1. Airflow expressed in standard cubic feet per minute (CFM).

2. Return air is through side opposite motor (left side).

3. Motor voltage at 115 V.

* Input / CFM / Cabinet Width (A=14-1/2, B=17-1/2, C=21, D=24-1/2)

† Indicates model available in LoNOx.

BLOWER PERFORMANCE CFM - UPFLOW (WITHOUT FILTER) - LEFT SIDE RETURN

MODELS

Input /

CFM

Speed 

Single Stage Left Side Airflow Data (SCFM)

Ext. Static Pressure (in. H2O) 

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 

40/1200/A 

High 

1810 1730 1660 1570 1480 1390 1300 1200 1090  930 

Medium 

High  1390 1390 1350 1320 1270 1210 1150 1080  970  790 

Medium 

Low  1120 1120 1120 1110 1080 1080 1020  930  830  690 

Low 

880 910 920 920 910 870 820 740 650 510 

60/1200/A 

High 

1770 1690 1630 1560 1490 1390 1290 1190 1050  920 

Medium 

High  1400 1380 1350 1320 1280 1230 1160 1060  930  780 

Medium 

Low  1120 1130 1150 1130 1120 1080 1000  950  790  630 

Low 

880 900 900 900 880 850 790 730 660 530 

80/1200/A 

High 

1790 1720 1670 1590 1530 1450 1350 1260 1140 1000 

Medium 

High  1420 1370 1350 1320 1280 1230 1170 1090  990  840 

Medium 

Low  1080 1120 1110 1100 1080 1040 1000  920  820  690 

Low 

N/A 900 900 890 870 850 800 730 670 560 

80/1600/B 

High 

2000 1960 1930 1900 1800 1760 1710 1640 1550 1460 

Medium 

1440 1440 1430 1420 1400 1380 1340 1300 1220 1150 

Low 

1220 1230 1230 1230 1200 1190 1170 1160  1110 1050 

80/2200/C 

High 

2710 2640 2560 2480 2360 2260 2160 2010 1860 1650 

Medium 

High  2110 2110 2070 2030 1980 1910 1850 1710 1570 1300 

Medium 

Low  1690 1690 1650 1610 1540 1480 1410 1280 1170 1030 

Low 

1350 1330 1310 1290 1260 1220 1150 1050  970  860 

100/1200/B 

High 

1780 1710 1640 1560 1490 1390 1290 1180 1030  820 

Medium 

High  1430 1410 1370 1340 1280 1220 1140 1040  890  730 

Medium 

Low  1140 1170 1150 1120 1080 1040  970  890  760  630 

Low 

920 940 950 940 920 890 850 770 660 560 

100/1600/B 

High 

1950 1890 1840 1790 1730 1660 1570 1480 1390 1300 

Medium 

1440 1420 1400 1390 1350 1320 1270 1210 1150 1060 

Low 

1230 1210 1190 1180 1150 1130 1090 1050  990  920 

100/2000/C 

High 

2770 2670 2610 2540 2450 2340 2210 2070 1890 1730 

Medium 

High  2120 2060 2030 2000 1950 1880 1810 1720 1580 1370 

Medium 

Low  1690 1660 1630 1610 1560 1490 1420 1350 1240 1070 

Low 

1390 1370 1330 1290 1250 1200 1120 1010  910  850 

115/1600/C 

High 

2160 2070 1990 1900 1800 1690 1580 1430 1260 1000 

Medium 

1760 1720 1690 1630 1560 1480 1390 1250 1080  890 

Low 

1510 1490 1470 1440 1380 1300 1210 1110  950  780 

115/2000/C 

High 

2740 2650 2560 2480 2380 2280 2170 1990 1840 1650 

Medium 

High  2120 2090 2040 2000 1940 1870 1780 1680 1550 1370 

Medium 

Low  1690 1670 1650 1610 1560 1510 1440 1310 1160 1030 

Low 

1390 1360 1330 1300 1250 1190 1100 1020  940  840 

130/2000/D 

High 

2680 2600 2520 2410 2300 2180 2050 1910 1730 1550 

Medium 

High  2140 2110 2070 1990 1930 1850 1770 1670 1530 1370 

Medium 

Low  1660 1640 1620 1570 1530 1470 1400 1310 1220 1090 

Low 

1370 1350 1320 1290 1240 1190 1140 1040  930  860 

Summary of Contents for GY8S

Page 1: ...ble and economical installation and operation These units are Category I listed and may be common vented with another gas appliance as allowed by the National Fuel Gas Code WARRANTY 20 year limited wa...

Page 2: ...3 8 3 3 4 100 80 1200 B 17 1 2 16 1 4 13 1 8 4 0 11 5 8 3 3 4 100 80 1600 B 17 1 2 16 1 4 13 1 8 4 0 11 5 8 3 3 4 100 80 2000 C 21 19 3 4 16 5 8 4 0 13 3 8 3 3 4 115 92 1600 C 21 19 3 4 16 5 8 4 0 13...

Page 3: ...0 40 70 100 80 1600 17 1 2 80 0 35 65 100 80 2000 21 80 0 25 55 115 92 1600 21 80 0 35 65 115 92 2000 21 80 0 30 60 130 104 2000 24 1 2 80 0 35 65 Input MBH Max Outlet Air Temp F Blower Blower Size I...

Page 4: ...2410 2320 2230 2130 2030 1900 1790 1630 1470 Medium High 2120 2060 2000 1970 1840 1730 1680 1570 1460 1260 Medium Low 1720 1700 1670 1620 1570 1500 1430 1310 1160 1000 Low 1410 1390 1360 1330 1280 12...

Page 5: ...2200 C High 2710 2640 2560 2480 2360 2260 2160 2010 1860 1650 Medium High 2110 2110 2070 2030 1980 1910 1850 1710 1570 1300 Medium Low 1690 1690 1650 1610 1540 1480 1410 1280 1170 1030 Low 1350 1330 1...