background image

YORK INTERNATIONAL

12

OFFSET (°F)

= (5 – 2)(10)

   8

= (3)(10)
      8

= 30
    8

      SETPOINT (°F) = 40 + 3.8

= 43.8°F

0-20mA - As shown in Fig. 19, connect input to
Microboard J22-4 (signal) and J22-5 (Gnd). A 0mA sig-
nal produces a 0°F offset. A 20mA signal produces the
maximum allowed offset (10 or 20°F above the local
setpoint value). The setpoint is changed linearly between
these extremes as the input varies over the range of 0-
20mA. This input will only be accepted when “Ana-
log” Remote Mode
 is selected, the “Remote Ana-
log Input Range” 
setpoint is set for “0-10VDC” and
Microboard Program Jumper J24 has been placed on
pins 1 and 2. Calculate the setpoint for various inputs as
follows:

OFFSET (°F) = (MA)(REMOTE RESET TEMP RANGE)

                    20

SETPOINT(°F) = LOCAL SE OFFSET

For example, if the input is 8mA, the Remote Reset
Temp Range Setpoint is programmed for 10°F and the
Local Leaving Chilled Liquid Temperature setpoint is
programmed for 40°F, the setpoint would be set to 44°F
as follows:

SIGNAL

COMMON

5

4

+

J22

FIG. 19 – REMOTE LEAVING CHILLED LIQUID TEMP.

SETPOINT WITH 0-20MA OR 4-20MA
SIGNAL

LD04501

OFFSET (°F)

= (8)(10)

20

= (80)
    20

= 4°F

      SETPOINT (°F) = 40 + 4

= 44°F

4-20mA - As shown in Fig. 19, connect input to Micro
Board J22-4 (signal) and J22-5 (Gnd.). A 4mA signal
produces a 0°F offset. A 20mA signal produces the
maximum allowed offset (10 or 20°F above the Local
setpoint Value). The setpoint is changed linearly between
these extremes as the input varies over the range of 0-
20mA. This input will only be accepted when “Ana-
log”
  Remote Mode is selected, the “Remote Ana-
log Input Range”
 setpoint is set for “2-10VDC” and
Microboard Program Jumper JP24 has been placed on
pins 1 and 2. Calculate the setpoint for various inputs as
follows:

OFFSET(°F) = 

(MA – 4)(REMOTE TEMP. RESET RANGE)

                        16

SETPOINT(°F) = LOCAL SE OFFSET

For example, if input is 8mA, and the Remote Reset
Temp. Range setpoint is programmed for 10°F and the
Local Leaving Chilled Liquid Temperature setpoint is
programmed for 40°F, the setpoint would be set to 42.5°F
as follows:

OFFSET (°F)

= (8 – 4)(10)

16

= (4)(10)
      16

= 40
   16

= 2.5°F

      SETPOINT (°F) = 40 + 2.5

= 42.5°F

Summary of Contents for MILLENNIUM YK

Page 1: ...s provisions for remote control inputs and provisions for remote setpoint reset of leaving chilled liquid tempera ture and current limit for EMS interfacing See Note 7 Five sets of unit status contact...

Page 2: ...ll load amperes for 1 to 255 minutes following each compressor start For more details refer to OptiView Control Center Instructions Form 160 54 O1 6 Controlling the maximum allowable compressor motor...

Page 3: ...U L or C S A Approved Units Only 8 Fig 14A Electro Mechanical Starter Manual Reset Overloads P Compressors Only 2300 to 4160 Volts U L or C S A Approved Units Only 8 Fig 15 Remote Current Limit Setpo...

Page 4: ...ion so they will allow the unit to start 4 The OptiView Control Center COMPRESSOR switch is in the RUN l position 5 The 30 minute anti recycle timer has timed out A closure of the Remote Mode Ready to...

Page 5: ...f Range FIG 5 ANTICIPATORY ALARM CONTACTS LD04604 FIG 6 REMOTE START AND STOP CONTACTS FROM ENERGY MANAGEMENT SYSTEM When the OptiView Control Center is in the Digital Analog or ISN remote operating m...

Page 6: ...lowing messages CYCLING SHUTDOWN AUTO RESTART and SYSTEM CYCLING CONTACTS OPEN The OptiView Control Center con tains a seven day time clock to select daily schedule Start Stop times Sun day through Sa...

Page 7: ...TWO UNIT SEQUENCE CONTROL Provides that cycling thermostat RWT will automati cally cycle either 1 or 2 unit Timer 3TR is an addi tional feature which prevents simultaneous starting of lead and lag un...

Page 8: ...LE UNITS TWO PARALLEL OPERATION SINGLE CHILLED WATER PUMP For this piping arrangement each chiller s water sensor is located in its own leaving water nozzle This produces a constant mixed chilled wate...

Page 9: ...lts and Microboard Program Jumper JP23 has been removed Calculate the setpoint for various inputs as follows SETPOINT 100 VDC X 7 For example if the input is 5VDC the setpoint would be set to 65 as fo...

Page 10: ...dulation input is in the form of a 1 to 11 second relay contact closure that applies 115VAC to the I O Board TB4 20 for 1 to 11 seconds As shown in Fig 17 connect dry closure relay contacts between I...

Page 11: ...SET F VDC 2 REMOTE RESET TEMP RANGE 8 SETPOINT F LOCAL SETPOINT OFFSET For example if the input is 5VDC and the Remote Re set Temp Range setpoint is programmed for 40 F the setpoint would be set to 43...

Page 12: ...e set to 44 F as follows SIGNAL COMMON 5 4 J22 FIG 19 REMOTE LEAVING CHILLED LIQUID TEMP SETPOINT WITH 0 20MA OR 4 20MA SIGNAL LD04501 OFFSET F 8 10 20 80 20 4 F SETPOINT F 40 4 44 F 4 20mA As shown i...

Page 13: ...J11 1 JP27 1 SHLD GND _ 5V J11 SHLD GND _ 5V J11 SHLD GND _ 5V J12 SHLD GND _ 5V MICROBOARD 031 01730 1 PC 104 2 1 J17 J16 FIG 21 MICROBOARD DIP SWITCH FOR AUTO MANUAL RESTART AFTER POWER FAILURE LD04...

Page 14: ...er square inch psia For Metric Units temperature is in degrees Celsius C and pressure in KiloPascals kPa _ _ On Solid State Starter units only when the Current Imbalance option is selected via the Sol...

Page 15: ...un Light The control relay scheme shown in Fig 23 can also be applied for a remote Run Light AND a Remote Shutdown Indicator when an EMS is not used When Evaporator Water is flowing the flow switch co...

Page 16: ...e accomplished in sev eral ways Two flow switches a flow switch and a relay or separate contacts on the same flow switch 14 15 Do not apply voltage on field wiring terminal blocks TB4 and TB6 in YORK...

Reviews: