187
YORK INTERNA
TIONAL
FORM 201.18-NM3
PROCEDURE
WEEKLY
QUARTERLY
SEMI-ANNUALLY
YEARLY
EVERY
___ HOURS
Check oil level in oil separator sight glass
X
Check liquid line sight glass / moisture indicator
X
Record system operating pressures and temperatures
X
Check programmable operating setpoints and safety cut-outs
and assure they are correct for particular application.
X
Check condenser coils for dirt/debris and clean if necessary
X
Check compressor superheat on evaporator and economizer
TXV’s; Check condenser and economizer subcooling
1
X
Check compressor and cooler heaters for operation
X
Sample compressor oil and replace oil if necessary
1
X
Leak check the chiller
1
X
Disconnect power source and lock out; Check tightness of
power wiring connections
1
X
MAINTENANCE REQUIREMENTS FOR YORK YCAS SCREW CHILLERS
*
* Reserved for customer use for any special site determined requirements.
1
This procedure must be performed at the specified time interval by an Industry Certified Technician who has been trained and qualified to work on this type of YORK
equipment. A record of this procedure being successfully carried out must be maintained on file by the equipment owner should proof of adequate maintenance be
required at a later date for warranty validation purposes.
9
Summary of Contents for MILLENNIUM YCAS 250
Page 61: ...61 YORK INTERNATIONAL FORM 201 18 NM3 This page intentionally left blank 7...
Page 65: ...65 YORK INTERNATIONAL FORM 201 18 NM3 LD04179 7...
Page 79: ...79 YORK INTERNATIONAL FORM 201 18 NM3 This page intentionally left blank 7...
Page 83: ...83 YORK INTERNATIONAL FORM 201 18 NM3 This page intentionally left blank 7...
Page 87: ...87 YORK INTERNATIONAL FORM 201 18 NM3 LD04268 7...
Page 195: ...195 YORK INTERNATIONAL FORM 201 18 NM3 This page intentionally left blank...