FORM 201.18-NM4
FORM 201.18-NM4
YORK INTERNATIONAL
YORK INTERNATIONAL
85
85A
LD04266
UNIT
CONTROL
MIN
MAX DUAL NON-FUSED
VOLTAGE
POWER
CIRCUIT
ELEMENT
DISC.
SUPPLY
AMP.
FUSE SIZE SWITCH SIZE
ALL MODELS
115-1-50/60
20A
20A 250V
30A 240V
W/O TRANS.
MODELS
-17
200-1-60
15A
15A 250V
30A 240V
WITH
-28
230-1-60
15A
15A 250V
30A 240V
TRANS.
-46
400-1-60
8A
8A 600V
30A 480V
*
-58
575-1-60
8A
8A 600V
30A 600V
* All primary and secondary wiring between transformer and control panel included.
CONTROL POWER SUPPLY
CAUTION:
No Controls (relays, etc.) should
be mounted in the Smart Panel
enclosure or connected to power
supplies in the control panel.
Additionally, control wiring not
connected to the Smart Panel
should not be run through the
cabinet. This could result in nui-
sance faults.
CAUTION:
Any inductive devices (relays)
wired in series with the flow
switch for start/stop, into the
Alarm circuitry, or pilot relays for
pump starters wired through mo-
tor contactor auxiliary contacts
must be suppressed with YORK
P/N 031-00808-000 suppressor
across the relay/contactor coil.
Any contacts connected to flow
switch inputs or BAS inputs on
terminals 13 - 19 or TB3, or any
other terminals, must be sup-
pressed with a YORK P/N 031-
00808-000 suppressor across
the relay/contactor coil.
CAUTION:
Control wiring connected to the
control panel should never be run
in the same conduit with power
wiring.
ELEMENTARY DIAGRAM
Summary of Contents for Millennium YCAS 0693
Page 49: ...49 YORK INTERNATIONAL FORM 201 18 NM4 7 This page intentionally left blank...
Page 65: ...65 YORK INTERNATIONAL FORM 201 18 NM4 LD04179 7...
Page 79: ...79 YORK INTERNATIONAL FORM 201 18 NM4 This page intentionally left blank 7...
Page 83: ...83 YORK INTERNATIONAL FORM 201 18 NM4 This page intentionally left blank 7...
Page 87: ...87 YORK INTERNATIONAL FORM 201 18 NM4 LD04268 7...