FIG. 23 – RUN CONTACTS/REMOTE RUN LIGHT AND
SHUTDOWN INDICATOR PLUS EMS

When run contacts are required for a Remote Run Light
and/or Shutdown Indicator AND Energy Management
System (EMS), connect (by others) as shown in the
diagram. The EMS, control relay, shutdown and run
lights are furnished by others. When the N.O. contacts
close, between terminals

35

and

36

on field wiring ter-

minal block TB2 in the OptiView Control Center, this
indicates that the unit is operating; the remote Run Light
will be energized. The unit run contacts open when the
unit is shutdown (safety or cycling) and the remote
indicator will then be energized. For run contacts to EMS
only refer to Fig. 4. When terminals 

35

 and 

36

are not

used for an EMS, they may be connected to a remote
Run Light. The control relay scheme shown in Fig. 23
can also be applied for a remote Run Light AND a
Remote Shutdown Indicator, when an EMS is not used.

When Evaporator Water is flowing, the flow switch con-
tact will close. If the flow switch opens for 2 seconds,
the unit shuts down and displays “CYCLING SHUT-
DOWN – AUTO RESTART” and “LEAVING
CHILLED LIQUID – FLOW SWITCH OPEN”. The
chiller will automatically restart when the switch again
closes. The flow switch status is checked 25 seconds
into “START SEQUENCE INITIATED” and continu-
ously thereafter.

FIG. 25 – EVAPORATOR WATER PUMP INTERLOCK

OR FLOW SWITCH

LD04400

LD06838

FIG. 24 – AUXILIARY SAFETY SHUTDOWN INPUT

The closure of a Momentary or Maintained N.O. Switch
or Relay Contacts will cause the unit to shut down and
display: “SAFETY SHUTDOWN – MANUAL RE-
START” and “AUXILIARY SAFETY – CONTACTS
CLOSED”. The unit will not restart until the contacts
open and the keypad COMPRESSOR switch is moved
to the “STOP-RESET” position (“O”) and then to the
“START”  (“      ”)position.

_

Summary of Contents for MILLENNIUM YK

Page 1: ...s provisions for remote control inputs and provisions for remote setpoint reset of leaving chilled liquid tempera ture and current limit for EMS interfacing See Note 7 Five sets of unit status contact...

Page 2: ...ll load amperes for 1 to 255 minutes following each compressor start For more details refer to OptiView Control Center Instructions Form 160 54 O1 6 Controlling the maximum allowable compressor motor...

Page 3: ...U L or C S A Approved Units Only 8 Fig 14A Electro Mechanical Starter Manual Reset Overloads P Compressors Only 2300 to 4160 Volts U L or C S A Approved Units Only 8 Fig 15 Remote Current Limit Setpo...

Page 4: ...ion so they will allow the unit to start 4 The OptiView Control Center COMPRESSOR switch is in the RUN l position 5 The 30 minute anti recycle timer has timed out A closure of the Remote Mode Ready to...

Page 5: ...f Range FIG 5 ANTICIPATORY ALARM CONTACTS LD04604 FIG 6 REMOTE START AND STOP CONTACTS FROM ENERGY MANAGEMENT SYSTEM When the OptiView Control Center is in the Digital Analog or ISN remote operating m...

Page 6: ...lowing messages CYCLING SHUTDOWN AUTO RESTART and SYSTEM CYCLING CONTACTS OPEN The OptiView Control Center con tains a seven day time clock to select daily schedule Start Stop times Sun day through Sa...

Page 7: ...TWO UNIT SEQUENCE CONTROL Provides that cycling thermostat RWT will automati cally cycle either 1 or 2 unit Timer 3TR is an addi tional feature which prevents simultaneous starting of lead and lag un...

Page 8: ...LE UNITS TWO PARALLEL OPERATION SINGLE CHILLED WATER PUMP For this piping arrangement each chiller s water sensor is located in its own leaving water nozzle This produces a constant mixed chilled wate...

Page 9: ...lts and Microboard Program Jumper JP23 has been removed Calculate the setpoint for various inputs as follows SETPOINT 100 VDC X 7 For example if the input is 5VDC the setpoint would be set to 65 as fo...

Page 10: ...dulation input is in the form of a 1 to 11 second relay contact closure that applies 115VAC to the I O Board TB4 20 for 1 to 11 seconds As shown in Fig 17 connect dry closure relay contacts between I...

Page 11: ...SET F VDC 2 REMOTE RESET TEMP RANGE 8 SETPOINT F LOCAL SETPOINT OFFSET For example if the input is 5VDC and the Remote Re set Temp Range setpoint is programmed for 40 F the setpoint would be set to 43...

Page 12: ...e set to 44 F as follows SIGNAL COMMON 5 4 J22 FIG 19 REMOTE LEAVING CHILLED LIQUID TEMP SETPOINT WITH 0 20MA OR 4 20MA SIGNAL LD04501 OFFSET F 8 10 20 80 20 4 F SETPOINT F 40 4 44 F 4 20mA As shown i...

Page 13: ...J11 1 JP27 1 SHLD GND _ 5V J11 SHLD GND _ 5V J11 SHLD GND _ 5V J12 SHLD GND _ 5V MICROBOARD 031 01730 1 PC 104 2 1 J17 J16 FIG 21 MICROBOARD DIP SWITCH FOR AUTO MANUAL RESTART AFTER POWER FAILURE LD04...

Page 14: ...er square inch psia For Metric Units temperature is in degrees Celsius C and pressure in KiloPascals kPa _ _ On Solid State Starter units only when the Current Imbalance option is selected via the Sol...

Page 15: ...un Light The control relay scheme shown in Fig 23 can also be applied for a remote Run Light AND a Remote Shutdown Indicator when an EMS is not used When Evaporator Water is flowing the flow switch co...

Page 16: ...e accomplished in sev eral ways Two flow switches a flow switch and a relay or separate contacts on the same flow switch 14 15 Do not apply voltage on field wiring terminal blocks TB4 and TB6 in YORK...

Reviews: