YORK INTERNATIONAL
84
EVAPORATOR PUMP CONTROL
The evaporator pump dry contacts (CTB2 - terminals 23
- 24) are energized when any of the following conditions
are true:
1. Low Leaving Chilled Liquid Fault
2. Any compressor is running
3. Daily Schedule is not programmed OFF and
Unit Switch is ON.
The pump will not run if the micropanel has been pow-
ered up for less than 30 seconds or if the pump has run
in the last 30 seconds to prevent pump motor overheat-
ing.
EVAPORATOR HEATER CONTROL
The evaporator heater is controlled by ambient air tem-
perature. When the ambient temperature drops below
40°F (4.4
°C)
the heater is turned on. When the tempera-
ture rises above 45°F (7.2
°C)
the heater is turned off. An
under voltage condition will keep the heater off until full
voltage is restored to the system.
CONDENSER FAN CONTROL
Condenser fan operation must be programmed with the
Options key under “Fan Control.” Condenser fan control
can be selected for Ambient Temp. and Disch. Pres-
sure, or Discharge Pressure Only.
The condenser fan control by “Ambient Temperature and
Discharge Pressure” is a feature that is integral to the
standard software control. If the optional discharge trans-
ducer is not installed, the condenser fans will operate
based on outdoor ambient temperature only. See Table
36.
The condenser fan control by “Discharge Pressure” is a
feature that can be selected if the discharge pressure
transducer is installed and fan recycling is not a con-
cern. Fan control by discharge pressure will work ac-
cording to Table 37. The fan control on-pressure
(ctrl_press) and fan differencial off-pressure (diff_press)
are programmable under the PROGRAM key.
TABLE 36
– CONDENSER FAN CONTROL USING OUTDOOR AMBIENT TEMPERATURE AND DISCHARGE
PRESSURE
FAN STAGE
ON
OFF
OAT>25° F (-3.9°C)
OAT < 20° F (-6.7°C)
1 - 1 FAN FWD
OR
AND
DP > ctrl_press
DP < ctrl_press - diff_press
OAT>45° F (7.2°C)
OAT < 40° F (4.4°C)
2 - 2 FANS FWD
OR
AND
DP > ctrl 20 PSIG (1.38 Bars) DP < ctrl_press - diff 20 PSIG (1.38 Bars)
TABLE 37
– CONDENSER FAN CONTROL USING DISCHARGE PRESSURE ONLY
FAN STAGE
ON
OFF
1 - 1 FAN FWD
DP > ctrl_press
DP < ctrl_press - diff_press
2 - 2 FANS FWD
DP > ctrl_press + 20 psig (1.38 Bars) DP < ctrl_press - diff 20 psig (1.38 Bars)
Unit Controls
Summary of Contents for MILLENNIUM YCAL0043SC
Page 106: ...YORK INTERNATIONAL 106 ELEMENTARY DIAGRAM YCAL0043SC YCAL0087SC FIG 11 ELEMENTARY DIAGRAM ...
Page 109: ...YORK INTERNATIONAL 109 FORM 150 62 NM2 This page intentionally left blank ...
Page 110: ...YORK INTERNATIONAL 110 ELEMENTARY DIAGRAM YCAL0107SC FIG 13 ELEMENTARY DIAGRAM ...
Page 112: ...YORK INTERNATIONAL 112 FIG 14 ELEMENTARY DIAGRAM ELEMENTARY DIAGRAM YCAL0107SC LD03534 ...
Page 113: ...YORK INTERNATIONAL 113 FORM 150 62 NM2 This page intentionally left blank ...
Page 114: ...YORK INTERNATIONAL 114 ELEMENTARY DIAGRAM YCAL0117SC YCAL0173SC FIG 15 ELEMENTARY DIAGRAM ...
Page 116: ...YORK INTERNATIONAL 116 ELEMENTARY DIAGRAM YCAL0117SC YCAL0173SC FIG 16 ELEMENTARY DIAGRAM ...
Page 118: ...YORK INTERNATIONAL 118 ELEMENTARY DIAGRAM YCAL0197SC YCAL0253SC FIG 17 ELEMENTARY DIAGRAM ...
Page 120: ...YORK INTERNATIONAL 120 ELEMENTARY DIAGRAM YCAL0197SC YCAL0253SC FIG 18 ELEMENTARY DIAGRAM ...
Page 129: ...YORK INTERNATIONAL 129 FORM 150 62 NM2 This page intentionally left blank ...
Page 130: ...YORK INTERNATIONAL 130 This page intentionally left blank ...
Page 131: ...YORK INTERNATIONAL 131 FORM 150 62 NM2 This page intentionally left blank ...