38
YORK INTERNATIONAL
6
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
START 30 MINUTE
CHILLED WATER
PUMP TIMER
CLOSE SAFETY
STATUS CONTACTS
TB4-42/43
SAFETY SHUTDOWN-
DISPLAY “DAY-TIME-LOW
REFRIGERANT TEMP-
ANALOG” AS STATUS
DE-ENERGIZE
(CLOSE) STABILIZER
REFRIGERANT SOLENOID
VALVE (2 SOL)
REFRIG
TEMP > 37°F
(2.8°C)
START ALL
PUMPS
30 MIN
CHILLED WATER
PUMP TIMER
ELAPSED
YES
YES
YES
YES
NO
PAGE 56
NO
NO
NO
REFRIG
TEMP < 33°F
(.6°C)
REFRIG
TEMP > 36°F
(2.2°C)
SHUTDOWN
CHILLED
WATER PUMP
A
B
A
B
C
D