137
YORK INTERNATIONAL
FORM 201.18-NM3
1. INTRODUCTION & PHYSICAL DESCRIPTION
29023A
1.1 GENERAL
The YORK Millennium Screw Chiller Control Panel is
a microprocessor based control system fitted to YCAS
liquid chillers. It is capable of multi-refrigerant system
control to maintain chilled liquid temperature within
programmed limits and to provide safety control of the
chiller. The microprocessor monitors leaving chilled
liquid temperature deviation from setpoint and the rate
of change of this temperature to start, stop, load and
unload compressors as required.
User interface is via a touch keypad and a liquid crystal
display allowing access to operating and programmed
data. Information can be displayed in English (Impe-
rial) units or S.I. (Metric) units (Section 8.1). Conver-
sion tables are provided at the back of this manual.
A master ON/OFF rocker switch is provided on the
chiller control panel to activate or deactivate the com-
plete chiller, while switches to activate or deactivate
individual refrigerant systems are provided on the Mi-
croprocessor Board(s).
External interface is available for control of the chiller
via a YORK ISN System or YORK Remote Control
Center. In addition, EMS/BAS System connections are
provided for remote cycling, current limiting, remote
temperature setpoint reset and alarm annunciation.
YCAS chillers each have a single split circuit evapora-
tor serving either 2, 3, or 4 independent refrigerant sys-
tems. YCAS 2 and 3-system chillers are configured as
a single self contained section with a single control panel
controlling the two refrigerant systems. YCAS 4-sys-
tem chillers are divided into 2 sections.
1.2 KEYPAD & DISPLAY
An operator keypad allows complete control of the
chiller from a central location. The keypad offers a
multitude of commands available to access displays,
program setpoints, and initiate system commands. Keys
are grouped and color coded for clarity and ease of use.
A 40 Character Liquid Crystal Display (2 lines of 20
characters) is used for displaying system parameters
and operator messages. The display has a lighted back-
ground for night viewing as well as a special feature
which intensifies the display for viewing in direct
sunlight.
Displays will be updated every two seconds by the mi-
croprocessor.
8
Summary of Contents for MILLENNIUM YCAS 250
Page 61: ...61 YORK INTERNATIONAL FORM 201 18 NM3 This page intentionally left blank 7...
Page 65: ...65 YORK INTERNATIONAL FORM 201 18 NM3 LD04179 7...
Page 79: ...79 YORK INTERNATIONAL FORM 201 18 NM3 This page intentionally left blank 7...
Page 83: ...83 YORK INTERNATIONAL FORM 201 18 NM3 This page intentionally left blank 7...
Page 87: ...87 YORK INTERNATIONAL FORM 201 18 NM3 LD04268 7...
Page 195: ...195 YORK INTERNATIONAL FORM 201 18 NM3 This page intentionally left blank...