YORK INTERNATIONAL
17
FORM 155.16-O3
CHECK PROGRAMMED
“MAX ALLOWED
LOADING” VALUE
(50-100%)
AT MAX
ALLOWED
LOADING
DISPLAY “SYSTEM RUN”
MAXIMUM COOLING
LIMIT LOAD COMMAND
TO MAXIMUM ALLOWED
LOADING (50-100%)
CHECK CONDENSER
WATER FLOW SWITCH
@ TB2-20
OPEN
FOR 30
SECONDS
CYCLING SHUTDOWN
DISPLAY “DAY-TIME-COND
FLOW SWITCH-
AUTOSTART” AS STATUS
COMPARE LEAVING
CHILLED WATER TEMP TO
LEAVING WATER TEMP
SETPOINT
AUTO
SOLENOID
CONTROL
DE-ENERGIZE (CLOSE)
REFRIGERANT LEVEL
SOLENOID VALVE (3SOL)
LCWT
> (SP-2) &
< (SP+5)
REFRIG
LEVEL
FLOAT SW
OPEN
ENERGIZE (OPEN)
REFRIGERANT LEVEL
SOLENOID VALVE (3SOL)
13
➤
➤➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
PAGE 46
A
A