Rate Limit Close Setpoint – Now programmable over the range of 5% to 50%. Previously, it was 10% to
50%.
•
The duration of the open or close pulse applied to the Valve Actuator is now independent of the selected
Period Setpoint. It is now a
fi
xed percentage of 3.5 seconds. Previously, it was a percentage of the Pe-
riod Setpoint. Therefore, longer Periods would produce longer output pulses for the same error, result-
ing in unstable op er a tion under certain conditions.
Compressor Motor Variable Speed Drive
•
The conditions to produce the “Harmonic Filter – Logic Board or Communications” Cycling shutdown
must now be present for 10 communication cycles before a shutdown is performed.
•
If either the 50% or 30% Leaving Chilled Liquid Temperature
SENSITIVITY
Setpoint is selected,
Pre-rotation Vane movement is further reduced when the chiller is operating at low load. When the Vane
position is less than 25% and Leaving Chilled Liquid Temperature is 2.5 ºF of Setpoint, the
maximum Vane pulse is limited to 3.5 seconds at 25% position and 0.9 seconds at 0% position. Vane
positions in between have linearly scaled maximums.
•
In previous Flash Memory Card versions, the S
ET FREQUENCY
Setpoint feature on the
VSD TUN-
ING
Screen did not correctly set the desired frequency in 50Hz applications. This is corrected in this
version.
•
Harmonic Filter Currents are now correctly displayed at maximum values.
History
Chiller Run Time is now included on History Details display and print.
Hot Gas Bypass
The Hot Gas Valve position is now animated on the
HOT GAS BYPASS
Screen.
SI0019 - SOFTWARE ENHANCEMENTS EFFECTIVE MARCH 2002 (CONT'D)
Summary of Contents for MAXE OPTIVIEW YK
Page 28: ...YORK INTERNATIONAL 28 FORM 160 54 M1 503 Microboard FIG 7 MICROBOARD LD07776...
Page 60: ...YORK INTERNATIONAL 60 FORM 160 54 M1 503 Keypad FIG 32 KEYPAD CONNECTOR LD04074...
Page 61: ...FORM 160 54 M1 503 61 YORK INTERNATIONAL FIG 33 KEYPAD LD04075 LD04076 8...
Page 173: ...FORM 160 54 M1 503 173 YORK INTERNATIONAL 26 This page intentionally left blank...
Page 177: ...FORM 160 54 M1 503 177 YORK INTERNATIONAL 26 This page intentionally left blank...