background image

5169034-UIM-B-0216

Johnson Controls Unitary Products

7

SECTION VII: LOW VOLTAGE CONTROL 

CONNECTIONS

The 24 volt power supply is provided by an internally wired low voltage
transformer which is standard on all models. If the unit is connected to a
208 volt power supply, the low voltage transformer must be rewired to
the 208 volt tap. See the unit wiring diagram.
Field supplied low voltage wiring can exit the unit through the top right
(when unit is vertical upflow) or the right side panel. Refer to Figure 5.
Remove desired knockout and pierce foil faced insulation to allow
wiring to pass through. Use as small of a hole as possible to minimize
air leakage. Install a 7/8” plastic bushing in the selected hole and keep
low voltage wiring as short as possible inside the control box.
To further minimize air leakage, seal the wiring entry point at the
outside of the unit.
The field wiring is to be connected at the pigtails supplied with the air
handler. Refer to Figures 11 & 12 for system wiring.

SECTION VIII: BLOWER SPEED 

CONNECTIONS

Adjust blower motor speed to provide airflow within the minimum and
maximum limits approved for indoor coil, electric heat and outdoor unit.
Make speed tap adjustments at the motor terminal block. Refer to
airflow data listed in Table 11. Connect motor wires to motor speed tap
receptacle for speed desired.

The standard ECM motor operates when a 24 VAC signal is sent to any
of its 5-speed taps. If simultaneous 24 VAC inputs are present, the
motor operates at the highest speed tap that is energized. The lowest
speed is 1, and the highest speed is 5. The air handler comes factory
wired with the electric heat kit connected to tap 5 for the heating speed,
and the cooling heat pump connected to tap 4 for the heating speed.
The cooling / heat pump indicating speed is supplied by the thermostat
“G” signal. 
The electric heat kit wire for the heating speed should be moved from 5
to the appropriate speed tap according to Table 4. If electric heat
requires speed tap 5, the highest speed tap available for cooling / heat
pump heating is tap 4. 
If a lower circulating speed is desired for fan only operation (lower than
a heating or cooling fan speed), connect the factory “red” wire shipped
on tap #4 into the lowest setting desired. Field install a wire from low
voltage “YEL,” and connect it to the motor speed tap desired for cooling
/ heat pump heating fan speed. 

 FIGURE 9:  

Line Power Connections

),(/'32:(5:,5,1*
9

&20321(17&2'(6

*1'*5281'/8*
&%&,5&8,7%5($.(5
&.7&,5&8,7
&1:,5(&211(&725187

*1'

12(/(&75,&+($7

32:(5
6833/<

&1

&1

*1'

-803(5%$5

6,1*/(6285&(32:(5

08/7,6285&(32:(5

08/7,6285&(32:(5
:,7+-803(5%$5

7(50,1$/%/2&.25
&,5&8,7%5($.(5

32:(5
6833/<

32:(5
6833/<

6,1*/(6285&(32:(5

&,5&8,7621N:N:
&,5&8,7621N:

7(50,1$/%/2&.25
&,5&8,7%5($.(5

&.7

&.7

32:(5
6833/<

&%

&%

&%

&%

&%

32:(5
6833/<

*1'

*1'

*1'

*1'

32:(5
6833/<

/

/

/

/

/

/

&.7

/

/

/

/

&%

&%

&%

/

/

/

/

/

/

/

/

/

08/7,6285&(32:(5

&.7

&.7

&,5&8,7621N:N:
&,5&8,7621N:

3+$6((/(&75,&+($7237,216

3+$6((/(&75,&+($732:(5237,216

$

NOTICE

All wiring must comply with local and national electrical code require-

ments. Read and heed all unit caution labels.

NOTICE

It is possible to vary the amount of electric heat turned on during the
defrost cycle of a heat pump. Standard wiring will only bring on the
first stage of electric heat during defrost. See Table 6 for additional
information on heat during defrost cycle.

 FIGURE 10:  

Blower Speed Connections

ECM - HIGH EFFICIENCY MOTOR

1

2 3

4 5

C

G

L

N

GRN

S

TANDARD

E

CM

 (X

1

3)

BL

O

WER

MO

T

O

R

BLU/WHT

BLK/WHT

RED/WHT

BLK

RED

F

O

R

P

O

WER

WIRING

CO

NTR

O

L

WIRING

F

O

R

T

O

 

S

E

Q

UEN

C

ER HEATER

T

O

 RE

S

I

S

T

O

R

T

O

 RE

S

I

S

T

O

R

T

O

 

COMMO

O

N

TRAN

S

F

O

R

M

ER

T

O

 24

0

O

N

TRAN

S

F

O

R

M

ER

A

0

4

0

2-

001

Summary of Contents for ME08B

Page 1: ...ld installed accessories Single phase kits are available from 2 5 kW to 25 kW 208 230 volt three phase kits are available from 10kW to 25kW SECTION II SAFETY This is a safety alert symbol When you see...

