background image

FORM 160.54-PW7

11

YORK INTERNATIONAL

0-10VDC - As shown in Fig. 18, connect input to
Microboard J22-3 (signal) and J22-5 (Gnd). A 0VDC
signal produces a 0°F offset. A 10VDC signal pro-
duces the maximum offset (10 or 20°F above the Lo-
cal Setpoint value). The setpoint is changed linearly
between these extremes as the input varies linearly
over the range of 0VDC to 10VDC. This input will
only be accepted when “Analog” Remote Mode is
selected., the “Remote Analog Input Range”
setpoint is set for “0-10VDC” and Microboard Pro-
gram Jumper JP24 has been removed. Calculate the
setpoint for various inputs as follows:

OFFSET(°F) = (VDC)(REMOTE RESET TEMP. RANGE)

        10

SETPOINT (°F) = LOCAL SE OFFSET

For example, if the input is 5VDC and the Remote Re-
set Temp Range setpoint is programmed for 10°F and
the Local Leaving Chilled Liquid Temperature setpoint
is programmed for 40°F, the setpoint would be set to
45°F as follows:

        OFFSET (°F) = 5 X 10

     10

= 50
   10

= 5°F

    SETPOINT (°F)

= 40 + 5

= 45°F

2-10VDC - As shown in Fig. 18, connect input to
Microboard J22-3 (signal) and J2-5 (Gnd). A 2VDC
signal produces a 0°F offset. A 10VDC signal produces
the maximum allowed offset (10°F or 20°F above the
Local Setpoint Value). The setpoint is changed linearly
between these extremes as the input varies over the
range of 2VDC to 10VDC. This input will only be ac-
cepted when “Analog” Remote Mode is selected,
the  “Remote Analog Input Range” setpoint is set
for “2-10VDC” and the Microboard Program Jumper
JP24 has been removed. Calculate the setpoint for vari-
ous inputs as follows:

OFFSET (°F) = (VDC – 2)(REMOTE RESET TEMP. RANGE)

8

SETPOINT (°F) = LOCAL SE OFFSET

For example, if the input is 5VDC and the Remote Re-
set Temp. Range setpoint is programmed for 40°F, the
setpoint would be set to 43.8°F.

SIGNAL

COMMON

5

3

+

J22

FIG. 18 – REMOTE LEAVING CHILLED LIQUID TEMP.

SETPOINT WITH 0-10VDC OR 2-10 VDC
SIGNAL

LD04500

changed over the range of 10° or 20ºF (as per the lo-
cally programmed Remote Reset Temperature
Range 
setpoint) above the Local Leaving Chilled Liq-
uid Temperature Setpoint. For example, if the Local
Setpoint is 40°F and the Remote Reset Tempera-
ture Range 
setpoint is programmed for 10°F, the Leav-
ing Chilled Liquid Temperature setpoint can be remotely
reset over the range of 40°F to 50°F. The Control Cen-
ter must be configured appropriately to accept the de-
sired signal type as follows:

• The appropriate Remote Mode must be selected:

Analog Remote Mode must be selected when
using a voltage or current signal input. Digital Re-
mote Mode 
must be selected when using a PWM
input.

• If Analog Remote Mode is selected, the Remote

Analog Input Range setpoint must be set to
“0-10VDC” or “2-10VDC” as detailed below, re-
gardless of whether the signal is a voltage or cur-
rent signal type.

• Microboard Program Jumper JP24 must be posi-

tioned appropriately per the input signal type as de-
tailed below. It is recommended a qualified Service
Technician position this jumper.

Important! The signal type used for
Remote Leaving Chilled Liquid Tem-
perature setpoint reset and the signal
type used for Remote Current Limit
setpoint reset must be the same. For
example, if a 0-10VDC signal is be-
ing used for Remote Current Limit
Setpoint, then a 0-10VDC signal must
be used for Leaving Chilled Liquid
Temperature reset.

