YORK INTERNATIONAL
88
OPTIONAL SINGLE-POINT POWER SUPPLY CONNECTION TO FACTORY CIRCUIT BREAKER –
2 COMPRESSOR UNITS (SEE FIG.4)
(One Field Provided Power Supply Circuit to the chiller. Field Connection to Circuit Breaker in ‘Option Panel’.
No internal Individual System Circuit Protection per Motor Control Center
10
.)
NOTE:
Wye-Delta Compressor Start not available with this option.
See page 89 for Electrical Data footnotes.
FIELD SUPPLIED WIRING
SYSTEM #1
SYSTEM #2
MODEL
VOLTS
MCA
1
FACTORY SUPPLIED BREAKER
COMPRESSOR
FANS
11, 12
COMPRESSOR
FANS
11, 12
YCAS
RATING
2
WIRE RANGE
7
(LUGS)
RLA
X-LRA QTY FLA(ea) LRA(ea) RLA
X-LRA
QTY FLA(ea) LRA(ea)
380
218
300
#N/A
84
681
3
4.8
23.0
84
681
3
4.8
23.0
0090EC
460
182
250
# 14 - 250
70
542
3
4.0
19.0
70
542
3
4.0
19.0
575
143
200
# 14 - 250
55
431
3
3.1
15.2
55
431
3
3.1
15.2
380
227
300
250 - 500
88
681
3
4.8
23.0
88
681
3
4.8
23.0
0100EC
460
189
250
# 14 - 250
73
542
3
4.0
19.0
73
542
3
4.0
19.0
575
150
200
# 14 - 250
58
431
3
3.1
15.2
58
431
3
3.1
15.2
380
269
350
250 - 500
121
900
3
5.2
21.0
86
681
3
5.2
21.0
0110EC
460
225
300
# 14 - 250
99
719
3
5.0
27.0
71
542
3
5.0
27.0
575
181
250
# 14 - 250
81
574
3
3.9
26.0
56
431
3
3.9
26.0
380
280
400
250 - 500
130
900
3
5.2
21.0
86
681
3
5.2
21.0
0120EC
460
235
300
250 - 500
107
719
3
5.0
27.0
71
542
3
5.0
27.0
575
189
250
# 14 - 250
87
574
3
3.9
26.0
56
431
3
3.9
26.0
0130EC
460
273
400
(2) 3/0-250
107
719
4
4.0
19.0
107
719
4
4.0
19.0
575
217
250
# 6 - 350
86
574
4
3.1
15.2
86
574
4
3.1
15.2
0140EC
460
293
400
(2) 3/0-250
116
719
4
4.0
19.0
116
719
4
4.0
19.0
575
234
400
(2) 3/0-250
93
574
4
3.1
15.2
93
574
4
3.1
15.2
0150EC
460
307
400
(2) 3/0-250
128
893
4
4.0
19.0
115
719
4
4.0
19.0
575
246
400
(2) 3/0-250
103
714
4
3.1
15.2
92
574
4
3.1
15.2
0160EC
460
320
400
(2) 3/0-250
128
893
4
4.0
19.0
128
893
4
4.0
19.0
575
257
400
(2) 3/0-250
103
714
4
3.1
15.2
103
714
4
3.1
15.2
0170EC
460
335
400
(2) 3/0-250
140
893
4
4.0
19.0
128
893
4
4.0
19.0
575
268
400
(2) 3/0-250
112
714
4
3.1
15.2
103
714
4
3.1
15.2
0180EC
460
347
400
(2) 3/0-250
140
893
4
4.0
19.0
140
893
4
4.0
19.0
575
277
400
(2) 3/0-250
112
714
4
3.1
15.2
112
714
4
3.1
15.2
0200EC
460
375
600
(3) 2/0-400
149
893
5
4.0
19.0
149
893
5
4.0
19.0
575
299
400
(2) 3/0-250
119
714
5
3.1
15.2
119
714
5
3.1
15.2
0210EC
460
393
600
(3) 2/0-400
163
893
5
4.0
19.0
149
893
5
4.0
19.0
575
313
400
(2) 3/0-250
130
714
5
3.1
15.2
119
714
5
3.1
15.2
0230EC
460
407
600
(3) 2/0-400
163
893
5
4.0
19.0
163
893
5
4.0
19.0
575
324
400
(2) 3/0-250
130
714
5
3.1
15.2
130
714
5
3.1
15.2
Electrical Data
(Continued)
LEGEND
ACR-LINE
ACROSS THE LINE START
C.B.
CIRCUIT BREAKER
D.E.
DUAL ELEMENT FUSE
DISC SW
DISCONNECT SWITCH
FACT CB
FACTORY-MOUNTED CIRCUIT BREAKER
FLA
FULL LOAD AMPS
HZ
HERTZ
MAX
MAXIMUM
MCA
MINIMUM CIRCUIT AMPACITY
MIN
MINIMUM
MIN NF
MINIMUM NON-FUSED
RLA
RUNNING LOAD AMPS
S.P. WIRE
SINGLE-POINT WIRING
Y-
∆
WYE-DELTA START
X-LRA
ACROSS-THE-LINE INRUSH LOCKED ROTOR AMPS
Y-LRA
WYE-DELTA INRUSH LOCKED ROTOR AMPS
VOLTAGE CODE
-17 = 200-3-60
-28 = 230-3-60
-40 = 380-3-60
-46 = 460-3-60
-58 = 575-3-60
Electrical Notes