background image

4

Unitary Products Group

036-21560-001 Rev. A (0204)

1. Airflow expressed in standard cubic feet per minute (CFM) and in cubic meters per minute (m

3

/min).

2. Motor voltage at 115 V.

FILTER PERFORMANCE

The airflow capacity data published in the “Blower Perfor-
mance” table listed above represents blower performance
WITHOUT filters. To determine the approximate blower per-
formance of the system, apply the filter drop value for the fil-
ter being used or select an appropriate value from the “Filter
Performance” table shown.

NOTE:  

The filter pressure drop values in the “Filter Perfor-

mance” table shown are typical values for the type of filter
listed and should only be used as a guideline. Actual pres-
sure drop ratings for each filter type vary between filter manu-
facturer.

BLOWER PERFORMANCE CFM

AIRFLOW WITH TOP RETURN

MODELS

Speed

Tap

EXTERNAL STATIC PRESSURE, INCHES W.C. (kPa)

Input/

Output/

Airflow/

cabinet

0.1 (0.025)

0.2 (0.050)

0.3 (0.075)

0.4 (0.099)

0.5 (0.124)

0.6 (0.149)

0.7 (0.174) 

0.8 (0.199) 

0.9 (0.224)

1.0 (0.249)

CFM  m

3

/min CFM  m

3

/min CFM  m

3

/min CFM  m

3

/min CFM  m

3

/min CFM  m

3

/min CFM  m

3

/min CFM  m

3

/min CFM  m

3

/min CFM  m

3

/min

60/55/

1200/B

High

1687

48

1652

47

1631

46

1595

45

1557

44

1511

43

1456

41

1382

39

1313

37

1211

34

Medium High 1193

34

1183

33

1173

33

1162

33

1142

32

1115

32

1076

30

1036

29

982

28

950

27

Medium Low 933

26

933

26

921

26

911

26

902

26

872

25

825

23

793

22

771

22

712

20

Low

752

21

745

21

731

21

718

20

698

20

652

18

602

17

580

16

536

15

496

14

80/75/

1200/B

High

1686

48

1658

47

1623

46

1572

44

1534

43

1465

41

1391

39

1305

37

1202

34

1091

31

Medium High 1257

36

1223

35

1218

34

1203

34

1177

33

1142

32

1094

31

1026

29

939

27

874

25

Medium Low 977

28

982

28

976

28

955

27

934

26

899

25

843

24

791

22

738

21

686

19

Low

775

22

777

22

757

21

733

21

698

20

663

19

627

18

584

17

549

16

490

14

80/75/

1600/C

High

2071

59

2026

57

1981

56

1935

55

1864

53

1796

51

1713

48

1625

46

1532

43

1401

40

Medium High 1583

45

1590

45

1569

44

1554

44

1532

43

1502

43

1457

41

1409

40

1327

38

1221

35

Medium Low 1256

36

1275

36

1275

36

1288

36

1275

36

1265

36

1232

35

1187

34

1126

32

1023

29

Low

937

27

939

27

936

26

945

27

942

27

936

26

912

26

874

25

810

23

726

21

100/95/

1600/C

High

1996

56

1961

56

1938

55

1896

54

1836

52

1779

50

1707

48

1625

46

1531

43

1399

40

Medium High 1449

41

1480

42

1495

42

1488

42

1488

42

1449

41

1417

40

1368

39

1299

37

1208

34

Medium Low 1167

33

1192

34

1192

34

1187

34

1202

34

1192

34

1182

33

1140

32

1097

31

1018

29

Low

932

26

900

25

871

25

840

24

805

23

761

22

710

20

663

19

641

18

623

18

100/95/

2000/C

High

2404

68

2320

66

2225

63

2138

61

2034

58

1924

54

1816

51

1692

48

1559

44

1422

40

Medium High 2018

57

1955

55

1883

53

1815

51

1750

50

1670

47

1586

45

