100
YORK INTERNATIONAL
DIMENSIONS - YCAS 300 - 330 (ENGLISH)
FIG. 49 – MODEL 300 - 330 DIMENSIONS (ENGLISH DIMENSIONS)
NOTES:
1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance,
reliable operation and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpre-
dictable air flow patterns and possible diminished performance. YORK's unit controls will optimize operation without nuisance high
pressure safety cutout; however, the system designer must consider potential performance degradation. Access to the unit control center
assumes the unit is no higher than on spring isolators. Recommended minimum clearances: Side to wall - 6'; rear to wall - 6'; control
panel end to wall - 4'; top - no obstructions allowed; distance between adjacent units - 10'. No more than one adjacent wall may be higher
than the unit.
LD05013
CONTROL ENTRY
(12) 1/2"
CONDUIT K.O.'S
9"
28"
2" TYP.
2"
4 3/4"
12"
VIEW B-B
VIEW C-C
7"
CONTROL
OPENING
(9" HIGH)
2"
POWER
OPENING
(21" HIGH)
7 1/2"
31 1/2"
42"
LD03980
91-13/16"
POWER OPENING
(7" WIDE x
21" HIGH)
CONTROL
TRANSFORMER
SERVICE SWITCH
4-7/16" (EDGE OF
UNIT TO COOLER
CONNECTION)
C
C
OPTIONS PANEL
MICRO-COMPUTER
CONTROL CENTER
B
B
20-1/8"
VIEW A-A
It is recommended that
power wiring enters
on the right side.
If left side entry is used,
be sure that space is
available for power wire
bending radius.
Technical Data
Summary of Contents for MILLENNIUM YCAS 250
Page 61: ...61 YORK INTERNATIONAL FORM 201 18 NM3 This page intentionally left blank 7...
Page 65: ...65 YORK INTERNATIONAL FORM 201 18 NM3 LD04179 7...
Page 79: ...79 YORK INTERNATIONAL FORM 201 18 NM3 This page intentionally left blank 7...
Page 83: ...83 YORK INTERNATIONAL FORM 201 18 NM3 This page intentionally left blank 7...
Page 87: ...87 YORK INTERNATIONAL FORM 201 18 NM3 LD04268 7...
Page 195: ...195 YORK INTERNATIONAL FORM 201 18 NM3 This page intentionally left blank...