270844-YTG-A-0407

Unitary Products Group

5

RETURN AIR AND FILTERS

The return air ducts to the furnace must have a total cross
sectional area of not less than two square inches per 1000
BTUH of furnace input rating for heating operation. 

If air con-

ditioning is to be installed with the furnace, or if it may be
added at a later time, larger return air ducts may be
required, depending on the capacity of the air condi-
tioner and the airflow required.

 

FILTER PERFORMANCE

The airflow capacity data published in the “Blower Perfor-
mance” table listed above represents blower performance
WITHOUT filters. To determine the approximate blower per-
formance of the system, apply the filter drop value for the fil-
ter being used or select an appropriate value from the “Filter
Performance” table shown.
The filter pressure drop values in the “Filter Performance”
table shown are typical values for the type of filter listed and
should only be used as a guideline. Actual pressure drop rat-
ings for each filter type vary between filter manufacturers.

BOTTOM/END RETURN

G8C05012(MU,MD)B12

1

B

High

1419

1357

1297

1212

1131

1050

942

846

Med

1221

1185

1145

1092

1036

961

879

780

Low

920

902

883

860

818

761

711

639

G8C07512(MU,MD)B12

1

B

High

1552

1491

1420

1348

1271

1185

1080

970

Med

1229

1237

1198

1164

1105

1039

956

861

Low

889

892

879

866

846

807

760

689

G8C07516(MU,MD)C12

1

C

High

1946

1862

1775

1620

1518

1409

1291

1160

Med

1683

1611

1551

1484

1388

1300

1190

1080

Low

1110

1138

1175

1190

1175

1126

1041

937

G8C10016(MU,MD)C12

1

C

High

1997

1920

1822

1723

1620

1500

1355

1211

Med

1728

1679

1635

1556

1465

1359

1249

1117

Low

1131

1156

1181

1190

1171

1126

1049

926

G8C10020(MU,MD)D11

2

D

High

2327

2232

2121

1999

1888

1763

1628

1473

Med-High

2050

1967

1868

1757

1658

1525

1403

1260

Med-Low

1911

1839

1758

1675

1593

1468

1340

1189

High

1780

1712

1642

1566

1465

1366

1249

1094

G8C12520(MU,MD)D11

2

D

High

2397

2304

2192

2063

1955

1822

1678

1521

Med-High

2151

2063

1977

1881

1774

1652

1528

1377

Med-Low

1972

1906

1838

1748

1660

1551

1419

1282

Low

1845

1794

1721

1646

1559

1451

1344

1208

G8C15020UHD11

2

D

High

2488

2389

2276

2151

2024

1883

1730

1577

Med-High

2164

2084

2024

1920

1816

1692

1558

1395

Med-Low

1998

1934

1868

1773

1673

1567

1445

1294

Low

1843

1793

1728

1653

1553

1453

1328

1192

1. Return air is through side opposite motor (left side) for one side return (worst case).

2. Airflows above 1800 CFM (50.97 m

3

/min) require either return from two sides or one side plus bottom

3. Airflows expressed in standard cubic feet per minute (CFM) and in cubic meters per minute (m

3

/min).

BLOWER PERFORMANCE (CONTINUED)

BTU/H (kW)

Input

Cabinet 

Size

Speed

 Tap

External Static Pressure, Inches WC - CFM

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

For applications requiring more than 1800 CFM, it
is required to use the bottom return, both side
returns or one side plus the bottom return.

• Single side return is not approved on 5 Ton mod-

els.

• 18” minimum height for return air box for bottom 

return only on Heating only applications with fur-
nace in the upflow configuration.

• 24” minimum height for return air box for bottom 

return only on A/C applications with furnace in 
the upflow configuration.

Summary of Contents for G8C05012(MU

Page 1: ...limited warranty on the heat exchanger 5 year limited parts warranty FEATURES 4 position MU upflow models allow horizontal left hori zontal right downflow and convertible applications 4 position MD m...

Page 2: ...8 19 0 42 G8C10016 MU MD C121 1600 C 21 20 20 3 8 20 0 19 1 2 18 1 4 18 3 4 18 5 8 19 0 42 G8C10020 MU MD D111 2000 D 24 5 23 1 2 20 3 8 20 0 23 21 3 4 18 3 4 22 1 8 19 0 42 G8C12520 MU MD D111 2000 D...

Page 3: ...0 17 1 2 8 0 80 0 35 65 G8C07516 MU MD C12 75 60 1600 21 11 4 80 0 30 60 G8C10016 MU MD C12 100 80 1600 21 11 4 80 0 40 70 G8C10020 MU MD D11 100 80 2000 24 1 2 11 3 80 0 35 65 G8C12520 MU MD D11 125...

Page 4: ...MU MD B121 B High 1507 1433 1371 1300 1223 1132 1040 938 Med 1239 1215 1175 1144 1085 1012 938 838 Low 907 907 891 875 849 800 741 672 G8C07512 MU MD B121 B High 1634 1562 1484 1417 1340 1238 1154 10...

Page 5: ...190 1175 1126 1041 937 G8C10016 MU MD C121 C High 1997 1920 1822 1723 1620 1500 1355 1211 Med 1728 1679 1635 1556 1465 1359 1249 1117 Low 1131 1156 1181 1190 1171 1126 1049 926 G8C10020 MU MD D112 D H...

Page 6: ...24 G8C15020UHD11 150 2000 D 2 25 x 16 24 x 24 DOWNFLOW Models Input Air Flow Cabinet Size Top Return Downflow Cleanable Air Filters Top Return Downflow Disposable Air Filters MBH CFM in in G8C05012 MU...

Page 7: ...ow 0 30 w c to obtain actual airflow 0 38 in w c ESP 1408 52 1356 1 Special floor base or air conditioning coil required for use on combustible floor 2 Line contact only permitted between lines formed...

Page 8: ...change without notice Printed in U S A 270844 YTG A 0407 Copyright by York International Corp 2007 All rights reserved Supersedes 246657 YTG C 0806 Unitary 5005 Norman Products York OK Group Drive 73...