Unitary Products Group
3
278177-BTG-A-0407
Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures.
Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local codes.
The furnace shall be installed so that the electrical components are protected from water.
Wire size and overcurrent protection must comply with the National Electric Code.
NOTES:
1. For altitudes above 2000 ft. reduce capacity 4% for each 1000 ft. above sea level.
2. Wire size based on copper conductors, 60°C, 3% voltage drop.
3. Continuous return air temperature must not be below 55°F.
4. All filters must be high velocity cleanable type.
ELECTRICAL AND PERFORMANCE DATA
Models
Input/
Cabinet
Output
Nominal
Airflow
Cabinet
Width
Total Unit
AFUE
Air Temp.
Rise
MBH
MBH
CFM
In.
Amps
%
°F
GM9S040A12DH11
40/A
37
1200
14-1/2
9
94
35 - 65
GM9S060B12DH11
60/B
55
1200
17-1/2
9
92
35 - 65
GM9S080B12DH11
80/B
74
1200
17-1/2
9
92
35 - 65
GM9S080C16DH11
80/C
74
1600
21
12
92
35 - 65
GM9S100C16DH11
100/C
93
1600
21
12
92
35 - 65
GM9S100C20DH11
100/C
93
2000
21
14
92
35 - 65
GM9S120D20DH11
120/D
112
2000
24-1/2
14
92
35 - 65
Models
Input/
Cabinet
Max. Outlet
Air Temp.
Blower
Blower
Size
Max.
Over-current
Protect
Min. Wire Size
(awg) @ 75 ft.
One Way
Operation
Weight
MBH °F
HP
Amps
In.
Lbs.
GM9S040A12DH11
40/A
165
1/2
7.0
11 x 8
20
14
120
GM9S060B12DH11
60/B
165
1/2
7.0
11 x 8
20
14
130
GM9S080B12DH11
80/B
165
1/2
7.0
11 x 8
20
14
145
GM9S080C16DH11
80/C
165
3/4
10.2
11 x 10
20
14
155
GM9S100C16DH11
100/C
165
3/4
10.2
11 x 10
20
14
170
GM9S100C20DH11
100/C
165
1
12.7
11 x 11
20
12
175
GM9S120D20DH11
120/D
165
1
12.7
11 x 11
20
12
180