FILTER PERFORMANCE

The airflow capacity data published in the “Blower Perfor-
mance” table listed above represents blower performance
WITHOUT filters. To determine the approximate blower per-
formance of the system, apply the filter drop value for the fil-
ter being used or select an appropriate value from the “Filter
Performance” table shown below.

NOTE:  The filter pressure drop values in the “Filter Perfor-
mance” table shown below are typical values for the type of
filter listed and should only be used as a guideline. Actual
pressure drop ratings for each filter type vary between filter
manufacturer.

NOTES: 

1. Air velocity through throwaway type filters may not exceed 300 
feet per minute. All velocities over this require the use of high 
velocity filters.
2. Air flows above 1800 CFM require either return from two sides or 
one side plus bottom.

RECOMMENDED FILTER SIZES

Nominal CFM Cabinet Size Side Return Filter in.

Bottom Return 

Filter in. (cm)

1200

A

16 x 25

14 x 25

1200

B

16 x 25

16 x 25

1600

C

16 x 25

20 x 25

2000

C

16 x 25

20 x 25

2000

D

(2) 16 x 25

22 x 25

FILTER PERFORMANCE - PRESSURE DROP INCHES W.C.

Airflow Range

Minimum Opening Size

Filter Type

Disposable

WASHABLE FIBER

Pleated

1 Opening

2 Openings

1 Opening

2 Opening

1 Opening

2 Opening

1 Opening

2 Opening

Sq. in.

Sq. in.

In w.c.

In w.c.

In w.c.

In w.c.

In w.c.

In w.c.

0 - 750

230

0.01

0.01

0.15

751 - 1000

330

0.04

0.03

0.20

1001 - 1250

330

0.08

0.07

0.20

1251 - 1500

330

0.08

0.07

0.25

1501 - 1750

380

658

0.14

0.08

0.13

0.06

0.30

0.17

1751 - 2000

380

658

0.17

0.09

0.15

0.07

0.30

0.17

2001 & Above

463

658

0.17

0.09

0.15

0.07

0.30

0.17

UNIT CLEARANCES TO COMBUSTIBLES

Application

Top

Front

Rear

Left Side

Right Side

Flue

Floor/ 

Bottom

Closet 

Alcove

Attic

In.

In.

In.

In.

In.

In.

Upflow

1

3

0

0

0

0

Combustible

Yes

Yes

Summary of Contents for GY9S-UP

Page 1: ...aser 10 year warranty on the heat exchanger in commercial appli cations 5 year limited parts warranty FEATURES Compact easy to install ideal height 40 cabinet Blower off delay for cooling SEER improve...

Page 2: ...MAGE RETURN END TOP IMAGE SUPPLY END 1 1 2 GAS PIPE ENTRY 7 8 JUNCTION BOX HOLE T STAT WIRING 7 8 K O CONDENSATE DRAIN 7 8 K O Models Nominal CFM Cabinet Size Cabinet Dimension A in B in C in D in GY9...

Page 3: ...12UP11 60 B 56 1200 17 1 2 9 92 0 40 70 GY9S080B12UP11 80 B 74 1200 17 1 2 9 92 0 45 75 GY9S080C16UP11 80 C 75 1600 21 12 92 0 45 75 GY9S080C20UP11 80 C 75 2000 21 14 92 0 40 70 GY9S100C16UP11 100 C 9...

Page 4: ...680 1595 1500 1390 1270 1155 M LO 1610 1545 1490 1440 1390 1315 1230 1155 1050 920 LOW 1325 1270 1225 1175 1105 1045 990 905 890 790 GY9S080C16UP11 GY9S100C16UP11 HIGH 1960 1955 1925 1890 1830 1765 16...

Page 5: ...ers 2 Air flows above 1800 CFM require either return from two sides or one side plus bottom RECOMMENDED FILTER SIZES Nominal CFM Cabinet Size Side Return Filter in Bottom Return Filter in cm 1200 A 16...

Page 6: ...tage Cool Y Y2 Single Second Stage Cool Y Single Stage Cool DN11C00124 C 24 Volt Common C 24 Volt Common Optional w Batteries BN11C01124 DP11C40124 PSC FURNACE CONTROL SINGLE STAGE AIR CONDITIONING BN...

Page 7: ...ACCESSORIES PROPANE LP CONVERSION KIT 1NP0347 All Models This accessory conversion kit may be used to convert natural gas units for propane LP operation Conversions must be made by qualified distribut...

Page 8: ...change without notice Printed in U S A 277805 YTG A 1106 Copyright by York International Corp 2006 All rights reserved Supersedes 246716 YTG B 0806 Unitary 5005 Norman Products York OK Group Drive 73...

Reviews: