036-21584-002 Rev. A (1205)

6

Unitary Products Group

For additional connection diagrams for all UPG equipment refer to “Low Voltage System Wiring” document available online at www.upgnet.com
in the Product Catalog Section.

Thermostat Chart - AC

AC10

2 Stage Scroll A/C w/ Variable Speed Furnace - PV8/9; (F,L)*8/9V, (G,L)*8/9V, XYG8V-*, XYF8V-*, XYG9V-*, XYF9V-*

*DN22U00124

THERMOSTAT

Y

First Stage Cool

R

24-Volt Hot (Heat XFMR)

C

24-Volt Common

THERMOSTAT

Connection of the "C" 

Termainal, 24-Volt 

Common, is optional 

when used with batteries

*PP32U70124

Y

First Stage Cool

Y2

Second Stage Cool

R

24-Volt Hot (Heat XFMR)

C

24-Volt Common

W/W1

Single/First Stage Heat

W2

Second Stage Heat

G

Fan

Thermostat Installer 

Setup Number 0170 - 

System Type - must be 

set to 8 - 2 Heat/2 Cool 

Multistage Conventional

G

Fan

G

Fan

E/W1

First Stage Heat

W2

Second Stage Heat

*PP32U72124

RC

24-Volt Hot (Cool XFMR)

E/W1

First Stage Heat

L

Malfunction Light

W2

Second Stage Heat

G

Fan

E/W1

First Stage Heat

Y2

Second Stage Cool

C

24-Volt Common

Y1

First Stage Cool

*DP22U70124

HM

Humidistat

DHM

Dehumidistat

VARIABLE SPEED

FURNACE CONTROL

R

24-Volt Hot

CFM CONTROL

W2

Second Stage Heat

Y1

First Stage Cool

*PP32U71124

THERMOSTAT

24V HUMIDIFIER

(Optional)

(X/L)

Malfunction Light

(O)

Reversing Valve– Energized in Cool

TWO STAGE

AIR CONDITIONING

Comfort Alert

Interface

HUM

Dehumidification - Open on Humidity Rise

C

24-Volt Common

C

24-Volt Common

R

24-Volt Hot

W2

Second Stage Heat

G

Fan

Y2

Second Stage Cool

E/W1

First Stage Heat

RC

24-Volt Hot (Cool XFMR)

Y1

First Stage Cool

R

24-Volt Hot

Y/Y2

Single/Second Stage Cool

Y2

Second Stage Cool

Y

First Stage Cool

Y2

Second Stage Cool

W2

Second Stage Heat

G

Fan

R

24-Volt Hot

W

First Stage Heat

R

24-Volt Hot

*DN22C00124

THERMOSTAT

Y2

Second Stage Cool

Y1

First Stage Cool

C

24-Volt Common

C

24-Volt Common

THERMOSTAT

Thermostat Installer Setup 

Number 15 - Compressor 

Protection - must be set to 5

( ) CONVENIENCE TERMINAL

NO FUNCTION IN THIS APPLICATION.

E2/P Switch must be in 

the E2 position and the 

Humidistat Jumper on 

CFM Control must be 

in the 'YES' position 

for Dehumidification

Step 1 of Thermostat User 

Configuration Menu 

must be set to MS 2

Connection of the "C" 

Termainal, 24-Volt Common, 

is optional 

when used with batteries

Step 16 of Thermostat 

User Configuration Menu 

must be set to ON to use 

Comfort Alert Features

Thermostat Installer Setup 

Number 1 - System Type - 

must be set to 6 - 2 

Heat/2 Cool Conventional

Connection of the "C" Termainal, 

24-Volt

Common, is optional 

when used with batteries

Connection of the "C" 

Termainal, 24-Volt 

Common, is optional 

when used with batteries

Step 1 of Thermostat User 

Configuration Menu must be 

set to MLTI STG

Summary of Contents for PV9A12N040UP11

Page 1: ...gas valve Two stage inducer operation Variable speed ECM blower operation Provides increased comfort level very quiet unit opera tion Adjustable delay timer allows two stage operation with single stage thermostat Compact easy to install ideal height 40 cabinet Blower off delay for cooling SEER improvement Easy to connect power control wiring Built in high level self diagnostics with fault code dis...

Page 2: ...TTOM IMAGE RETURN END TOP IMAGE SUPPLY END 1 1 2 GAS PIPE ENTRY 7 8 JUNCTION BOX HOLE T STAT WIRING 7 8 K O CONDENSATE DRAIN 7 8 K O CABINET AND DUCT DIMENSIONS Models Nominal CFM Cabinet Size Cabinet Dimension A in B in C in D in PV9A12N040UP11 1200 A 14 1 2 13 1 2 12 1 8 6 1 4 PV9B12N060UP11 1200 B 17 1 2 16 1 4 15 1 8 8 1 2 PV9B12N080UP11 1200 B 17 1 2 16 1 4 15 1 8 8 1 2 PV9C16N080UP11 1600 C ...

Page 3: ...om two sides or one side plus bottom ELECTRICAL AND PERFORMANCE DATA Models Input High Low Output High Low Nominal Airflow Cabinet Width Total Unit AFUE Air Temp Rise MBH MBH CFM In Amps F PV9A12N040UP11 40 26 38 24 1200 14 1 2 9 94 0 35 65 PV9B12N060UP11 60 39 56 36 1200 17 1 2 9 93 2 40 70 PV9B12N080UP11 80 52 75 49 1200 17 1 2 9 92 5 45 75 PV9C16N080UP11 80 52 75 49 1600 21 12 92 8 45 75 PV9C20...

Page 4: ... 1490 920 C A 1250 790 1290 790 D A 1310 810 1360 840 C C 1090 690 1140 690 D C HIGH LOW HEAT CFM 40 000 INPUT 3 Ton 60 000 INPUT 3 Ton JUMPER SETTINGS CFM CFM High Low High Low HEAT Tap ADJ Tap 1045 740 1110 710 A Any 905 645 960 640 B Any 825 595 870 600 C Any 765 590 830 570 D Any 80 000 INPUT 3 Ton 80 000 INPUT 4 Ton JUMPER SETTINGS CFM CFM High Low High Low HEAT Tap ADJ Tap 1330 880 1490 990 ...

Page 5: ...d upon the number of return air openings or return air opening size and add to the ESP from Step 3 to determine the total system static 5 If total system static matches a ESP value in the airflow table i e 0 20 0 60 etc the system airflow corre sponds to the intersection of the ESP column and Model Blower Speed row FILTER SIZES Input Output BTU H CFM Cabinet Size Side Return Filter in Bottom Retur...

Page 6: ...ight O Reversing Valve Energized in Cool TWO STAGE AIR CONDITIONING Comfort Alert Interface HUM Dehumidification Open on Humidity Rise C 24 Volt Common C 24 Volt Common R 24 Volt Hot W2 Second Stage Heat G Fan Y2 Second Stage Cool E W1 First Stage Heat RC 24 Volt Hot Cool XFMR Y1 First Stage Cool R 24 Volt Hot Y Y2 Single Second Stage Cool Y2 Second Stage Cool Y First Stage Cool Y2 Second Stage Co...

Page 7: ...2 Delay on furnace to OFF HM Humidistat BSG Bonnet Sensor Bonnet Sensor Optional BS Bonnet Sensor AUX Auxiliary Heat E W1 First Stage Auxiliary Heat E W1 First Stage Auxiliary Heat W Auxiliary Heat Y2 Second Stage Heat Cool DHM Dehumidistat HUM Dehumidification Open on Humidity Rise Y2 Second Stage Heat Cool Y2 Second Stage Heat Cool Y2 Second Stage Heat Cool Y 2 O Reversing Valve Energized in Coo...

Page 8: ...SIDE RETURN FILTER RACK 1SF0101 Fits all cabinet sizes Attaches to side of furnace cabinet in side return applications Holds any 16x25x1 permanent or disposable filter SIDE RETURN FILTER 1SR0302 All Models 1SR0200 All Models BOTTOM RETURN FILTER 1BR0114 or 1BR0214 For 14 1 2 cabinets 1BR0117 or 1BR0217 For 17 1 2 cabinets 1BR0121 or 1BR0221 For 21 cabinets 1BR0124 or 1BR0224 For 24 1 2 cabinets IN...

Reviews: