JOHNSON CONTROLS
FORM 201.23-EG1 (1007)
119
High Efficiency YCIV_ _ _ _ E/V
High Efficiency YCIV_ _ _ _ E/V
Model No./Nameplate
System 1
System 2
Std. & Ultra Quiet Cond. Fans
High Head/Static Cond. Fans
Two-Speed Cond. Fans
Std. & Ultra Quiet Cond. Fans
High Head/Static Cond. Fans
Two-Speed Cond. Fans
YCIV E/V
Input Volts
(9)
Input Freq
Compressor
Condenser Fans
Compressor
Condenser Fans
Compressor
Condenser Fans
Compressor
Condenser Fans
Compressor
Condenser Fans
Compressor
Condenser Fans
RLA (5)
Qty.
FLA (EA)
RLA (5)
Qty.
FLA (EA)
RLA (5)
Qty.
FLA (EA)
RLA (5)
Qty.
FLA (EA)
RLA (5)
Qty.
FLA (EA)
RLA (5)
Qty.
FLA (EA)
0157
460
60
110
4
2.8
110
4
2.8
380
60
139
4
3.5
139
4
9.3
139
4
3.5
139
4
9.3
0590
400
50
132
4
3.1
132
4
9.3
138
4
3.8
132
4
3.1
132
4
9.3
138
4
3.8
0177
460
60
111
5
2.8
122
4
2.8
380
60
141
5
3.5
141
5
9.3
154
4
3.5
154
4
9.3
0630
400
50
134
5
3.1
134
5
9.3
139
5
3.8
146
4
3.1
146
4
9.3
154
4
3.8
0187
460
60
154
5
2.8
105
5
2.8
380
60
195
5
3.5
195
5
9.3
132
5
3.5
132
5
9.3
0700
400
50
185
5
3.1
185
5
9.3
196
5
3.8
126
5
3.1
126
5
9.3
131
5
3.8
0197
460
60
141
5
2.8
141
5
2.8
380
60
179
5
3.5
179
5
9.3
179
5
3.5
179
5
9.3
0760
400
50
170
5
3.1
170
5
9.3
180
5
3.8
170
5
3.1
170
5
9.3
180
5
3.8
0207
460
60
141
6
2.8
152
5
2.8
380
60
179
6
3.5
179
6
9.3
193
5
3.5
193
5
9.3
0800
400
50
170
6
3.1
170
6
9.3
178
6
3.8
183
5
3.1
183
5
9.3
195
5
3.8
0227
460
60
150
6
2.8
150
6
2.8
380
60
190
6
3.5
190
6
9.3
190
6
3.5
190
6
9.3
0830
400
50
180
6
3.1
180
6
9.3
189
6
3.8
180
6
3.1
180
6
9.3
189
6
3.8
0247
460
60
194
6
2.8
149
6
2.8
380
60
245
6
3.5
245
6
9.3
188
6
3.5
188
6
9.3
0930
400
50
233
6
3.1
233
6
9.3
246
6
3.8
178
6
3.1
178
6
9.3
187
6
3.8
YCIV E/V
Control
KVA (7)
Unit Short Circuit Withstand (KA)
Field Wiring & Protection
Std. & Ultra Quiet Cond. Fans
High Head/High Static Fans
Two-Speed Cond. Fans
Terminal Block
(STD)
Circuit Breaker
(OPT)
Minimum Ckt.
Ampacity (MCA) (3)
Recommended
Fuse/Ckt. Breaker
Rating (4)
Max. Inverse Time
Ckt. Brkr. Rating (2)
Max Dual Element
Fuse Size (2)
Minimum Ckt. Am-
pacity (MCA) (3)
Recommended
Fuse/Ckt. Breaker
Rating (4)
Max. Inverse Time
Ckt. Brkr. Rating (2)
Max Dual Element
Fuse Size (2)
Minimum Ckt.
Ampacity (MCA) (3)
Recommended
Fuse/Ckt. Breaker
Rating (4)
Max. Inverse Time
Ckt. Brkr. Rating (2)
Max Dual Element
Fuse Size (2)
0157
1.8
30KA
65KA
270
300
350
350
1.8
30KA
65KA
341
400
450
450
388
450
500
500
0590
1.8
30KA
65KA
322
400
450
450
372
450
500
500
342
400
450
450
0177
1.8
30KA
65KA
288
350
400
400
1.8
30KA
65KA
365
450
500
500
417
500
500
500
0630
1.8
30KA
65KA
344
400
450
450
400
450
500
500
366
450
500
500
0187
1.8
30KA
65KA
325
400
450
450
1.8
30KA
65KA
411
500
600
600
469
600
600
600
0700
1.8
30KA
65KA
388
450
500
500
450
500
600
600
414
500
600
600
0197
1.8
30KA
65KA
345
400
450
450
1.8
30KA
65KA
437
500
600
600
495
600
600
600
0760
1.8
30KA
65KA
412
500
500
500
474
600
600
600
442
500
600
600
0207
1.8
30KA
65KA
362
450
500
500
1.8
30KA
65KA
458
600
600
600
522
600
700
700
0800
1.8
30KA
65KA
433
500
600
600
501
600
600
600
463
600
600
600
0227
1.8
30KA
65KA
371
450
500
500
1.8
30KA
65KA
469
600
600
600
539
600
700
700
0830
1.8
30KA
65KA
443
500
600
600
517
600
700
700
472
600
600
600
0247
1.8
30KA
65KA
424
500
600
600
1.8
30KA
65KA
536
700
700
700
606
700
800
800
0930
1.8
30KA
65KA
506
600
700
700
581
700
800
800
541
700
700
700
Summary of Contents for Latitude YCIV0157E
Page 115: ...JOHNSON CONTROLS FORM 201 23 EG1 1007 115 INTENTIONALLY LEFT BLANK...
Page 127: ...JOHNSON CONTROLS FORM 201 23 EG1 1007 127 INTENTIONALLY LEFT BLANK...
Page 128: ...JOHNSON CONTROLS 128 Typical Control Wiring Two Compressor...
Page 130: ...JOHNSON CONTROLS 130 Typical Control Wiring Three Compressor...
Page 138: ...JOHNSON CONTROLS 138...
Page 139: ...JOHNSON CONTROLS FORM 201 23 EG1 1007 139...
Page 140: ...Form 201 23 EG1 1007 Supersedes 201 23 EG1 607 File in ET2...