background image

Unitary Products Group

3

036-21560-001 Rev. A (0204)

NOTE: For high altitude conversion, an orifice change may also be required. See Form 035-14460-001 for application information.

* Wire size and overcurrent protection must comply with the National Electric Code.

NOTES: 

1. For altitudes above 2000 ft. reduce capacity 4% for each 1000 ft. above sea level.
2. Wire size based on copper conductors, 60°C, 3% voltage drop.
3. Continuous return air temperature must not be below 55°F.

 * ESP (External Static Pressure) .5" WG is at furnace outlet ahead of cooling coil.

NOTES:

 

1. All filters must be high velocity cleanable type.

FIELD WIRING DIAGRAMS

POWER WIRING

HIGH ALTITUDE PRESSURE SWITCH APPLICATION

Input (MBH)

Upflow Models

Output (MBH)

4,500 To 10,000 Ft.

60/1200

55

1PS0901

80/1200

74

1PS0902

80/1600

74

1PS0903

100/1600

93

1PS0901

100/2000

93

1PS0901

120/2000

112

1PS0901

ELECTRICAL AND PERFORMANCE DATA

Input

Output

Nominal Airflow

Cabinet Width

AFUE

Air Temp. Rise

MBH

kW

MBH

kW

CFM

m

3

/min

In.

mm

%

°F

°C

60

18

55

16.1

1200

34.0

17-1/2

444

91

40 - 70

22 - 39

80

23

74

21.7

1200

34.0

17-1/2

444

91

35 - 65

19 - 36

80

23

74

21.7

1600

45.3

21

533

91

40 - 70

22 - 39

100

29

93

27.3

1600

45.3

21

533

91

35 - 65

19 - 36

100

29

93

27.3

2000

56.6

21

533

91

35 - 65

19 - 36

120

35

112

32.8

2000

56.6

24-1/2

622

91

35 - 65

19 - 36

Input

Max. Outlet 

Air Temp.

Blower

Blower Size

Total Unit 

Max. 

Over-current 

Protect

Min. Wire Size

(awg) @ 75 ft. 

One Way

MBH kW

°F

°C

HP

Amps

In.

mm

Amps

60

18

170

76.7

1/2

7.0

11 x 8

279 x 203

9

20

14

80

23

170

76.7

1/2

7.0

11 x 8

279 x 203

9

20

14

80

23

170

76.7

3/4

10.2

11 x 10

279 x 254

12

20

14

100

29

175

79.4

3/4

10.2

11 x 10

254 x 254

12

20

14

100

29

175

79.4

1

12.7

11 x 11

279 x 279

14

20

12

120

35

175

76.7

1

12.7

11 x 11

279 x 279

14

20

12

MODEL

NUMBER

FILTER SIZE

ADD-ON COOLING

APPROX.

OPER. WEIGHT

TONS

CFM* @ .5 ESP

GY9S060B12DH11

(2) 14 x 20

1-1/2, 2, 2-1/2, 3

1550

130

GY9S080B12DH11

2, 2-1/2, 3

1530

145

GY9S080C16DH11

3, 3-1/2, 4

1860

155

GY9S100C16DH11

3, 3-1/2, 4

1830

170

GY9S100C20DH11

3-1/2, 4, 5

2000

175

GY9S120D20DH11

3-1/2, 4, 5

2100

180

NOMINAL
115 VOLT

BLK

WHT

GRN

BLK (HOT)

WHT (NEUTRAL)

GRD

ROOM

THERMOSTAT

FURNACE
CONTROL

CONDENSING

UNIT

TO AIR CONDITIONER

CONTROLS

R

W

G
Y
C

R

W

G
Y
C

Summary of Contents for GY9

Page 1: ...install ideal height 40 cabinet Blower off delay for cooling SEER improvement Easy to connect power control wiring Built in high level self diagnostics with fault code display Low unit amp requiremen...

Page 2: ...44 80 75 23 42 21 96 1200 33 98 B 17 1 2 44 4 16 1 4 41 3 15 1 8 38 4 1 3 4 4 44 80 75 23 42 21 96 1600 45 31 C 21 53 3 19 3 4 50 2 18 1 2 47 0 2 1 8 5 40 100 95 29 28 27 82 1600 45 31 C 21 53 3 19 3...

Page 3: ...18 55 16 1 1200 34 0 17 1 2 444 91 40 70 22 39 80 23 74 21 7 1200 34 0 17 1 2 444 91 35 65 19 36 80 23 74 21 7 1600 45 3 21 533 91 40 70 22 39 100 29 93 27 3 1600 45 3 21 533 91 35 65 19 36 100 29 93...

Page 4: ...Medium High 1583 45 1590 45 1569 44 1554 44 1532 43 1502 43 1457 41 1409 40 1327 38 1221 35 Medium Low 1256 36 1275 36 1275 36 1288 36 1275 36 1265 36 1232 35 1187 34 1126 32 1023 29 Low 937 27 939 27...

Page 5: ...percentage by airflow difference to obtain airflow reduction 0 8 x 90 72 5 Subract airflow reduction value to airflow 0 50 to obtain actual airflow 0 58 ESP 2125 72 2053 ACCESSORIES PROPANE LP CONVER...

Page 6: ...lude Fan Switch NOTE For One stage Cool or One stage Heat Cool must be used with Subbase 2TB17700424 2TB17700424 SUBBASE 24V One stage heat cool Manual changeover integral subbase System Switch Cool O...

Page 7: ...Unitary Products Group 7 036 21560 001 Rev A 0204 NOTES...

Page 8: ...ct to change without notice Printed in U S A 036 21560 001 Rev A 0204 Copyright by York International Corp 2004 All rights reserved Supersedes Nothing Unitary 5005 Norman Products York OK Group Drive...

Reviews: