246796-YTG-D-0407

4

Unitary Products Group

HORIZONTAL SIDEWALL VENTING

For applications where vertical venting is not possible, the
only approved method of horizontal venting is the use of an
auxiliary power vent. Approved power venters are Fields
Controls Model SWG-4Y or the appropriate Tjernlund GPAK
model. Follow all application and installation details provided
by the manufacturer of the power vent. This unit may be hori-
zontally vented using 4” (10.2 cm) diameter pipe with a mini-
mum length of 4.5 feet (1.37 m) and a maximum length of
34.5 feet (10.82 m) with up to 4 elbows.

FILTER PERFORMANCE

The airflow capacity data published in Blower Performance
Tables above, represents blower performance WITHOUT fil-
ters. To determine the approximate blower performance of
the system, apply the filter drop value for the filter being used
or select an appropriate value from the Table below.

NOTE: 

The filter pressure drop values in Blower Perfor-

mance Tables are typical values for the type of filter listed and 
should only be used as a guideline. Actual pressure drop rat-
ings for each filter type vary between filter manufacturer.

NOTES: 

1. Air velocity through throwaway type filters may not exceed 300 
feet per minute. All velocities over this require the use of high 
velocity filters.

RECOMMENDED FILTER SIZES

CFM

Cabinet Size

Top Return (in)

1200

A

(2) 14 x 20

1600

B

(2) 14 x 20

1200

B

(2) 14 x 20

1600

C

(2) 14 x 20

2000

C

(2) 14 x 20

FILTER PERFORMANCE - PRESSURE DROP INCHES W.C. AND (KPA)

Airflow Range

Minimum 

Opening Size

Filter Type

Disposable

Washable Fiber

Pleated

CFM

 in

2

   

In W.C.

In W.C.

In W.C.

0 - 750

230

0.01

0.01

0.15

751 - 1000

330

0.05

0.05

0.20

1001 - 1250

330

0.10

0.10

0.20

1251 - 1500

330

0.10

0.10

0.25

1501 - 1750

380

0.15

0.14

0.30

1751 - 2000

380

0.19

0.18

0.30

2001 & Above

463

0.19

0.18

0.30

UNIT CLEARANCES TO COMBUSTIBLES

Application

Top

Front

Rear

Left

 Side

Right

 Side

Flue

Floor/ 

Bottom

Closet

Alcove

Attic

Line 

Contact

In.

In.

In.

In.

In.

In.

Downflow

1

6

0

0

3

6

1

1

Yes

Yes

Yes

No

Downflow B-Vent

1

3

0

0

0

1

1

1

Yes

Yes

Yes

No

Horizontal

1

6

0

0

3

6

Combustible

No

Yes

Yes

Yes

2

Horizontal B-Vent

1

3

0

0

0

1

Combustible

No

Yes

Yes

Yes

2

1

Special floor base or air conditioning coil required for use on combustible floor.

2

Line contact only permitted between lines formed by the intersection of the rear panel and side panel (top in horizontal position) of the furnace 
jacket and building joists, studs or framing.

Summary of Contents for PT8DH

Page 1: ...ce as allowed by the National Fuel Gas Code ANSI Z223 1 latest edition WARRANTY 20 year limited warranty on the heat exchanger 10 year heat exchanger warranty on commercial applica tions 5 year limited parts warranty FEATURES Two stage heating operation includes Two stage gas valve Two stage inducer operation This provides both increased comfort level and very quiet unit operation Delay timer allo...

Page 2: ...H11 2000 C 21 19 3 4 18 1 2 13 1 2 RATINGS PHYSICAL ELECTRICAL DATA MODEL Input High Low Output BTU H High Low Nominal Airflow Cabinet Width AFUE Blower Blower Size MBH MBH CFM In Hp Amps In PT8A12 N L 040DH11 57 42 46 34 1200 14 1 2 80 0 1 2 7 7 10 x 8 PT8A12 N L 060DH11 80 59 64 48 1200 14 1 2 80 0 1 2 7 7 10 x 8 PT8A12 N L 080DH11 80 59 64 48 1600 17 1 2 80 0 3 4 9 6 10 x 10 PT8B16 N L 080DH11 ...

Page 3: ...910 810 680 560 Low 980 970 960 930 890 830 760 680 550 450 PT8B16 N L 080DH11 High 2070 2000 1930 1850 1770 1670 1580 1470 1360 1250 Medium 1650 1630 1610 1560 1490 1420 1360 1270 1170 1040 Low 1410 1400 1370 1340 1320 1270 1210 1140 1050 950 PT8C16 N L 080DH11 High 1895 1812 1736 1624 1544 1437 1311 1153 1032 836 Medium 1726 1645 1581 1491 1412 1311 1192 1049 908 750 Low 1561 1493 1430 1373 1304...

Page 4: ...ween filter manufacturer NOTES 1 Air velocity through throwaway type filters may not exceed 300 feet per minute All velocities over this require the use of high velocity filters RECOMMENDED FILTER SIZES CFM Cabinet Size Top Return in 1200 A 2 14 x 20 1600 B 2 14 x 20 1200 B 2 14 x 20 1600 C 2 14 x 20 2000 C 2 14 x 20 FILTER PERFORMANCE PRESSURE DROP INCHES W C AND KPA Airflow Range Minimum Opening...

Page 5: ...ract the airflow 0 50 from the airflow 0 60 to obtain airflow difference 1170 1240 70 CFM 3 Subtract the total system static from 0 50 and divide this difference by the difference in ESP values in the table 0 60 0 50 to obtain a percentage 0 58 0 50 0 60 0 50 0 8 4 Multiply percentage by airflow difference to obtain airflow reduction 0 8 x 70 56 5 Subtract airflow reduction value from airflow 0 50...

Page 6: ...tion Light E W1 First Stage Heat G Fan G Fan Connection of the C Termainal 24 Volt Common is optional when used with batteries Thermostat Installer Setup Number 1 System Type must be set to 6 2 Heat 2 Cool Conventional R 24 Volt Hot Heat XFMR W2 Second Stage Heat RC 24 Volt Hot Cool XFMR E W1 First Stage Heat G Fan DN22U00124 THERMOSTAT Y2 Second Stage Cool Y2 Second Stage Cool Y First Stage Cool ...

Page 7: ...Bonnet Sensor Bonnet Sensor Optional BS Bonnet Sensor W2 Second Stage Auxiliary Heat W2 Second Stage Auxiliary Heat AUX Auxiliary Heat E W1 First Stage Auxiliary Heat E W1 First Stage Auxiliary Heat W Auxiliary Heat Y2 Second Stage Heat Cool Y2 Second Stage Heat Cool Y2 Second Stage Heat Cool Y2 Second Stage Heat Cool L Malfunction Light L Malfunction Light L Malfunction Light X L Malfunction Ligh...

Page 8: ...o change without notice Printed in U S A 246796 YTG D 0407 Copyright by York International Corp 2007 All rights reserved Supersedes 246796 YTG C 0806 Unitary 5005 Norman Products York OK Group Drive 73069 NOTES ...

Reviews: