background image

5132210-UIM-H-0916

10

Johnson Controls Unitary Products

6.

The furnace and its equipment shutoff valve must be disconnected
from the gas supply system during and pressure testing of that sys-
tem at test pressures in excess of 1/2 psi (3.48 kPA)

7.

The furnace must be isolated from the gas supply piping system by
closing its individual manual shut-off valve before conducting any
pressure testing of the gas supply piping system at test pressures
equal to or less than 1/2 psig (3.48 kPa).

HIGH ALITITUDE GAS CONVERSION

This furnace is constructed at the factory for natural gas-fired operation
at altitudes up to 2,000 feet above sea level. For installations located
above 2,000 feet, the gas input rate to the burners must be reduced by
4% per 1,000 feet above sea level. It may be necessary to change to
smaller orifices at high altitude. Refer to the table below for the correct
orifice size to use.

FLUE VENT AND AIR INTAKE HOOD

The flue vent hood and air intake hoods are shipped loose. These hoods
must be installed to assure proper unit operation. The hoods must be fas-
tened to the outside of the side gas control/electrical compartment with
the screws provided. See Figure 8.

 WARNING

FIRE OR EXPLOSION HAZARD
Failure to follow the safety warning exactly could result in serious
injury, death or property damage.
Never test for gas leaks with an open flame. use a commercially
available soap solution made specifically for the detection of leaks to
check all connections. A fire or explosion may result causing property
damage, personal injury or loss of life.

!

Table 9: 

High Altitude Gas Orifice Sizing

ELEVATION ABOVE SEA LEVEL (FEET)

GAS TYPE

0-2000 (FACTORY) 2001-3000 3001-4000 4001-5000 5001-6000 6001-7000 7001-8000 8001-9000 9001-10000

NATURAL GAS ORIFICE SIZES

36

37

38

38

39

40

41

41

42

42

42

43

43

43

44

44

45

46

LP GAS    ORIFICE SIZES

51

51

52

52

52

52

53

53

53

54

54

55

55

55

55

55

56

56

 WARNING

Flue hood surfaces may be hot.

!

 FIGURE 8:  

Flue Vent Outlet Air Hood

 CAUTION

The flue exhaust hood must be properly installed and within the rec-
ommended clearances. Further communications and action must be
given to the home or building owner(s) to eliminate any unauthorized
human contact around this area during the heating cycle. Flue hood
surfaces and the immediate area reach high temperatures during the
heating cycle.

AIR INTAKE HOOD

AIR INTAKE SCREEN

EXHAUST HOOD

A0284-001

!

Table 10: 

Natural Gas Application Data

Available On Models

Input (MBH)

1

High Fire

1. Heating capacity valid for elevations up to 2000 feet above sea level. For elevations above 2,000 feet, rated capacity should be reduced by 4% for each 1,000 feet 

above sea level.

Output (MBH)

High Fire

Gas Rate

2

Ft.

3

/Hr.

High Fire/Low Fire

2. Based on 1075 BTU/Ft.

3

.

Number of

Burners

Temp. Rise ºF

At Full Input

3

3. The air flow must be adequate to obtain a temperature rise within the range shown. Continuous return air temperature should not be below 55°F.

Min.

Max.

2, 2-1/2 Tons

50

41

46

2

40

70

3, 3-1/2, 4, 5 Tons

65

53

60

2

40

70

2, 2-1/2 Tons

75

61

70

3

40

70

3, 3-1/2, 4, 5 Tons

100

81

93

3

40

70

4, 5 Tons

125

101

116

4

40

70

Summary of Contents for PHG4 Series

Page 1: ...or installation Only gas piping electric power and duct connections are required at the point of installation The gas fired heaters have spark ignition The refrigerant system is fully charged with R 4...

Page 2: ...mproper installation adjustment alteration service or mainte nance can cause injury or property damage Refer to this manual For assistance or additional information consult a qualified installer servi...

Page 3: ...o a unit to meet local codes they are to be installed at the dealer s and or customer s expense Size of unit for proposed installation should be based on heat loss heat gain calculation made according...

Page 4: ...are provided for this purpose WARNING Do not attach supply and return duct work to the bottom of the unit base pan as the drain pan could be compromised WARNING Excessive exposure of this furnace to...

Page 5: ...ection Distance in Direction Distance in Top3 3 Units must be installed outdoors Over hanging structure or shrubs should not obstruct condenser air discharge outlet 36 Power Entry Right Side 36 Side O...

Page 6: ...n the return air ductwork or install a Filter Frame Kit A filter rack and high velocity filters are standard on three phase units Filters must always be used and must be kept clean When filters become...

