-1/4

116

106

93

85

400

Unit with Electric Heat

29-1/4

23-3/8

103

155

84

126

468

Unit with Plenum

33-3/8

23-1/2

88

190

70

154

502

Unit with Electric Heat & Plenum

36-5/8

23-5/8

76

236

63

195

570

NOTE: Unit weights (with electric heat accessory) are based on an average heater weight of 68 lbs.

Summary of Contents for FCHP090

Page 1: ...his equipment All forms referenced in this instruction may be ordered from Standard Register Toll Free Tel 877 318 9675 Toll Free Fax 877 379 7920 Installer should pay particular attention to the word...

Page 2: ...Drain Piping 6 8 Motor Mounting Assembly 7 9 Hole Locations for Pressure Drop 8 10 Pressure Drop vs Supply Air CFM 8 11 Field Wiring 10 12 Unit Dimensions Clearances 11 TABLES Table No Description Pa...

Page 3: ...of installation The packaging consists of a bottom wooden skid that can be lifted with a fork truck from any direction a cardboard container that covers the entire unit and strapping that secures the...

Page 4: ...oned space after a long shutdown TABLE 2 APPLICATION DATA Model Accessory Based on a Standard Blower Motor Center of Gravity Dimensions In Weight Distribution Lbs A B W1 W2 W3 W4 Total FHP090 Basic Un...

Page 5: ...to minimize the transmission of noise and vibration Insulate all ductwork running through unconditioned areas to prevent moisture condensation and to provide more economi cal operation The return air...

Page 6: ...he matching outdoor unit for piping limitations line sizes and other design considerations INSTALLING REFRIGERANT MAINS WARNING Provisions for recovering refrigerant releases must be available during...

Page 7: ...usted in half turn increments 3 The tension on the belt should be adjusted for a deflection of 3 16 of an inch per foot of belt span with an applied force of 2 to 3 pounds This adjustment is made by m...

Page 8: ...90 0 40 0 95 1 06 0 28 1 06 1 16 0 14 1 17 1 26 800 0 82 0 97 1 10 0 81 1 06 1 07 0 74 1 18 1 27 0 63 1 30 1 38 0 51 1 42 1 49 880 1 10 1 11 1 24 1 09 1 24 1 21 1 02 1 37 1 45 0 91 1 50 1 55 0 78 1 6...

Page 9: ...se factory mounted motors are wired for a 460V power supply Refer to the wiring diagram inside the motor terminal box when reconnecting the motor leads for a 208 or 230 volt power supply TABLE 6 BLOWE...

Page 10: ...in lieu of the unit Refer to electric heat instruction Form 035 16602 002 for additional installation information NOTE Motors are wired for a 460V power supply Refer to the wiring diagram inside the m...

Page 11: ...th RETURN AIR opening 24 Side with SUPPLY AIR opening 24 1 Side with PIPING CONNECTIONS 52 2 Side opposite PIPING CONNECTIONS 12 Side with access for both POWER CONTROL WIRING 3 Bottom 4 1 Overall dim...

Page 12: ...sur faces This is recommended to prevent any loss in capacity and efficiency DRAIN PAN The condensate drain pan should be inspected regularly to as sure proper drainage FILTERS The filters must be rep...

Reviews: