background image

NOTE: To find the Btuh input, multiply the number of
cubic feet of gas consumed per hour by the BTU
content of the gas in your particular locality. Contract
your gas company for this information, as it varies
widely from city to city.

EXAMPLE: It is found by measurement that it takes 26 seconds
for the hand to turn on the 1 cubic foot dial to make a revolution
with only a 120,000 Btuh furnace running. Using this informa-
tion, locate 26 seconds in the first column of Table 3.

Read across to the column headed "1 Cubic Foot" where you
will see that 138 cubic feet of gas per hour are consumed by
the furnace at that rate. Multiply 138 by 850 (the BTU rating of
the gas obtained from the local gas company). The result is
117,300 Btuh, which is close to the 120,000 Btuh rating of the
furnace.

If the actual input is not within 

±

 2% of the furnace rating, with

allowance being made for the permissible range of the regula-
tor setting (0.3 inches W.C.), replace the orifice spuds with
spuds of the proper size.

CAUTION: Be sure to relight any gas appliances that
were turned off at the start of this input check.

ADJUSTMENT OF MANIFOLD GAS PRESSURE

1.  Turn gas off at main gas valve. Remove 1/8" plug in the main

gas valve body and install proper manometer tube adapter
fitting. Connect line from gas valve tap to manometer.

2.  Refer to Figure 7 for location of pressure regulator adjust-

ment cap and screw on main gas valve.

NOTE: The screw-off cap for the pressure regulator
must be removed entirely to gain access to the ad-
justment screw.

WARNING: The cap must be replaced in order for the
furnace to operate properly.

3.  Turn gas and electrical supplies ON. Start furnace and

observe manifold pressure on manifold.

4.  Adjust manifold pressure by adjusting gas valve regulator

screw.

If gas valve regulator is turned in, or clockwise, manifold
pressure is increased. If screw is turned out, or counterwise,
manifold pressure will decrease.

WARNING: The manifold pressure must be checked
with the screw-off cap in place on the pressure regu-
lator.

WARNING: If manifold pressure is too high, an over-
fire condition exists which could cause heat ex-
changer failure. If the manifold pressure is too low,
sooting and eventual clogging of the heat exchanger
could occur.

5.  Once the correct gas pressure to the burners has been

established, turn the gas valve knob to OFF and turn the
electrical supply switch OFF; then, remove the pressure
tap at the gas valve and re-install the plug using a com-
pound (on the threads) resistant to the action of LP gases.

6.  Turn the electrical and gas supplies back on, and, with the

burners in operation, check for gas leakage around the
plug with a soap and water solution.

WARNING: Be sure that the gas valve pressure regu-
lator cap is replaced.

ADJUSTMENT OF PRIMARY AIR

The main burners should be in operation for 15 minutes before
making the primary air adjustment. The burner flame should
not contain any yellow color. With the furnace operating at full
input, adjust the primary air of the burners as follows:

Natural Gas - All models are shipped with the air shutters
partially open.

Local variations in the gas supply may require changes in the
settings described above. To change the air shutter settings,
use the following procedure:

1.  Remove the front access door.

2.  Loosen shutter locking screw.

3.  Adjust the air shutters with power to the unit "off", and

retighten the locking screws.

4.  Observe through the observation port to see if all flames are

now blue in color. See Figure 8 for proper flame pattern. If
yellow flames are still visible, repeat steps 2 thru 4.

5.  Cycle the burners on and off a few times to verify the

burners are lighting promptly and properly.

6.  Replace the front access door.

ADJUSTMENT OF TEMPERATURE RISE

The temperature rise, or temperature difference between the
return air and the heated air from the furnace, must be within
the range shown on the furnace rating plate and within the
application limitations shown in Table 1. After the temperature
rise has been determined, the cfm can be calculated.

After about 20 minutes of operation, determine the furnace
temperature rise. Take readings of both the return air and the
heated air in the ducts, about six feet from the furnace where
they will not be affected by radiant heat. 

Increase the blower speed to decrease the temperature rise;
decrease the blower speed to increase the rise.

To adjust blower speed, perform the following steps:

FIGURE 7 - GAS VALVE - WHITE-RODGERS 36E97

LIGHT BLUE

OUTER CONE

CROSSOVER

FLAME

INTERGAL

CROSSOVER TUBE

MANIFOLD

BURNER

BLUE

INNER

CONES

FIGURE 8 - PROPER FLAME APPEARANCE

650.64-N4

Unitary Products Group

9

Summary of Contents for P4UCB30N12206

Page 1: ...hone in your building Extinguish any open flame Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department UPFLOW GAS FIRED FURNACE INDUCED DRAFT INSTALLATION INSTRUCTION Supersedes 650 64 N3Y 992 650 64 N4Y 195 035 11008 CAUTION THIS PRODUCT MUST BE INSTALLED IN STRICT COM PLIANCE WITH THE ENCLOS...

