54
YORK INTERNATIONAL
E
START
ALL PUMPS
CHECK STRONG
SOLUTION TEMP
@ RT 3
➤
➤
➤
>136°F
(57.8°C)
STEAM
UNIT
ENERGIZE 6 SOL
TO OPEN STEAM
CONDENSATE DRAIN
VALVE
DISPLAY “DAY-TIME-LRT-
CHK FOR CRYSTALLIZATION”
AS STATUS
START 6-MINUTE
DILUTION CYCLE
TIMER
ENTER DILUTION
CYCLE @
22
PAGE 36
EXIT DILUTION
CYCLE @
*
PAGE 42
6 MIN.
DILUTION
TIMER
ELAPSED
LRT
CUTOUT
TRIPPED
30 MIN.
CHILL WATER
PUMP TIMER
ELAPSED
SHUTDOWN
CHILLED
WATER
PUMP
LRT
CUTOUT
TRIPPED
UNIT
SW IN
STOP/
RESET
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
NO
NO
NO
NO
NO
NO
NO
YES
YES
➤
YES
YES
YES
YES
YES
A
B
C
A
B
D
C