YORK INTERNATIONAL
55
FORM 150.62-NM2
Sys Switch Off tells that the system switch under OP-
TIONS is turned off. The system will not be allowed to
run until the switch is turned back on.
These messages inform the operator that the chilled liq-
uid temperature is below the point (determined by the
setpoint and control range) that the micro will bring on a
system or that the micro has not loaded the lead system
far enough into the loading sequence to be ready to bring
the lag system ON. The lag system will display this mes-
sage until the loading sequence is ready for the lag sys-
tem to start.
The COMPS RUNNING message indicates that the re-
spective system is running due to demand. The “X” will
be replaced with the number of compressors in that sys-
tem that are running.
The anti-recycle timer message shows the amount of
time left on the respective systems anti-recycle timer.
This message is displayed when the system is unable
to start due the anti-recycle timer being active.
The anti-coincident timer is a software feature that
guards against 2 systems starting simultaneously. This
assures instantaneous starting current does not become
excessively high due to simultaneous starts. The micro
limits the time between compressor starts to 1 minute
regardless of demand or the anti-recycle timer being
timed out. The anti-coincident timer is only present on
two system units.
When this message appears, discharge pressure limit-
ing is in effect. The Discharge Pressure Limiting feature
is integral to the standard software control; however the
discharge transducer is optional. Therefore, it is impor-
tant to keep in mind that this control will not function
unless the optional discharge transducer is installed in
the system.
The limiting pressure is a factory set limit to keep the
system from faulting on the high discharge pressure
cutout due to high load or pull down conditions. When
the unload point is reached, the micro will automatically
unload the affected system by deenergizing one com-
pressor. The discharge pressure unload will occur when
the discharge pressure gets within 15 PSIG of the pro-
grammed discharge pressure cutout. This will only hap-
pen if the system is fully loaded and will shut only one
compressor off. If the system is not fully loaded, dis-
charge limiting will not go into effect. Reloading the af-
fected system will occur when the discharge pressure
drops to 85% of the unload pressure and 10 minutes
have elapsed.
S Y S
1
N O
C O O L
L O A D
S Y S
2
N O
C O O L
L O A D
S Y S
1
S Y S
S W I T C H
O F F
S Y S
2
S Y S
S W I T C H
O F F
S Y S
1
A R
T I M E R
X X
S
S Y S
2
A R
T I M E R
X X
S
S Y S
1
C O M P S
R U N
X
S Y S
2
C O M P S
R U N
X
S Y S
1
A C
T I M E R
X X
S
S Y S
2
A C
T I M E R
X X
S
S Y S
1
D S C H
L I M I T I N G
S Y S
2
D S C H
L I M I T I N G
2
Summary of Contents for MILLENNIUM YCAL0043SC
Page 106: ...YORK INTERNATIONAL 106 ELEMENTARY DIAGRAM YCAL0043SC YCAL0087SC FIG 11 ELEMENTARY DIAGRAM ...
Page 109: ...YORK INTERNATIONAL 109 FORM 150 62 NM2 This page intentionally left blank ...
Page 110: ...YORK INTERNATIONAL 110 ELEMENTARY DIAGRAM YCAL0107SC FIG 13 ELEMENTARY DIAGRAM ...
Page 112: ...YORK INTERNATIONAL 112 FIG 14 ELEMENTARY DIAGRAM ELEMENTARY DIAGRAM YCAL0107SC LD03534 ...
Page 113: ...YORK INTERNATIONAL 113 FORM 150 62 NM2 This page intentionally left blank ...
Page 114: ...YORK INTERNATIONAL 114 ELEMENTARY DIAGRAM YCAL0117SC YCAL0173SC FIG 15 ELEMENTARY DIAGRAM ...
Page 116: ...YORK INTERNATIONAL 116 ELEMENTARY DIAGRAM YCAL0117SC YCAL0173SC FIG 16 ELEMENTARY DIAGRAM ...
Page 118: ...YORK INTERNATIONAL 118 ELEMENTARY DIAGRAM YCAL0197SC YCAL0253SC FIG 17 ELEMENTARY DIAGRAM ...
Page 120: ...YORK INTERNATIONAL 120 ELEMENTARY DIAGRAM YCAL0197SC YCAL0253SC FIG 18 ELEMENTARY DIAGRAM ...
Page 129: ...YORK INTERNATIONAL 129 FORM 150 62 NM2 This page intentionally left blank ...
Page 130: ...YORK INTERNATIONAL 130 This page intentionally left blank ...
Page 131: ...YORK INTERNATIONAL 131 FORM 150 62 NM2 This page intentionally left blank ...