Summary of Contents for MILLENNIUM YK

Page 1: ...s provisions for remote control inputs and provisions for remote setpoint reset of leaving chilled liquid tempera ture and current limit for EMS interfacing See Note 7 Five sets of unit status contact...

Page 2: ...ll load amperes for 1 to 255 minutes following each compressor start For more details refer to OptiView Control Center Instructions Form 160 54 O1 6 Controlling the maximum allowable compressor motor...

Page 3: ...U L or C S A Approved Units Only 8 Fig 14A Electro Mechanical Starter Manual Reset Overloads P Compressors Only 2300 to 4160 Volts U L or C S A Approved Units Only 8 Fig 15 Remote Current Limit Setpo...

Page 4: ...ion so they will allow the unit to start 4 The OptiView Control Center COMPRESSOR switch is in the RUN l position 5 The 30 minute anti recycle timer has timed out A closure of the Remote Mode Ready to...

Page 5: ...f Range FIG 5 ANTICIPATORY ALARM CONTACTS LD04604 FIG 6 REMOTE START AND STOP CONTACTS FROM ENERGY MANAGEMENT SYSTEM When the OptiView Control Center is in the Digital Analog or ISN remote operating m...

Page 6: ...lowing messages CYCLING SHUTDOWN AUTO RESTART and SYSTEM CYCLING CONTACTS OPEN The OptiView Control Center con tains a seven day time clock to select daily schedule Start Stop times Sun day through Sa...

Page 7: ...TWO UNIT SEQUENCE CONTROL Provides that cycling thermostat RWT will automati cally cycle either 1 or 2 unit Timer 3TR is an addi tional feature which prevents simultaneous starting of lead and lag un...

Page 8: ...LE UNITS TWO PARALLEL OPERATION SINGLE CHILLED WATER PUMP For this piping arrangement each chiller s water sensor is located in its own leaving water nozzle This produces a constant mixed chilled wate...

Page 9: ...lts and Microboard Program Jumper JP23 has been removed Calculate the setpoint for various inputs as follows SETPOINT 100 VDC X 7 For example if the input is 5VDC the setpoint would be set to 65 as fo...

Page 10: ...dulation input is in the form of a 1 to 11 second relay contact closure that applies 115VAC to the I O Board TB4 20 for 1 to 11 seconds As shown in Fig 17 connect dry closure relay contacts between I...

Page 11: ...SET F VDC 2 REMOTE RESET TEMP RANGE 8 SETPOINT F LOCAL SETPOINT OFFSET For example if the input is 5VDC and the Remote Re set Temp Range setpoint is programmed for 40 F the setpoint would be set to 43...

Page 12: ...e set to 44 F as follows SIGNAL COMMON 5 4 J22 FIG 19 REMOTE LEAVING CHILLED LIQUID TEMP SETPOINT WITH 0 20MA OR 4 20MA SIGNAL LD04501 OFFSET F 8 10 20 80 20 4 F SETPOINT F 40 4 44 F 4 20mA As shown i...

Page 13: ...J11 1 JP27 1 SHLD GND _ 5V J11 SHLD GND _ 5V J11 SHLD GND _ 5V J12 SHLD GND _ 5V MICROBOARD 031 01730 1 PC 104 2 1 J17 J16 FIG 21 MICROBOARD DIP SWITCH FOR AUTO MANUAL RESTART AFTER POWER FAILURE LD04...

Page 14: ...er square inch psia For Metric Units temperature is in degrees Celsius C and pressure in KiloPascals kPa _ _ On Solid State Starter units only when the Current Imbalance option is selected via the Sol...

Page 15: ...un Light The control relay scheme shown in Fig 23 can also be applied for a remote Run Light AND a Remote Shutdown Indicator when an EMS is not used When Evaporator Water is flowing the flow switch co...

Page 16: ...e accomplished in sev eral ways Two flow switches a flow switch and a relay or separate contacts on the same flow switch 14 15 Do not apply voltage on field wiring terminal blocks TB4 and TB6 in YORK...

Reviews: