46
YORK INTERNATIONAL
NOTES:
1. For leaving brine temperature below 40°F (4.40°C), contact your nearest YORK office for application requirements.
2. For leaving water temperature higher than 55°F (12.8°C) contact the nearest YORK office for application guidelines.
3. The evaporator is protected against freezing to -20°F (-28.8°C) with an electric heater as standard.
TEMPERATURE AND FLOWS
(ENGLISH UNITS)
TEMPERATURE AND FLOWS
(SL UNITS)
MODEL
LEAVING WATER
COOLER FLOW
AIR ON
NUMBER
TEMPERATURE
(°
F)
(GPM
3
)
CONDENSER (
°
F)
YCAS
MIN.
1
MAX.
2
MIN.
MAX.
MIN.
MAX
0250EC
40
55
225
800
0
125
0270EC
40
55
225
800
0
125
0300EC
40
55
255
800
0
125
0330EC
40
55
255
800
0
125
0360EC
40
55
300
1060
0
125
0400EC
40
55
330
1060
0
125
0440EC
40
55
330
1060
0
125
MODEL
LEAVING WATER
COOLER FLOW
AIR ON
NUMBER
TEMPERATURE (
°
C)
(L/S)
3
CONDENSER (
°
C)
YCAS
MIN.
1
MAX.
2
MIN.
MAX.
MIN.
MAX
0250EC
4.4
12.8
14.0
50.0
-17.7
51.7
0270EC
4.4
12.8
14.0
50.0
-17.7
51.7
0300EC
4.4
12.8
16.0
50.0
-17.7
51.7
0330EC
4.4
12.8
16.0
50.0
-17.7
51.7
0360EC
4.4
12.8
19.0
67.0
-17.7
51.7
0400EC
4.4
12.8
21.0
67.0
-17.7
51.7
0440EC
4.4
12.8
21.0
67.0
-17.7
51.7
Technical Data
Excessive flow, above the max GPM,
will damage the evaporator.
Summary of Contents for MILLENNIUM YCAS 250
Page 61: ...61 YORK INTERNATIONAL FORM 201 18 NM3 This page intentionally left blank 7...
Page 65: ...65 YORK INTERNATIONAL FORM 201 18 NM3 LD04179 7...
Page 79: ...79 YORK INTERNATIONAL FORM 201 18 NM3 This page intentionally left blank 7...
Page 83: ...83 YORK INTERNATIONAL FORM 201 18 NM3 This page intentionally left blank 7...
Page 87: ...87 YORK INTERNATIONAL FORM 201 18 NM3 LD04268 7...
Page 195: ...195 YORK INTERNATIONAL FORM 201 18 NM3 This page intentionally left blank...