46
YORK INTERNATIONAL
NOTES:
1. For leaving brine temperature below 4.40°C (40°F), contact your nearest YORK office for application requirements.
2. For leaving water temperature higher than 12.8°C (55°F) contact the nearest YORK office for application guidelines.
3. The evaporator is protected against freezing to -28.8°C (-20°F) with an electric heater as standard.
TEMPERATURE AND FLOWS
(SI UNITS)
Technical Data
Excessive flow, above the max GPM,
will damage the evaporator.
MODEL
LEAVING WATER
COOLER FLOW
AIR ON
NUMBER
TEMPERATURE (°C)
(L/S)
3
CONDENSER (°C)
YCAS
MIN.
1
MAX.
2
MIN.
MAX.
MIN.
MAX
0693
4.4
13.0
14.0
50.0
-17.7
51.7
0773
4.4
13.0
14.0
50.0
-17.7
51.7
0783
4.4
13.0
14.0
50.0
-17.7
51.7
0873
4.4
13.0
16.0
50.0
-17.7
51.7
0953
4.4
13.0
16.0
50.0
-17.7
51.7
1063
4.4
13.0
19.0
67.0
-17.7
51.7
1093
4.4
13.0
21.0
67.0
-17.7
51.7
1163
4.4
13.0
21.0
67.0
-17.7
51.7
1263
4.4
13.0
21.0
67.0
-17.7
51.7