background image

035-19650-001 Rev. C (0404)

6

Unitary Products Group

6.

1st and 2nd Stage satisfied simultaneously

• Both stages of the Gas Valve are de-energized.
• Flame Rectification is lost.
• The Inducer and Hum relays are de-energized after a 15-second

post purge.

• 30 seconds later the Control shifts the Blower from Heat High to

Heat Low.

• After the Blower-Off Delay Circuit is satisfied, the Blower and

EAC are de-energized.

7.

Manual Fan Operation

• With the thermostat in the Fan On position, a circuit is completed

between R and G of the Control.

• The Heat Low and EAC relays are energized by the Control.

8.

Call for Cooling

• The thermostat closes two circuits R to Y and R to G. Since the

Outdoor Unit is connected to Y and C at the Control, it is ener-
gized.

• The Cool and EAC relays are energized by the Control.
• A Blower-Off Delay Timing Circuit is energized by the call on Y.

9.

Cooling call satisfied

• The thermostat opens the R to Y and R to G circuits.
• The Outdoor Unit is de-energized.
• The 60-second, Blower-Off Delay, timing circuit is initiated.
• After 60 seconds, the Cool and EAC relays are de-energized.

Heating Indoor Fan Off Delay

Changing the dipswitches on the Integrated Control can change the
indoor fan “OFF” time delay. The dipswitches are located above the
thermostat terminals. Refer to Figure 8 for the dipswitch settings to
obtain the desired fan OFF delay. The blower off delay must be long
enough to adequately cool the furnace, but not so long that cold air is
blown into the living space.

The blower on delay is fixed at 30 seconds and cannot be adjusted.

The continuous fan speed dipswitch (switch # 3 on the Integrated Con-
trol) does not function on variable speed models. Dipswitch # 3 should
be left in the off position.

Continuous Blower:

There are two modes of continuous blower operation. 

Mode One:

 The blower is controlled directly through the blower

motor. In the first mode, when the thermostat fan-switch is set to
the ON position a circuit is completed between terminals “R” and
“G” of the thermostat. The continuous fan speed will be 63% of
the high cool speed. If more air is desirable the green wire
labeled (G Cool Speed) may be connected to the “G” terminal of
the ignition control to achieve HIGH COOL speed (DIP switch
number 3 on the ignition control must be in the OFF position).

Mode Two:

 The blower is controlled through the ignition control.

This configuration is used with multi-speed direct drive PSC
motors. 

Do not use this configuration with a variable speed

motor.

 Refer to Heating Indoor Fan Off Delay for Fan ON / OFF

Delays.

The air cleaner and the blower motor are energized through the ignition
control or directly through the motor.

DIRECT DRIVE BLOWER MOTOR

A failed PSC motor should always be replaced with a PSC motor suit-
able for the furnace model being serviced. Follow the procedure below
to replace the motor.

Removal of the Variable Speed Blower Motor Assembly:

The procedure for removing the variable speed blower assembly:

1.

Disconnect the electrical supply to the furnace and remove the
access doors.

2.

Remove blower assembly mounting screws and slide the blower
assembly out of the slots in the deck. If the two shipping screws
were not previously removed, also remove and discard these two
screws located on each front corner of the blower assembly.

3.

Loosen the blower wheel set screw that secures the blower wheel
to the blower motor shaft.

4.

Remove the motor mount bolts.

5.

Slide the variable speed motor out of the blower housing.

Reassembly of the Variable Speed Blower Motor Assembly:

1.

Slide the new variable speed motor in to the blower housing. Make
sure you line up the flat side on the motor shaft with the setscrew
on the hub in the center of the blower wheel. 

2.

Install the motor mount bolts in to the fan housing.

3.

Center the indoor fan wheel in the fan housing and tighten the
blower wheel set screw on the flat side the blower motor shaft.

4.

Reinstall blower assembly mounting screws and slide the blower
assembly back in the slots in the deck. Do not reinstall the two
shipping screws were removed.

5.

Install the access doors.

6.

Restore power to the furnace and verify operation.

INSTALLATION OF PSC MOTOR:

The motor speed tap wires are connected to the 1/4" quick connect ter-
minal on the Integrated Control using the black jumper wire that is
secured to the wire harness inside the burner compartment and is
marked “PSC Motor”. Follow the instructions below to properly install
the PSC motor.

1.

Install the PSC direct drive motor into motor mount.

2.

Slide motor in motor mount insuring there is no interference
between moving and stationary parts. Position wire leads down-
ward. Tighten motor mount band screw to 30 in. lbs.

3.

Center the blower wheel in the blower housing and align the shaft
flat with the blower wheel set screw. Tighten setscrew to 30 in. lbs.

4.

Replace blower assembly and fasten with 5 screws

5.

Strap motor capacitor to electric panel. Refer to Table 2 for proper
capacitor selection.

6.

Fasten electric panel to blower housing.

7.

Remove red wire from circuit input terminal. Plug jumper wire
(attach to motor power harness) on 120-volt line terminal on igni-
tion control and jumper to circuit Input. Connect brown door switch
wire to jumper.

8.

Connect white main harness lead to Line neutral.

9.

Connect motor leads to cool, heat lo and heat high per electrical
wire diagram table in the Installation manual.

10. Connect brown capacitor leads from motor to capacitor and cover

terminals with boot supplied.

11.

The motor ground (green) wire is secured to the right front of the
blower mounting plate with a screw.

12. Restore power to the furnace and verify operation.

 FIGURE 7: 

White Rodgers Intergrated Control

INDOOR FAN OFF
DELAY DIP SWITCHES

Summary of Contents for P XU Series

Page 1: ...r explosion A qualified service agency should be contacted to inspect the furnace and replace all gas controls control system parts electrical parts that have been wet or the furnace if deemed necessa...

Page 2: ...making sure the physical support is sound without sagging cracks or gaps Examine the furnace base making sure it is physically sound without cracks gaps or sagging and has a good seal 5 Examine the fu...

Page 3: ...Wait five 5 minutes to clear out any gas If you then smell gas STOP Follow B in the safety information above If you don t smell gas go to next step 7 Move gas control switch to the ON position Do not...

Page 4: ...ilter size from Table 1 Removing Filters Internally Mounted Air Filters Most upflow furnaces have their filters located on the side or bottom of the furnace in a filter wire retainer located inside th...

Page 5: ...iliary Limit and Roll out Switches for closed contacts The Control checks that the Low Fire Pressure Switch 1LP is open The Inducer Motor is energized on high speed closing the con tacts of 1LP The Co...

Page 6: ...the furnace model being serviced Follow the procedure below to replace the motor Removal of the Variable Speed Blower Motor Assembly The procedure for removing the variable speed blower assembly 1 Dis...

Page 7: ...l power and gas supply to the furnace 13 Check furnace operation Cleaning the Secondary Heat Exchanger 1 Follow steps 1 8 under cleaning the Heat Exchanger 2 Remove the vent piping from the vent blowe...

Page 8: ...Dirty Filter Improperly sized duct system Incorrect blower speed selection Incorrect firing rate Faulty blower motor Faulty Control 6 Flash Reason 1LP has opened five times during one call for heat Ef...

Page 9: ...W INDUCER LOW STAGE PRESSURE SWITCH HSI 1ST STAGE MAIN VALVE FLAME SENSE LOW CIRCULATOR HEAT SPEED 1ST STAGE LOW PRESSURE SWITCH CLOSE RECOGNITION HSI WARM UP 17 SEC IGNITION ACTIVATION PERIOD 4 SEC T...

Page 10: ...E CIR HUM EAC XFMR LINE PARK PARK HEAT COOL 1 4 2 6 10 12 14 7 8 9 13 3 5 15 17 16 11 C G R W Y HUM EAC XFMR LINE CIR HUM EAC XFMR LINE PARK PARK HEAT COOL 19 24 25 31 26 32 33 34 50 21 22 23 27 45 28...

Page 11: ...CHANNEL TOE PLATE 32 COVER HEAT EXCHANGER 33 PANEL FRONT Blower 34 PANEL FRONT Burner PANEL FRONT Burner 35 PANEL TOP 36 SUPPORT BURNER 37 WRAPPER CABINET Insulated WRAPPER CABINET Insulated 38 PANEL...

Page 12: ...NAL BOTTOM FILTER RACK 17 1 2 CABINETS 21 CABINETS 24 1 2 CABINETS CONDENSATE NEUTRALIZER KIT ALL MODELS REPLACEMENT PART CONTACT INFORMATION This is a generic parts list To request a complete parts l...

Page 13: ...035 19650 001 Rev C 0404 Unitary Products Group 13 SECTION IV WIRING DIAGRAM FIGURE 9 Wiring Diagram...

Page 14: ...035 19650 001 Rev C 0404 14 Unitary Products Group NOTES...

Page 15: ...035 19650 001 Rev C 0404 Unitary Products Group 15...

Page 16: ...plies only to products installed in the United States and Canada EXCLUSIONS This warranty does not cover any 1 Shipping labor or material charges 2 Damages resulting from transportation installation o...

Reviews: