11
TABLE 9:
Electrical Data For Single Source Power Supply: 208/230-3-60
Air Handler
Models
Heater
Models
1,2
Heater
Amps
@240V
Field Wiring
Min. Circuit Ampacity
MOP.
3
208V
230V
208V
230V
ME08B
6HK36501025
23.1
28.3
30.9
30
35
ME12B
6HK36501025
23.1
29.8
32.4
30
35
6HK36501525
34.6
42.2
46.2
45
50
6HK36501825
41.6
49.8
54.6
50
55
6HK46502025
2
46.2
54.8
60.1
55
70
ME14D
6HK36501025
23.1
29.8
32.4
30
35
6HK36501525
34.6
42.2
46.2
45
50
6HK36501825
41.6
49.8
54.6
50
55
ME16C
6HK36501025
23.1
31.8
34.4
35
35
6HK36501525
34.6
44.2
48.2
45
50
6HK36501825
41.6
51.8
56.6
55
60
6HK46502025
2
46.2
56.8
62.1
60
70
ME20D
6HK36501025
23.1
31.8
34.4
35
35
6HK36501525
34.6
44.3
48.2
45
50
6HK36501825
41.6
51.9
56.7
55
60
6HK46502025
2
46.2
56.8
62.0
60
70
6HK46502525
2
57.7
69.3
75.9
70
80
1. 6HK3 = 3-Phase with terminal block connections only, 6HK4 = 3-Phase with service disconnect.
2. The 20kW and 25kW heater models (6HK46502025 and 6HK46502525) come with circuit breakers standard. Single source power MCA and MOP
requirements are given here only for reference if used with field installed single point power modification (S1-32436041000).
3. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse. The 1st circuit includes blower motor amps.
Refer to the latest edition of the National Electric Code or in Canada the Canadian electrical Code and local codes to determine correct wire sizing.
TABLE 10:
Electrical Data For Multi-source Power Supply: 208/230-3-60
Air Handler
Models
Heater
Models
1
Heater
Amps
@240V
Min. Circuit Ampacity
MOP.
2
208V
230V
208V
230V
Circuit
Circuit
1st
3
2nd
1st
3
2nd
1st
3
2nd
1st
3
2nd
ME12B
6HK46502025
46.2
29.8
25.0
32.4
27.6
30
25
35
30
ME16C
6HK46502025
46.2
31.8
25.0
34.4
27.6
35
25
35
30
ME20D
6HK46502025
46.2
31.8
25.0
34.4
27.6
35
25
35
30
6HK46502525
57.7
38.0
31.3
41.3
34.6
40
35
45
35
1. The 20kW and 25kW heater models (6HK46502025 and 6HK46502525) come with circuit breakers standard.
2. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse. The 1st circuit includes blower motor amps.
Refer to the latest edition of the National Electric Code or in Canada the Canadian electrical Code and local codes to determine correct wire sizing.