Page 2: ...carrier s freight bill A separate request for inspection by the carrier s agent should be made in writing Also before installation the unit should be checked for screws or bolts which may have loosen...

Page 3: ...URATION These air handler units are supplied ready to be installed in an upflow downflow horizontal right or horizontal left position Refer to Figure 2 The unit requires no conversion procedures AIR H...

Page 4: ...ENSIONS C D 12 3 16 19 1 8 B 20 1 2 21 1 2 TABLE 1 Dimensions ME MODELS Dimensions1 Wiring Knockout Dimensions1 2 A B C D E F Height Width Bottom Opening Top Opening Power Control ME08B 21 1 2 17 1 2...

Page 5: ...d be designed in accordance with the Air Conditioning Contractors of America ACCA Manual D HORIZONTAL SUSPENSION For suspension of these units in horizontal applications it is recom mended to use angl...

Page 6: ...for Horizontal right hand airflow applica tion only Follow instructions with heater for modification SECTION VI LINE POWER CONNECTIONS Power may be brought into the unit through the supply air end of...

Page 7: ...heat kit connected to tap 5 for the heating speed and the cooling heat pump connected to tap 4 for the heating speed The cooling heat pump indicating speed is supplied by the thermostat G signal The...

Page 8: ...correct wire sizing TABLE 4 Electrical Heat Minimum Fan Speed Heater Kit Models1 2 3 Nom kW 240V Air Handler Models ME08B ME12B ME14D ME16C ME20D 6HK 0 1 6500206 2 4kW Med Lo 2 Med Lo 2 Med Lo 2 Med L...

Page 9: ...onnect OR 1 with service disconnect 2 1 2 1 with service disconnect no breaker jumper bar OR 2 with service disconnect breaker jumper bar 3 6HK3 3 Phase with terminal block connectors only 6HK4 3 Phas...

Page 10: ...Field Wiring Min Circuit Ampacity MOP 3 208V 230V 208V 230V TABLE 8 Electrical Data For Multi source Power Supply 208 230 1 60 Air Handler Models Heater Models Heater Amps 240V Min Circuit Ampacity M...

Page 11: ...A and MOP requirements are given here only for reference if used with field installed single point power modification S1 32436041000 3 MOP Maximum Overcurrent Protection device must be HACR type circu...

Page 12: ...MED HI 1272 1245 1209 1174 1143 1106 1073 3 MED 1072 1040 1007 973 937 874 778 2 MED LO 857 821 794 756 676 613 567 1 LO 654 606 557 504 443 379 271 CM30B 5 HI 1354 1325 1294 1263 1230 1198 1168 4 ME...

Page 13: ...52 1706 1680 1633 1591 1546 1511 2 MED LO 1545 1505 1468 1432 1393 1351 1307 1 LO 1340 1296 1260 1219 1169 1118 1055 CM48D 5 HI 2062 2024 1993 1952 1910 1868 1836 4 MED HI 2006 1958 1932 1890 1850 181...

Page 14: ...e fan only to assure a dry coil Drill 2 holes one 12 away from the air handler in the supply air duct and on 12 away from the air handler in the return air duct before any elbows in the duct work Inse...

Page 15: ...L AND NATIONAL CODES MUST BE FOLLOWED SEE INSTALLATION INSTRUCTIONS FOR PROPER LOW VOLTAGE FIELD WIRING CONNECTIONS LEGEND LS LIMIT SWITCH SEQ SEQUENCER HE HEATING ELEMENT FL FUSIBLE LINK H SEQUENCER...

Page 16: ...UE BLUE BLUE BLUE YELLOW YELLOW BLACK BLACK YELLOW YELLOW BLACK BLACK RED WHITE BLACK BLUE BLACK BLUE YELLOW BLACK YELLOW YELLOW BLUE BLACK BLUE BLACK YELLOW RLY 1 RLY 2 RLY 3 RLY 6 RLY 5 RLY 4 HE2 FL...

Page 17: ...dry bulb temperature Return air dry bulb temperature Temperature drop 1 2 3 4 5 Low Medium Low Medium Medium High High A B C D Outside air dry bulb temperature Return air wet bulb temperature Supply a...

Page 18: ...oting and correcting any problems Operate the unit through cooling cycles from the thermostat noting and correcting any problems Operate the unit through mechanical heating cycles from the thermostat...

Reviews: