035-19643-001 Rev. B (0204)

Unitary Products Group

9

3 Flash (Part Two; 2nd Stage)

Reason:

2LP did not close within 30 seconds of a call for 2nd
Stage heat.

Effect:

After 30 seconds the Control will enter a ‘Soft Lockout’
period, and the Inducer will be de-energized. After 3
minutes the Control will try again. The procedure will be
repeated if 2LP does not close.

Causes:

Faulty Inducer.
Restricted vent system.
Vent system that exceeds specifications.
Blocked or restricted condensate drain.
Broken or leaking pressure switch tubing.
Faulty 2LP.

4 Flash

Reason:

Open limit circuit. The limit circuit includes the Primary
Limit, Auxiliary Limit, and Rollout Switches.

Effect:

Blower and Inducer operate at Low Heat speed. If the
open switch resets, the furnace will resume normal
operation.

Causes:

Dirty Filter
Improperly sized duct system.
Incorrect blower speed selection
Incorrect firing rate
Faulty blower motor
Faulty Control

6 Flash

Reason:

1LP has opened five times during one call for heat.

Effect:

Control enters ‘Soft Lockout’. It will automatically reset
and try again after 1 hour.

Causes:

Restricted vent system
Vent system that exceeds specifications
High wind

7 Flash

Reason:

Flame rectification could not be established

- Flame rectification must be maintained for 7 seconds
to be recognized by the control.

Effect:

Control tries 3 times then goes into ‘Soft Lockout’.

- There is a 1-minute delay after a failed ignition
attempt
- 7 seconds is added to the igniter warm-up time after
a failed ignition attempt.

Causes:

Faulty hot surface igniter
Contaminated flame rod.
Poor ground connection to furnace.
Reversed polarity to furnace
Moisture on flame sensing circuit
Low gas pressure
Faulty gas valve

8 Flash

Reason:

Flame rectification has been lost 5 times, during 1 call
for heat, after it was recognized by the control.

- Flame rectification is recognized after 7 seconds of
burner operation.

Effect:

Control goes into ‘Soft Lockout’ after the 5th attempt to
maintain combustion.

Causes:

Restricted vent system.
Blocked or restricted condensate drain.
Foreign objects in the inducer housing.

LED on constantly

Reason:

The control discovered an internal fault during its self-
check procedure.

Effect:

All operations cease.

Causes:

Voltage spikes.
Supply voltage is too high or low.
- Reset the control by breaking line voltage for 30
seconds.
Control failure.

Never bypass pressure switch to allow furnace opera-
tion. To do so will allow furnace to operate under poten-
tially hazardous conditions.

Do not try to repair controls. Replace defective controls
with UPG Source 1 Parts.

Never adjust pressure switch to allow furnace operation.

IGNITION CONTROL (P/N 031-01909-000)

Normal flame sense current is approximately

2.4 microamps DC (µa)

Low flame signal control lockout point is

0.15 microamps DC (µa)

Summary of Contents for P XD-V Series

Page 1: ...e fur nace can result in fire or explosion A qualified service agency should be contacted to inspect the furnace and replace all gas controls control system parts electrical parts that have been wet o...

Page 2: ...ng making sure the physical support is sound without sagging cracks or gaps Examine the furnace base making sure it is physically sound without cracks gaps or sagging and has a good seal 5 Examine the...

Page 3: ...e control system and any gas control which has been under water Operating Instructions 1 STOP Read the safety information above 2 Set the thermostat to the lowest setting 3 Turn off all electric power...

Page 4: ...lter after cleaning you must do the following 1 Slide filter into place 2 Snap the door on or place the door in position and tighten the retaining screws if provided 3 Make sure the door is secure to...

Page 5: ...iliary Limit and Roll out Switches for closed contacts The Control checks that the Low Fire Pressure Switch 1LP is open The Inducer Motor is energized on high speed closing the con tacts of 1LP The Co...

Page 6: ...provide the highest CFM Pin Position B and C are the medium and medium low CFM settings Pin Position D will provide the lowest CFM Refer to Table 16 in the installation manual for the proper HEAT Tap...

Page 7: ...s were not previously removed also remove and discard these two screws located on each front corner of the blower assembly 3 Loosen the blower wheel set screw that secures the blower wheel to the blow...

Page 8: ...the conden sate drain pan Remove the vent blower housing blower and the condensate pan The turbulators can then be gently removed from the secondary heat exchanger 3 Using a stiff wire brush remove t...

Page 9: ...by the control Effect Control tries 3 times then goes into Soft Lockout There is a 1 minute delay after a failed ignition attempt 7 seconds is added to the igniter warm up time after a failed ignitio...

Page 10: ...W INDUCER LOW STAGE PRESSURE SWITCH HSI 1ST STAGE MAIN VALVE FLAME SENSE LOW CIRCULATOR HEAT SPEED 1ST STAGE LOW PRESSURE SWITCH CLOSE RECOGNITION HSI WARM UP 17 SEC IGNITION ACTIVATION PERIOD 4 SEC T...

Page 11: ...itary Products Group 11 SECTION III REPLACEMENT PARTS LIST 15 16 1 17 3 7A 13 14 5 8 12 9 2 7 6 6 11 6A 24 27 26 35 38 34 32 33 25 36 22 37 21 20 28 29 23 31 30 18 19 51 63 43 53 59 57 58 55 39 41 52...

Page 12: ...R BURNER BOX 31 COVER HEAT EXCHANGER 32 PANEL FRONT Blower 33 PANEL FRONT Burner 34 PANEL TOP 35 SUPPORT BURNER 36 WRAPPER CABINET 37 PANEL VESTIBULE Lower 38 PLUG WINDOW CLEAR 875 MISCELLANEOUS 39 CO...

Page 13: ...SWITCH KIT DOES NOT INCLUDE ORIFICES FOR APPLICATION INFORMATION SEE FORM 035 14460 000 CONDENSATE NEUTRALIZER KIT ALL MODELS REPLACEMENT PART CONTACT INFORMATION This is a generic parts list To requ...

Page 14: ...035 19643 001 Rev B 0204 14 Unitary Products Group SECTION IV WIRING DIAGRAM FIGURE 10 Wiring Diagram...

Page 15: ...035 19643 001 Rev B 0204 Unitary Products Group 15 NOTES...

Page 16: ...lies only to products installed in the United States and Canada EXCLUSIONS This warranty does not cover any 1 Shipping labor or material charges 2 Damages resulting from transportation installation or...

Reviews: