Unitary Products Group
3
036-21560-001 Rev. A (0204)
NOTE: For high altitude conversion, an orifice change may also be required. See Form 035-14460-001 for application information.
* Wire size and overcurrent protection must comply with the National Electric Code.
NOTES:
1. For altitudes above 2000 ft. reduce capacity 4% for each 1000 ft. above sea level.
2. Wire size based on copper conductors, 60°C, 3% voltage drop.
3. Continuous return air temperature must not be below 55°F.
* ESP (External Static Pressure) .5" WG is at furnace outlet ahead of cooling coil.
NOTES:
1. All filters must be high velocity cleanable type.
FIELD WIRING DIAGRAMS
POWER WIRING
HIGH ALTITUDE PRESSURE SWITCH APPLICATION
Input (MBH)
Upflow Models
Output (MBH)
4,500 To 10,000 Ft.
60/1200
55
1PS0901
80/1200
74
1PS0902
80/1600
74
1PS0903
100/1600
93
1PS0901
100/2000
93
1PS0901
120/2000
112
1PS0901
ELECTRICAL AND PERFORMANCE DATA
Input
Output
Nominal Airflow
Cabinet Width
AFUE
Air Temp. Rise
MBH
kW
MBH
kW
CFM
m
3
/min
In.
mm
%
°F
°C
60
18
55
16.1
1200
34.0
17-1/2
444
91
40 - 70
22 - 39
80
23
74
21.7
1200
34.0
17-1/2
444
91
35 - 65
19 - 36
80
23
74
21.7
1600
45.3
21
533
91
40 - 70
22 - 39
100
29
93
27.3
1600
45.3
21
533
91
35 - 65
19 - 36
100
29
93
27.3
2000
56.6
21
533
91
35 - 65
19 - 36
120
35
112
32.8
2000
56.6
24-1/2
622
91
35 - 65
19 - 36
Input
Max. Outlet
Air Temp.
Blower
Blower Size
Total Unit
Max.
Over-current
Protect
Min. Wire Size
(awg) @ 75 ft.
One Way
MBH kW
°F
°C
HP
Amps
In.
mm
Amps
60
18
170
76.7
1/2
7.0
11 x 8
279 x 203
9
20
14
80
23
170
76.7
1/2
7.0
11 x 8
279 x 203
9
20
14
80
23
170
76.7
3/4
10.2
11 x 10
279 x 254
12
20
14
100
29
175
79.4
3/4
10.2
11 x 10
254 x 254
12
20
14
100
29
175
79.4
1
12.7
11 x 11
279 x 279
14
20
12
120
35
175
76.7
1
12.7
11 x 11
279 x 279
14
20
12
MODEL
NUMBER
FILTER SIZE
ADD-ON COOLING
APPROX.
OPER. WEIGHT
TONS
CFM* @ .5 ESP
GY9S060B12DH11
(2) 14 x 20
1-1/2, 2, 2-1/2, 3
1550
130
GY9S080B12DH11
2, 2-1/2, 3
1530
145
GY9S080C16DH11
3, 3-1/2, 4
1860
155
GY9S100C16DH11
3, 3-1/2, 4
1830
170
GY9S100C20DH11
3-1/2, 4, 5
2000
175
GY9S120D20DH11
3-1/2, 4, 5
2100
180
NOMINAL
115 VOLT
BLK
WHT
GRN
BLK (HOT)
WHT (NEUTRAL)
GRD
ROOM
THERMOSTAT
FURNACE
CONTROL
CONDENSING
UNIT
TO AIR CONDITIONER
CONTROLS
R
W
G
Y
C
R
W
G
Y
C