Page 2: ...s 4 Paper bags boxes or other paper products WARNING Never operate the furnace with the blower door removed To do so could result in serious personal injury and or equipment damage WARNING Each furnace in this series is a Category I furnace suitable for common venting with other gas fired appliances as allowed by the National Fuel Gas Code NFPA 54 ANSI Z223 1 latest edition WARNING This appliance ...

Page 3: ...to obtain proper air for combustion and ventilation in confined spaces 1 Air Source from Inside the Building Two permanent openings one within 12 inches of the top of the confined space and one within 12 inches of the bottom shall each have a free area of not less than one square inch per 1 000 Btuh of total input rating of all appliances located in the space The openings shall com municate freely...

Page 4: ...h Velocity Filter Size Weight lbs HP Size Side Bottom P4UCB30N12206 30 60 180 1 1 2 15 x 13 10 5 15 12 2 16 x 26 30 x 26 293 NOTES 1 Filters must be high velocity type 2 All applications require return air from both side inlets and or bottom TABLE 2 RATINGS PHYSICAL ELECTRICAL DATA FIGURE 1 FURNACE DIMENSIONS Model A B C D E F P4UCB30N12206 32 1 4 30 3 4 31 1 2 49 3 4 51 13 5 32 1 An adapter is su...

Page 5: ... Fuel Gas Code ANSI Z223 1 or CAN CGA B149 1 or 2 Installation Code latest editions The following steps shall be followed with each appliance connected to the venting system placed in operation while any other appliances connected to the common venting system are not in operation 1 Seal any unused openings in the common venting system 2 Inspect venting system for propersize andhorizontalpitch as r...

Page 6: ... furnace This will expose the fiter to allow removal to re install the filter simply reverse this procedure For bottom filter removal use the following procedure Remove the toe piece at the bottom of the furnace by removing the four sheet metal screws holding it in place and slide the filter out of the furnace To install the filter reverse this proce dure Side Return Locate and knock out the squar...

Page 7: ... 70 latest edition Canadian Electric Code C22 1 Part 1 latest edition and or local codes Electrical wires which are field installed shall conform with the tempera ture limitation for 63 F 35 C rise wire when installed in accord ance with instructions Specific electrical data is given on the furnace rating plate Provide a power supply separate from all other circuits Install overcurrent protection ...

Page 8: ... addi tional procedures 1 When the gas supply is initially connected to the furnace the gas piping may be full of air In order to purge this air it is recommended that the ground joint union be loosened until the odor of gas is detected When gas is detected immediately retighten the union and check for leaks Allow five minutes for any gas to dissipate before continuing with the start up procedure ...

Page 9: ...the heat exchanger could occur 5 Once the correct gas pressure to the burners has been established turn the gas valve knob to OFF and turn the electrical supply switch OFF then remove the pressure tap at the gas valve and re install the plug using a com pound on the threads resistant to the action of LP gases 6 Turn the electrical and gas supplies back on and with the burners in operation check fo...

Page 10: ...G Do not attempt to relight this furnace by hand with a match or any other means There may be a potential shock hazard from the components of the hot surface ignition system The furnace can only be lit automatically by its hot surface ignition system The following describes the sequence of operation of the furnace Refer to the schematic wiring diagrams pages 14 15 for component locations CONTINUOU...

Page 11: ...rs may be cleaned by rinsing in hot water 9 Reassemble the burners in the reverse order making sure the burner shield is tightened securely in place Cleaning the Heat Exchanger 1 Turn off the main manual gas valve external to the furnace 2 Turn off electrical power to the furnace 3 Remove the upper access door 4 Disconnect wires from HSI sensor rollout switch and HSI igniter Remove igniter careful...

Page 12: ...stem s response Then use the Trou bleshooting Table on page 16 to check the system s operation Use the table by reading the upper left hand box and then following the instructions in each box If the condition described in the box is true yes answer go down to the next box If the condition is not true no answer go to the box to the right C o ntinue checking and answering the questions in the boxes ...

Page 13: ...WIRING DIAGRAM 650 64 N4 Unitary Products Group 13 ...

Page 14: ...pen 3573 3396 3237 3074 2873 2724 2360 1922 5 Open 3032 2848 2683 2422 2283 1905 Airlfow is expressed in standard cubic feet per minute u Operation at these conditons will cause excessive furnace furnace temperature rise Operation at these conditions will cause motor overload NOTES Return air is through both sides Air filters installed Motor voltage at 230V For bottom only return reduce rating by ...

Page 15: ...venter NO NO YES Hot surface igniter begins to glow Main burner lights NOTE Before troubleshooting familiarize yourself with the startup and checkout procedures Check for 25vac on 50E47 acrosss MV terminals If no voltage replace 50E47 Check electrical connections between 50E47 gas valve If Okay replace gas valve Place jumper on between C NC pressure switch 1LP Check hoses connected to pressure swi...

Page 16: ...ry Products Group P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in U S A Copyright by York International Corporation 1995 All Rights Reserved Code SBY 650 64 N4Y 195 ...

Reviews: