VENT CLEARANCES

A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.

‡ 

Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor. For clearance not specified in ANSI Z223.1 / NFPA 

54 or CSA B149.1-00.
Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer’s Installation Manual.
Any fresh air or make up inlet for dryer or furnace area is considered to be forced air inlet. 
Avoid areas where condensate drippage may cause problems such as above planters, patios, or adjacent to windows where steam may cause fogging. 
A terminus of a vent shall be either: 
Fitted with a cap in accordance with the vent manufacturer’s installation instructions, or In accordance with the installation instructions for a special venting system.
* Does not apply to multiple installations of this furnace model. Refer to "VENTING MULTIPLE UNITS" in this section of these instructions.
IMPORTANT: Consideration must be given for degradation of building materials by flue gases. Sidewall termination may require sealing or shielding of building surfaces 
with a corrosion resistant material to protect against combustion product corrosion. Consideration must be given to wind direction in order to prevent flue products and/or 
condensate from being blown against the building surfaces. If a metal shield is used it must be a stainless steel material at a minimum dimension of 20 inches. It is rec-
ommended that a retaining type collar be used that is attached to the building surface to prevent movement of the vent pipe.
Responsibility for the provision of proper adequate venting and air supply for application shall rest with the installer.
Vent shall extend high enough above building, or a neighboring obstruction, so that wind from any direction will not create a positive pressure in the vicinity of the vent.

 FIGURE 12:  Home Layout

L

E

D

B

V

V

V

X

V

B

V

J

X

B

B

B

V

V

F

V

C

B

X

V

I

V

G

H

A

M

K

OPERABLE

FIXED
CLOSED

VENT TERMINAL

AIR SUPPLY

AREA WHERE TERMINAL IS NOT PERMITTED

FIXED
CLOSED

Canadian Installations

1

US Installation

2

A. Clearance above grade, veranda, porch, deck, or

balcony

12 inches (30 cm)

12 inches (30 cm)

B. Clearance to window or door that may be opened

12 inches (30 cm) for models <100,000
BTUH (30 kW), 36 inches (91 cm) for 
models >100,000 BTUH (30 kW)

Two-pipe (direct vent) applications: 9 inches
(23 cm) for models <50,000 BTUH (15 kW), 
12 inches (30 cm) for models >50,000 BTUH 
(15 kW). Single-pipe applications: 4 feet.

C. Clearance to permanently closed window

4 Feet

4 Feet

D. Vertical clearance to ventilated soffit located 

above the terminal within a horizontal distance 
of 2 feet (61 cm) from the center line of the terminal

4 Feet

4 Feet

E. Clearance to unventilated soffit

12 Inches

12 Inches

F. Clearance to outside corner 

12 Inches

12 Inches

G. Clearance to inside corner

12 Inches (two-pipe), 6 Feet (one-pipe)

12 Inches (two-pipe), 6 Feet (one-pipe)

H. Clearance to each side of center line 

extended above meter/regulator assembly

3 feet (91 cm) within a height 15 feet 
(4.5 m) above the meter/regulator assembly

3 feet (91 cm) within a height 15 feet 
(4.5 m) above the meter/regulator assembly

I.

Clearance to service regulator vent outlet

3 feet (91 cm)

3 feet (91 cm)

J. Clearance to nonmechanical air supply 

inlet to building or the combustion 
air inlet to any other appliance

12 inches (30 cm) for models <100,000
BTUH (30 kW), 36 inches (91 cm) for 
models >100,000 BTUH (30 kW)

Two-pipe (direct vent) applications: 9 inches 
(23 cm) for models <50,000 BTUH (15 kW), 
12 inches (30 cm) for models >50,000 BTUH 
(15 kW). Single-pipe applications: 4 feet.

K. Clearance to a mechanical supply inlet

6 feet (1.83 m)

3 feet (91 cm) above if within 10 feet (3 cm) 
horizontally

L. Clearance above paved sidewalk or paved 

driveway located on public property

7 feet (2.13 m) 

7 feet (2.13 m) 

M. Clearance under veranda, porch, deck, or balcony

12 inches (30 cm) 

12 inches (30 cm) 

Dryer Vent **

3 ft (91.44 cm) 

3 ft (91.44 cm) 

Plumbing Vent Stack **

3 ft (91.44 cm) 

3 ft (91.44 cm) 

Gas Appliance Vent Terminal **

3 ft (91.44 cm) * 

3 ft (91.44 cm) * 

Vent Termination from any Building Surface 

12" (30.4 cm) 

12" (30.4 cm) 

Above anticipated snow depth 

12" (30.4 cm) 

12" (30.4 cm) 

A. Clearance above grade, veranda, porch, deck, or

balcony

12 inches (30 cm)

12 inches (30 cm)

B. Clearance to window or door that may be opened

12 inches (30 cm) for models <100,000
BTUH (30 kW), 36 inches (91 cm) for 
models >100,000 BTUH (30 kW)

Two-pipe (direct vent) applications: 9 inches
(23 cm) for models <50,000 BTUH (15 kW), 
12 inches (30 cm) for models >50,000 BTUH 
(15 kW). Single-pipe applications: 4 feet.

C. Clearance to permanently closed window

4 Feet

4 Feet

D. Vertical clearance to ventilated soffit located 

above the terminal within a horizontal distance 
of 2 feet (61 cm) from the center line of the terminal

4 Feet

4 Feet

1.

In accordance with the current CSA B149.1-00, Natural Gas and Propane Installation Code.

2.

In accordance with the current ANSI Z223.1 / NFPA 54, National Gas Code.