1497

42

1394

39

1246

35

Medium Low 1626

46

1581

45

1531

43

1488

42

1418

40

1363

39

1291

37

1225

35

1123

32

964

27

Low

1336

38

1291

37

1249

35

1205

34

1155

33

1091

31

1018

29

951

27

884

25

759

21

120/112/

2000/D

High

2520

71

2432

69

2353

67

2251

64

2152

61

2042

58

1947

55

1815

51

1701

48

1525

43

Medium High 2018

57

1979

56

1945

55

1911

54

1863

53

1779

50

1705

48

1599

45

1493

42

1353

38

Medium Low 1586

45

1545

44

1501

42

1457

41

1407

40

1351

38

1287

36

1216

34

1081

31

926

26

Low

1321

37

1266

36

1213

34

1163

33

1111

31

1071

30

987

28

864

24

763

22

700

20

FILTER PERFORMANCE - PRESSURE DROP INCHES W.C. AND (KPA)

AIRFLOW RANGE

MINIMUM 

OPENING SIZE

FILTER TYPE

DISPOSABLE

COARSE FIBER 

WASHABLE

*

*

PLEATED

CFM

m

3

/m

 in

2

   

cm

2

In W.C.

kPA

In W.C.

kPA

In W.C..

kPA

0 - 750

0 - 21.4

230

584.2

0.01

0.00249

0.01

0.00249

0.15

0.03736

751 - 1000

21.25 - 28.32

330

838.2

0.05

0.01245

0.05

0.01245

0.20

0.04982

1001 - 1250

28.33 - 35.40

330

838.2

0.10

0.02491

0.10

0.02491

0.20

0.04982

1251 - 1500

35.41 - 42.48

330

838.2

0.10

0.02491

0.10

0.02491

0.25

0.06227

1501 - 1750

42.49 - 49.55

380

965.2

0.15

0.03736

0.14

0.03487

0.30

0.07473

1751 - 2000

49.56 - 56.63

380

965.2

0.19

0.04733

0.18

0.04484

0.30

0.07473

2001 & Above

56.64 - Above

463

1176.0

0.19

0.04733

0.18

0.04484

0.30

0.07473

*.

Coarse Fiber Filters are the type supplied with furnace (if supplied).

Summary of Contents for GY9

Page 1: ...install ideal height 40 cabinet Blower off delay for cooling SEER improvement Easy to connect power control wiring Built in high level self diagnostics with fault code display Low unit amp requiremen...

Page 2: ...44 80 75 23 42 21 96 1200 33 98 B 17 1 2 44 4 16 1 4 41 3 15 1 8 38 4 1 3 4 4 44 80 75 23 42 21 96 1600 45 31 C 21 53 3 19 3 4 50 2 18 1 2 47 0 2 1 8 5 40 100 95 29 28 27 82 1600 45 31 C 21 53 3 19 3...

Page 3: ...18 55 16 1 1200 34 0 17 1 2 444 91 40 70 22 39 80 23 74 21 7 1200 34 0 17 1 2 444 91 35 65 19 36 80 23 74 21 7 1600 45 3 21 533 91 40 70 22 39 100 29 93 27 3 1600 45 3 21 533 91 35 65 19 36 100 29 93...

Page 4: ...Medium High 1583 45 1590 45 1569 44 1554 44 1532 43 1502 43 1457 41 1409 40 1327 38 1221 35 Medium Low 1256 36 1275 36 1275 36 1288 36 1275 36 1265 36 1232 35 1187 34 1126 32 1023 29 Low 937 27 939 27...

Page 5: ...percentage by airflow difference to obtain airflow reduction 0 8 x 90 72 5 Subract airflow reduction value to airflow 0 50 to obtain actual airflow 0 58 ESP 2125 72 2053 ACCESSORIES PROPANE LP CONVER...

Page 6: ...lude Fan Switch NOTE For One stage Cool or One stage Heat Cool must be used with Subbase 2TB17700424 2TB17700424 SUBBASE 24V One stage heat cool Manual changeover integral subbase System Switch Cool O...

Page 7: ...Unitary Products Group 7 036 21560 001 Rev A 0204 NOTES...

Page 8: ...ct to change without notice Printed in U S A 036 21560 001 Rev A 0204 Copyright by York International Corp 2004 All rights reserved Supersedes Nothing Unitary 5005 Norman Products York OK Group Drive...

Reviews: