YORK INTERNATIONAL
12
FORM 201.19-W1 (304)
ELECTRICAL DATA (CONT'D)
Suitable for:
Across-The-Line-Start
One
fi
eld provided power supply circuit to the unit. Field
con nec tions to factory pro vid ed Circuit Breaker in the Op-
tions Panel. Factory con nec tions to Terminal Blocks in
each of the two Power Pan els.
OPTIONAL SINGLE-POINT POWER SUPPLY
CONNECTION TO FACTORY CIRCUIT BREAKER
OPTIONAL SINGLE-POINT POWER SUPPLY CONNECTION TO FACTORY CIRCUIT BREAKER –
2 COMPRESSOR UNITS
(One Field Provided Power Supply Circuit to the chiller. Field Connections to Factory Provided Circuit Breaker.
No Internal Branch Circuit Protection (Breakers) per Motor Control Center
10
.)
NOTES:
Wye-Delta Compressor Start not available with this op tion.
See page 4 for Electrical Data footnotes.
NOTES:
1. – – – – – – – Dashed Line indicates Field Provided Wiring.
2. The above recommendations are based on the National Electric Code and using copper connectors only.
Field wiring must also comply with local codes.
See page 4 for notes.
FIELD SUPPLIED WIRING SYSTEM #1 SYSTEM #2
MODEL
VOLTS
MCA
1
FACTORY SUPPLIED BREAKER COMPRESSOR FANS
11, 12
COMPRESSOR FANS
11, 12
YCAS
RATING
2
WIRE RANGE
7
(LUGS) RLA X-LRA QTY FLA(ea) LRA(ea) RLA X-LRA QTY FLA(ea) LRA(ea)
0130EC
460 273 400 (2) 3/0-250 107 719 4 4.0 19.0 107 719 4 4.0 19.0
575 217 250 # 6 - 350 86 574 4 3.1 15.2 86 574 4 3.1 15.2
0140EC
460 293 400 (2) 3/0-250 116 719 4 4.0 19.0 116 719 4 4.0 19.0
575 234 400 (2) 3/0-250 93 574 4 3.1 15.2 93 574 4 3.1 15.2
0150EC
460 307 400 (2) 3/0-250 128 893 4 4.0 19.0 115 719 4 4.0 19.0
575 246 400 (2) 3/0-250 103 714 4 3.1 15.2 92 574 4 3.1 15.2
0160EC
460 320 400 (2) 3/0-250 128 893 4 4.0 19.0 128 893 4 4.0 19.0
575 257 400 (2) 3/0-250 103 714 4 3.1 15.2 103 714 4 3.1 15.2
0170EC
460 335 400 (2) 3/0-250 140 893 4 4.0 19.0 128 893 4 4.0 19.0
575 268 400 (2) 3/0-250 112 714 4 3.1 15.2 103 714 4 3.1 15.2
0180EC
460 347 400 (2) 3/0-250 140 893 4 4.0 19.0 140 893 4 4.0 19.0
575 277 400 (2) 3/0-250 112 714 4 3.1 15.2 112 714 4 3.1 15.2
0200EC
460 375 600 (3) 2/0-400 149 893 5 4.0 19.0 149 893 5 4.0 19.0
575 299 400 (2) 3/0-250 119 714 5 3.1 15.2 119 714 5 3.1 15.2
0210EC
460 393 600 (3) 2/0-400 163 893 5 4.0 19.0 149 893 5 4.0 19.0
575 313 400 (2) 3/0-250 130 714 5 3.1 15.2 119 714 5 3.1 15.2
0230EC
460 407 600 (3) 2/0-400 163 893 5 4.0 19.0 163 893 5 4.0 19.0
575 324 400 (2) 3/0-250 130 714 5 3.1 15.2 130 714 5 3.1 15.2
LD05551
Summary of Contents for Millennium YCAS0130EC
Page 5: ...YORK INTERNATIONAL 5 FORM 201 19 W1 304 This page intentionally left blank...
Page 25: ...YORK INTERNATIONAL 25 FORM 201 19 W1 304 LEGEND LD09241...
Page 26: ...YORK INTERNATIONAL 26 FORM 201 19 W1 304 LD03282 LD03283 2 ACE MOTOR PROTECTOR MODULE LD03284...
Page 31: ...YORK INTERNATIONAL 31 FORM 201 19 W1 304 NOTES...