Page 7: ...rate branch circuit fed directly from the main distribution panel and properly fused Refer to Figures 7 and 8 for typical field wiring and to the appropriate unit wiring diagram for control circuit an...

Page 8: ...51 1 4 Width 35 3 4 35 3 4 45 3 4 45 3 4 45 3 4 45 3 4 Height 47 49 49 49 53 55 Operating WT lbs 394 404 449 453 498 505 532 534 551 559 564 577 581 588 Compressors Type Scroll Scroll Scroll Scroll Sc...

Page 9: ...5 The gas supply should be a separate line and installed in accor dance with all applicable safety codes After the gas connections have been completed open the main shut off valve admitting nor mal ga...

Page 10: ...leaks to check all connections A fire or explosion may result causing property damage personal injury or loss of life Table 9 High Altitude Gas Orifice Sizing ELEVATION ABOVE SEA LEVEL FEET GAS TYPE...

Page 11: ...864 780 Medium High 4 1349 1297 1265 1224 1185 1146 1107 1063 975 High 5 1487 1462 1392 1331 1318 1281 1241 1201 1121 30050 Low 1 700 657 599 554 512 461 411 365 273 Low Medium 2 906 868 825 779 735...

Page 12: ...1858 1807 1749 1710 1667 1629 1589 1546 1460 Medium 3 2054 1998 1934 1890 1843 1801 1757 1710 1616 Medium High 4 2195 2144 2098 2049 2003 1955 1883 1868 1838 High 5 2445 2388 2306 2293 2235 2178 2129...

Page 13: ...w 1 1032 999 970 938 910 879 843 808 737 Low Medium 2 1272 1236 1204 1165 1129 1081 1037 968 829 Medium 3 1611 1574 1518 1494 1439 1405 1357 1266 1083 Medium High 4 1892 1777 1771 1701 1639 1617 1565...

Page 14: ...ings are selected If the heat pump and gas heating sections are run at the same time HI LIMIT trips may occur A Y call without an O call from the indoor thermostat is primary heat pump heat A W call f...

Page 15: ...frost cycle is initiated A temperature inhibit feature prohibits defrost if the coil temperature is above 40 F A forced defrost feature puts the system into a defrost period every 6 hours and 4 minute...

Page 16: ...g 8 on the LED Post Purge The control board runs the induced draft motor for a 15 second post purge period and then de energizes the inducer If a call for heat occurs during post purge the control fin...

Page 17: ...hich automatically lights the burners 5 Remove the access panel 6 Turn the gas valve switch to the OFF position 7 Wait five 5 minutes to clear out any gas If you then smell gas STOP Follow B in the in...

Page 18: ...within the range shown on the rating plate and the data in Table 6 After the temperature rise has been determined the CFM can be calcu lated as follows Direct Drive Blower All units have direct drive...

Page 19: ...as in your particular locality Contact your gas company for this information since it varies widely from city to city Table 19 Gas Rate Cubic Feet Per Hour1 Seconds for9 One Rev Size of Test Dial 1 2...

Page 20: ...VOLTAGE 19 2 VAC PREVENTING FURTHER RELAY OUTPUTS FOR 2 SECONDS LOW VOLTAGE 16 VAC STOPPED CURRENT RELAY OUTPUTS FOR 2 SECONDS LIQUID LINE SENSOR FAILURE OPEN OR SHORTED OUTDOOR AMBIENT SENSOR FAILUR...

Page 21: ...EVENTING FURTHER RELAY OUTPUTS FOR 2 SECONDS LOW VOLTAGE 16 VAC STOPPED CURRENT RELAY OUTPUTS FOR 2 SECONDS LIQUID LINE SENSOR FAILURE OPEN OR SHORTED OUTDOOR AMBIENT SENSOR FAILURE OPEN OR SHORTED CO...

Page 22: ...Manifold sets must be at least 700 psig high side and 180 psig low side with 550 psig retard All hoses must have a service pressure rating of 800 psig Leak detectors must be designed to detect HFC re...

Page 23: ...le timer Measured voltage L1 to L2 L2 to L3 L1 to L3 Total amperes L1 L2 L3 Compressor amperes L1 L2 L3 Measured voltage R and C outdoor unit control board Electrical Connections Inspection Check all...

Page 24: ...U H Measured BTU H Clock Gas Meter Nat Gas Supply Air Dry Bulb Temp Temp Rise Return Air Dry Bulb Temp Manifold Pressure at 100 Firing Rate w c Inlet Gas Pressure w c LP Gas Conversion Kit LP Conversi...

Reviews: