FORM 160.54-M1(503)
67
YORK INTERNATIONAL
FIG. 38 –
CM-2 CURRENT MODULE – INTERFACE, CURRENT TRANSFORMERS & VARIABLE RESISTORS
LD04082
LD04081
NOTES:
A. Requires passing motor lead through current transformer (CT)
once
before connecting to power supply.
B. Requires passing motor lead through CT
twice
before con nect ing
to power supply.
C. Requires passing motor lead through CT
three
times before con-
necting to power supply.
D. Calculates resistance of “RES” to achieve 1.0VDC at FLA.
MOTOR CT
VOLTAGE
FLA
RATIO
RES
D
(OHMS)
65-111
A
200:1
208-600
112-224
A
350:1 R = 1.282 (CT RATIO)
225-829
A
700:1 FLA
830-1790
A
1400:1
11-18
C
200:1
R = 0.247 (CT RATIO)
FLA
19-37
B
200:1
R = 0.370 (CT RATIO)
2300-4160
FLA
38-123
A
200:1
R = 0.740 (CT RATIO)
124-264
A
350:1
FLA
265-518
A
700:1
10
Summary of Contents for MAXE OPTIVIEW YK
Page 28: ...YORK INTERNATIONAL 28 FORM 160 54 M1 503 Microboard FIG 7 MICROBOARD LD07776...
Page 60: ...YORK INTERNATIONAL 60 FORM 160 54 M1 503 Keypad FIG 32 KEYPAD CONNECTOR LD04074...
Page 61: ...FORM 160 54 M1 503 61 YORK INTERNATIONAL FIG 33 KEYPAD LD04075 LD04076 8...
Page 173: ...FORM 160 54 M1 503 173 YORK INTERNATIONAL 26 This page intentionally left blank...
Page 177: ...FORM 160 54 M1 503 177 YORK INTERNATIONAL 26 This page intentionally left blank...