Summary of Contents for GF9S

Page 1: ...6 GAS PIPING 6 ELECTRICAL POWER 8 TWINNING AND STAGING 9 COMBUSTION AIR AND VENT SYSTEM 11 CONDENSATE PIPING 18 SAFETY CONTROLS 18 START UP AND ADJUSTMENTS 19 WIRING DIAGRAM 25 LIST OF FIGURES Dimens...

Page 2: ...plate and power supply to be sure that the elec trical characteristics match All models use nominal 115 VAC 1 Phase 60 Hertz power supply DO NOT CONNECT THIS APPLI ANCE TO A 50 HZ POWER SUPPLY OR A VO...

Page 3: ...required for servicing and cleaning 2 Eighteen 18 inches 46 cm at the side where access is required for passage to the front when servicing or for inspection or replacement of flue vent connections In...

Page 4: ...s properly sized as well 1 The Air Temperature Rise is determined by subtracting the Return Air Temperature Reading from the Supply Air Temperature Read ing 2 The External Static Pressure is determine...

Page 5: ...igure 1 for unit and plenum dimensions Attic installations must meet all minimum clearances to combustibles and have floor support with required service accessibility The supply air temperature MUST N...

Page 6: ...the instructions in this section specify the type of gas approved for this furnace only use those approved gases The installation of a drip leg and ground union is required Refer to Figure 4 IMPORTANT...

Page 7: ...ing a wrench to the body of the gas valve will damage the valve causing improper operation and or the valve to leak TABLE 5 High Altitude Conversion 40 120 MBTUH Models Type Of Gas Orifice at Sea Leve...

Page 8: ...ernate wiring method is to use a field provided 2 5 08 cm x 4 10 2 cm box and cover on the outside of the furnace Route the furnace leads into the box using a protective bushing where the wires pass t...

Page 9: ...n two furnaces are installed using the same duct system it is very important that the two furnace cir culating air blowers operate in unison If one blower starts before the second blower the duct syst...

Page 10: ...will shut off at the same time Continuous Fan On a thermostat call for continuous fan G signal both furnace blowers will come on at the same time in cooling speed and will stay on until the G signal...

Page 11: ...maximum of 5 elbows in the combustion air piping and a maximum of 5 elbows in the vent piping 4 Three vent terminal elbows two for vent pipe and one for air intake pipe are already accounted for as v...

Page 12: ...rom the furnace to the out side termination B Ventilated combustion air systems from the furnace to the attic or crawl space termination 6 Disassemble the combustion air and vent piping apply cement p...

Page 13: ...0 kW 36 inches 91 cm for models 100 000 BTUH 30 kW Two pipe direct vent applications 9 inches 23 cm for models 50 000 BTUH 15 kW 12 inches 30 cm for models 50 000 BTUH 15 kW Single pipe applications 4...

Page 14: ...ombustion air systems must be installed so the vent and the combustion air pipes terminate in the same atmospheric zone Refer to Figures 14 or 15 VENTING MULTIPLE UNITS Multiple units can be installed...

Page 15: ...ll bring air in from the outdoors to the furnace combustion air intake collar on the burner box The second pipe Shown in Figure 19 is the furnace vent pipe The combustion air intake pipe should be loc...

Page 16: ...e louver is in the fully open position This type of installation requires that the supply air to the appli ance s be of a sufficient amount to support all of the appliance s in the area Operation of a...

Page 17: ...sage Follow all notes procedures and required materials in the SEALED COMBUS TION AIR SUPPLY section in these instructions when installing the combustion air pipe from the unit and into a ventilated a...

Page 18: ...p pump must be approved for use with acidic condensate CONDENSATE DRAIN TRAP AND DRAIN FREEZE PROTECTION Special precautions MUST be made if installing furnace in an area which may drop below freezing...

Page 19: ...th x 1 8 0 3 cm diameter tubing 2 pieces of 4 10 cm length x 1 8 0 3 cm diameter tubing 1 5 16 0 8 cm tee 1 5 16 0 8 cm x 1 8 0 3 cm reducing coupling 1 1 8 0 3 cm adapter 1 Dwyer Manometer These item...

Page 20: ...3600 then divided by the time it took to measure 0 10 m3 of gas from the gas meter For Propane LP Gas multiply the Heat content of the gas MJ m3 or Default 93 15 times 0 10 m3 of gas measured at the...

Page 21: ...l reference atmo spheric pressure Refer to Figure 26 for connection details IMPORTANT The cap for the pressure regulator must be removed entirely to gain access to the adjustment screw Loosening or ti...

Page 22: ...ning the jumper on two of the four pins as shown in Figure 27 The blower speed connections shown in Figure 27 are typical How ever these connections may vary from model to model and may be changed as...

Page 23: ...35 1175 33 1105 31 1045 30 990 28 905 25 890 25 790 22 80 1600 C 100 1600 C HIGH 1960 56 1955 55 1925 55 1890 54 1830 52 1765 50 1695 48 1615 46 1600 45 1485 42 M HI 1565 44 1560 44 1560 44 1575 45 15...

Page 24: ...that total system static is 0 58 w c To determine the system airflow complete the follow ing steps Obtain the airflow values at 0 50 w c 125 Pa 0 60 w c 150 Pa ESP Airflow 0 50 2285 CFM 64 70 m3 min A...

Page 25: ...105561 UIM B 0605 Unitary Products Group 25 SECTION XI WIRING DIAGRAM FIGURE 27 Wiring Diagram...

Page 26: ...105561 UIM B 0605 26 Unitary Products Group NOTES...

Page 27: ...105561 UIM B 0605 Unitary Products Group 27 NOTES...

Page 28: ...o change without notice Printed in U S A 105561 UIM B 0605 Copyright by York International Corp 2005 All rights reserved Supersedes 105561 UIM A 0205 Unitary 5005 Norman Product York OK Group Drive 73...

Reviews: