background image

035-19650-001 Rev. C (0404)

Unitary Products Group

7

Hot Surface Ignition System

FURNACE CLEANING SECTION

NOTE: 

The cleaning operations listed below must be performed only by

a qualified service agency.

Burner Removal/Cleaning

The main burners should be checked periodically for dirt accumulation.
If cleaning is required, follow this procedure:

1.

Turn off the electrical power to the unit.

2.

Turn off the gas supply at the external manual shut-off valve and
loosen the ground union joint.

3.

Remove the burner door and remove the burner box cover.

4.

Disconnect wires from flame sensor, rollout switch and HSI igniter.
Remove igniter carefully, as it is easily broken.

5.

Remove the screws that hold the burner box assembly to the vest
panel and remove the assembly.

6.

Remove burners from the burner assembly.

7.

Burners may be cleaned by rinsing in hot water.

8.

Reassemble the burners in the reverse order.

Cleaning the Heat Exchanger

1.

Turn off the electrical power to the unit.

2.

Turn off the gas supply at the external manual shut-off valve and
loosen the ground union joint.

3.

Remove the upper access panel and remove the burner box
cover.

4.

Disconnect wires from flame sensor, rollout switch and HSI igniter.
Remove igniter carefully, as it is easily broken.

5.

Remove the screws that hold the burner box assembly to the vest
panel and remove the assembly.

6.

Remove burners from the burner assembly.

7.

Remove the upper cover plate at the top of the furnace. Remove
the internal baffle.

8.

The upper portion of the heat exchanger is now exposed.

9.

With a long flexible wire brush, clean inside each tube at both the
top and bottom. The brush must pass around the rear heat
exchanger tubes and then vacuum loose the scale and dirt from
each tube.

10. Clean - vacuum all burners.

11.

Replace all components in reverse order. Reconnect all wiring.

12. Restore electrical power and gas supply to the furnace.

13. Check furnace operation.

Cleaning the Secondary Heat Exchanger

1.

Follow steps 1 - 8 under cleaning the Heat Exchanger.

2.

Remove the vent piping from the vent blower housing. Disconnect
the drain lines from the vent blower housing and from the conden-
sate drain pan. Remove the vent blower housing blower and the
condensate pan. The turbulators can then be gently removed from
the secondary heat exchanger.

3.

Using a stiff wire brush, remove the loose scale or soot from each
tube.

4.

Vacuum the secondary heat exchanger.

5.

Finish the cleaning procedure by following steps 11 thru 13 under
cleaning the Heat Exchanger.

TROUBLESHOOTING

The following visual checks should be made before troubleshooting:

1.

Check to see that the power to the furnace and the ignition control
module is ON.

2.

The manual shut-off valves in the gas line to the furnace must be
open.

3.

Make sure all wiring connections are secure.

4.

Review the sequence of operation. Start the system by setting the
thermostat above the room temperature. Observe the system’s
response. Then use the troubleshooting section in this manual to
check the system’s operation.

TABLE 2: 

Replacement PSC Motor / Capacitor Information

High Fire Inputs

Airflow

Cabinet Size

Motor 

Part Number

Motor 

Horsepower

Capacitor 

Part Number

Capacitor 

Rating 

BTU/H (kW)

CFM (m³)

60,000 (17.6)

1,200 (33.98)

B

024-23271-000

1/2

024-20045-000

7.5 f

80,000 (23.4)

1,600 (45.31)

C

024-26002-000

3/4

024-20046-000

10.0 f

100,000 (29.3)

2,000 (56.63)

C

024-23288-001

1.0

024-20446-000

15.0 f

120,000 (35.1)

2,000 (56.63)

D

024-23238-001

1.0

024-20446-000

15.0 f

HOT SURFACE IGNITION SYSTEM
Do not attempt to light this furnace by hand (with a
match or any other means). There may be a potential
shock hazard from the components of the hot surface
ignition system. The furnace can only be lit automatically
by its hot surface ignition system.

Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and danger-
ous operation. Verify proper operation after servicing.

Summary of Contents for P XU Series

Page 1: ...r explosion A qualified service agency should be contacted to inspect the furnace and replace all gas controls control system parts electrical parts that have been wet or the furnace if deemed necessa...

Page 2: ...making sure the physical support is sound without sagging cracks or gaps Examine the furnace base making sure it is physically sound without cracks gaps or sagging and has a good seal 5 Examine the fu...

Page 3: ...Wait five 5 minutes to clear out any gas If you then smell gas STOP Follow B in the safety information above If you don t smell gas go to next step 7 Move gas control switch to the ON position Do not...

Page 4: ...ilter size from Table 1 Removing Filters Internally Mounted Air Filters Most upflow furnaces have their filters located on the side or bottom of the furnace in a filter wire retainer located inside th...

Page 5: ...iliary Limit and Roll out Switches for closed contacts The Control checks that the Low Fire Pressure Switch 1LP is open The Inducer Motor is energized on high speed closing the con tacts of 1LP The Co...

Page 6: ...the furnace model being serviced Follow the procedure below to replace the motor Removal of the Variable Speed Blower Motor Assembly The procedure for removing the variable speed blower assembly 1 Dis...

Page 7: ...l power and gas supply to the furnace 13 Check furnace operation Cleaning the Secondary Heat Exchanger 1 Follow steps 1 8 under cleaning the Heat Exchanger 2 Remove the vent piping from the vent blowe...

Page 8: ...Dirty Filter Improperly sized duct system Incorrect blower speed selection Incorrect firing rate Faulty blower motor Faulty Control 6 Flash Reason 1LP has opened five times during one call for heat Ef...

Page 9: ...W INDUCER LOW STAGE PRESSURE SWITCH HSI 1ST STAGE MAIN VALVE FLAME SENSE LOW CIRCULATOR HEAT SPEED 1ST STAGE LOW PRESSURE SWITCH CLOSE RECOGNITION HSI WARM UP 17 SEC IGNITION ACTIVATION PERIOD 4 SEC T...

Page 10: ...E CIR HUM EAC XFMR LINE PARK PARK HEAT COOL 1 4 2 6 10 12 14 7 8 9 13 3 5 15 17 16 11 C G R W Y HUM EAC XFMR LINE CIR HUM EAC XFMR LINE PARK PARK HEAT COOL 19 24 25 31 26 32 33 34 50 21 22 23 27 45 28...

Page 11: ...CHANNEL TOE PLATE 32 COVER HEAT EXCHANGER 33 PANEL FRONT Blower 34 PANEL FRONT Burner PANEL FRONT Burner 35 PANEL TOP 36 SUPPORT BURNER 37 WRAPPER CABINET Insulated WRAPPER CABINET Insulated 38 PANEL...

Page 12: ...NAL BOTTOM FILTER RACK 17 1 2 CABINETS 21 CABINETS 24 1 2 CABINETS CONDENSATE NEUTRALIZER KIT ALL MODELS REPLACEMENT PART CONTACT INFORMATION This is a generic parts list To request a complete parts l...

Page 13: ...035 19650 001 Rev C 0404 Unitary Products Group 13 SECTION IV WIRING DIAGRAM FIGURE 9 Wiring Diagram...

Page 14: ...035 19650 001 Rev C 0404 14 Unitary Products Group NOTES...

Page 15: ...035 19650 001 Rev C 0404 Unitary Products Group 15...

Page 16: ...plies only to products installed in the United States and Canada EXCLUSIONS This warranty does not cover any 1 Shipping labor or material charges 2 Damages resulting from transportation installation o...

Reviews: